SRB-E-204ST / SRB-E-204PE

Operating instructions

Safety-monitoring module

EN

6.  Diagnostic

6.1  LED indications

LED Function

Display type

RUN

Ready for operation

Continuously lit

Not a valid application

Flashes

In 1/2

Inputs S12 and S22 closed

Continuously lit

Time window for synchronicity exceeded

Flashes quickly

Second channel has not opened

Flashes slowly

In 3/4

Inputs S32 and S42 closed

Continuously lit

Time window for synchronicity exceeded

Flashes quickly

Second channel has not opened

Flashes slowly

In 5/6

Inputs S52 and S62 closed

Continuously lit

Time window for synchronicity exceeded

Flashes quickly

Second channel has not opened

Flashes slowly

In 7/8

Inputs S72 and S82 closed

Continuously lit

Time window for synchronicity exceeded

Flashes quickly

Second channel has not opened

Flashes slowly

Out

Safety outputs ON

Continuously lit

SRB-E-204ST

Safety outputs waiting for start (input X2) Flashes slowly
Feedback circuit not closed (input X3)

Flashes slowly

SRB-E-204PE

Safety outputs waiting for input signals X2 
and X3

Flashes quickly

Single flashing of all LEDs with mains on

6.2  Malfunctions

Malfunctions and fault causes are displayed with the ERR-LEDs via 

short and long flashing signals

LED Error cause

Long flash Short flash

ERR

Operating voltage too low

1

1

Operating voltage too high

1

2

Invalid rotary switch setting

1

3

External voltage on output Q1

1

5, 7, 9

External voltage on output Q2

1
2

6, 8

1

Termination to GND on output Q1

2

2

Termination to GND on output Q2

2

3

Cross-wire between inputs S12 and S22

2

4

Cross-wire between inputs S32 and S42

2

5

Cross-wire between inputs S52 and S62

2

6

Cross-wire between inputs S72 and S82

2

7

Undefined level on outputs:

X2

3

4

X3

3

5

S12

2

9

S22

3

1

S32

3

2

S42

3

3

S52

3

6

S62

3

7

S72

3

8

S82

3

9

Rotary switch > 30 sec. to position C

6

8

LED Error cause

Long flash Short flash

ERR

Application changed and  
activation of operating voltage

LEDs flash quickly:

RUN, In 1/2, In 3/4, In 

5/6, In 7/8, Out

Application was changed during active 
operation

LEDs flash quickly:

ERR, In 1/2, In 3/4, In 

5/6, In 7/8, Out

Other fault codes:  
Consult technical sales dept. at Schmersal

7.  Wiring examples

7.1  Possible applications

All applications for 1 or 2-channel safe evaluation for protective 

equipment as follows:

•  Safety door monitoring to ISO 14119

•  Position switches with positive break to IEC 60947-5-1 

•  Safety sensors to IEC 60947-5-3

•  Emergency stop command devices to ISO 13850 and IEC 60947-5-5

•  Magnetic safety sensors to IEC 60947-5-3

•  Safety light curtain and photoelectric barriers according to IEC 61496

The connection of magnetic safety switches to the SRB-E-... 

safety-monitoring module is only admitted when the 

requirements of the standard IEC 60947-5-3 are observed.

As the technical data are regarded, the following minimum 

requirements must be met:

• 

Switching capacity: min. 240 mW

• Switching voltage: min. 24 VDC

• 

switching current: min. 10 mA

For example, the following safety sensors meet the 

requirements:

 BNS 36-02Z(G), BNS 36-02/01Z(G)

 BNS 260-02Z(G), BNS 260-02/01Z(G)

When sensors with LED are wired in the control circuit 

(protective circuit), the following rated operating voltage must 

be observed and respected:

• 24 VDC with a max. tolerance of –5%/+20%

Otherwise availability problems could occur, especially in 

series-wired sensors, where a voltage drop in the control 

circuit is triggered by LED's for instance.

Содержание SRB-E-204PE

Страница 1: ...ly with this warning notice could lead to physical injury and or damage to the machine Content 1 About this document 1 1 Function 1 1 2 Target group authorised qualified personnel 1 1 3 Explanation of the symbols used 1 1 4 Appropriate use 2 1 5 General safety instructions 2 1 6 Warning about misuse 2 1 7 Exclusion of liability 2 2 Product description 2 1 Ordering code 2 2 2 Special versions 2 2 3...

Страница 2: ...vasive work on the device as well as arbitrary repairs conversions and modifications to the device are strictly forbidden the manufacturer shall accept no liability for damages resulting from such invasive work arbitrary repairs conversions and or modifications to the device The safety relay module is to be operated in an area in which access by personnel is restricted 2 Product description 2 1 Or...

Страница 3: ...A Fuse rating of the signalling outputs internal electronic trip tripping current 100 mA Max switching cycles minute 60 Inductive consumers provision is to be made for suitable protective wiring for suppression Mechanical data Connection type refer to 2 1 Cable section refer to 2 1 Connecting cable rigid or flexible Tightening torque for the terminals 0 5 Nm Material of enclosure glass fibre reinf...

Страница 4: ...put channel 1 Input channel 2 In 7 8 High level at S72 S82 For flash code see section 6 1 Y1 Signalling output NO sensor 1 Y2 Signalling output NO sensor 2 Y3 Signalling output NO sensor 3 Y4 Signalling output NO sensor 4 Q1 Q2 Safety outputs Out Outputs activated For flash code see section 6 1 1 S11 S12 S21 S22 A1 A2 X3 X2 Q2 Q1 Y2 Y1 SRB E 204ST Out S31 S32 S41 S42 S72 S52 S51 Y3 S82 S62 S61 Y4 ...

Страница 5: ...es 1 4 NC NC No 9 Autostart No 1 4 NC NC Yes 10 Autostart No 1 4 NC NC No 11 Yes Yes Yes No No 1 2 3 4 NC NC No 12 Autostart Yes Yes No No 1 2 3 4 NC NC No 13 Yes Yes Yes Yes No 1 2 3 4 NC NC No 14 Autostart Yes Yes Yes No 1 2 3 4 NC NC No C Configuration mode SRB E 204PE Rotary knob position Reset button detection of the trailing edge Cross wire monitoring active Sensor Input Sensor configuration...

Страница 6: ... is deleted Lights up Flashes Flashes Flashes Setting cycle active Application 1 is deleted No valid application stored Flashes SRB E ready for new applications Select new application Select desired application 1 11 New application will be loaded Lights up Setting cycle active Lights up Lights up Lights up Lights up Lights up Lights up Lights up Lights up Lights up Ready for operation The desired ...

Страница 7: ...42 2 5 Cross wire between inputs S52 and S62 2 6 Cross wire between inputs S72 and S82 2 7 Undefined level on outputs X2 3 4 X3 3 5 S12 2 9 S22 3 1 S32 3 2 S42 3 3 S52 3 6 S62 3 7 S72 3 8 S82 3 9 Rotary switch 30 sec to position C 6 8 LED Error cause Long flash Short flash ERR Application changed and activation of operating voltage LEDs flash quickly RUN In 1 2 In 3 4 In 5 6 In 7 8 Out Application...

Страница 8: ...it Signalling outputs must not be used in safety circuits Wiring example SRB E 204ST 0V GND X3 A1 S22 S11 A2 S21 X2 Q1 Q2 Y1 S12 24VDC KA KB KA K B F1 S42 S31 S41 S32 KA KB S51 S52 S61 S62 S72 S82 Y2 Y3 Y4 R H2 a b c d e f d a a d d a Wiring example SRB E 204PE 0V GND X3 A1 S22 S11 A2 S21 X2 Q1 Q2 Y1 S12 24VDC F1 S42 S31 S41 S32 S51 S52 S61 S62 S72 S82 Y2 Y3 Y4 a b c d e f d a a d d a g Key a Safe...

Страница 9: ... Rotary knob position 12 Rotary knob position 13 Rotary knob position 14 7 4 Feedback circuit SRB E 204ST Suitable for increase in capacity or number of contacts by means of contactors or relays with positive guided contacts If the feedback circuit is not required establish a bridge X3 24VDC KB KA 7 5 Cascading SRB E 204PE Safety inputs X2 and X3 can be used for cascading of several SRB E 204PE mo...

Страница 10: ...DC S72 S82 S51 S61 Unrequired inputs S12 S32 S52 S72 must be switched to 24VDC or bridged to outputs S11 S21 S31 S41 S51 S61 Rotary knob position Function SRB E 204ST 5 Reset button detection of the trailing edge 6 Reset without monitoring autostart 8 Set up and maintenance 8 1 Commissioning The safety relay module features protection class IP54 for installation in a switch cabinet The safety rela...

Страница 11: ...e accumulation of faults then this must take place during the intervals noted as follows at least every month for PL e with category 3 or category 4 according to ISO 13849 1 or SIL 3 with HFT hardware fault tolerance 1 according to IEC 62061 at least every 12 months for PL d with category 3 according to ISO 13849 1 or SIL 2 with HFT hardware fault tolerance 1 according to IEC 62061 Damaged or defe...

Страница 12: ...rototype test certificate 01 205 5365 00 18 Person authorised for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal July 12 2018 Authorised signature Philip Schmersal Managing Director EU Declaration of conformity Original K A Schmersal GmbH Co KG Möddinghofe 30 42279 Wuppertal Germany Internet www schmersal com We hereby ...

Отзывы: