schmersal SRB 220XV2 V.2 Скачать руководство пользователя страница 5

5

SRB 220XV2 V.2

Operating instructions

Safety-monitoring module

EN

5.4  Setting report SRB 220 XV2 V.2

This report regarding the setting of the device must be completed 

accordingly by the customer and enclosed in the technical manual of 

the machine.

The setting report must be available whenever a safety check is  

performed.

Company:

The safety-monitoring module is used in the following machine:

Machine n°

Machine type

Module n°

Set drop-out delay:

Set on (date)

Signature of the responsible person

6.  Set-up and maintenance

6.1  Functional testing

The safety function of the safety-monitoring module must be tested. 

The following conditions must be previously checked and met:

1. Correct fixing

2. Check the integrity of the cable entry and connections

3.  Check the safety-monitoring module's enclosure for damage.

4.  Check the electrical function of the connected sensors and  

their influence on the safety-monitoring module and the  

downstream actuators

6.2  Maintenance

A regular visual inspection and functional test, including the following 

steps, is recommended:

1. Check the correct fixing of the safety-monitoring module

2. Check the cable for damages

3. Check electrical function

The device has to be integrated into the periodic check-ups 

according to the Ordinance on Industrial Safety and Health, 

however at least 1 × year.

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The safety-monitoring module must be disassembled in a de-energised 

condition only. Push up the bottom of the enclosure and hang out 

slightly tilted forwards.

7.2  Disposal

The safety-monitoring module must be disposed of in an appropriate 

manner in accordance with the national prescriptions and legislations.

8.  Appendix

8.1  Wiring examples

Dual-channel control, shown for a guard door monitor; with two 

contacts A and B, where at least one is a positive break contact; 

with external reset button 

J

 (see Fig. 7)

•  Relay outputs: Suitable for 2-channel control, for increase in capacity 

or number of contacts by means of contactors or relays with  

positive-guided contacts.

•  The control system recognises wire breakage, earth faults and  

cross-wire shorts in the monitoring circuit.

K2

K3

K4

F1

A1 S21 S22 S13

L1

N

K

B

K

C

K

B

K

A

K

A

K

A

K

D

K

B

K1

K2

K3

K4

S14

A2

S31 S32 S33 S34 Y39 Y40

K

C

K

D

13 23 37

a)

J

S

UB

K

D

K

C

K1

S11

S12

24 38

47

48

14

RT

Fig. 7

a) Channel control

 F2 = hybrid  fuse 50 mA / 800 mA

 

S

 = Feedback circuit

8.2  Start configuration

External reset button (with edge detection) (see Fig. 8)

•  The external reset button is integrated as shown.

•  The safety-monitoring module is activated by the reset (after release) 

of the reset button (= detection of the trailing edge). Faults in the reset 

button, e.g. welded contacts or manipulations which could lead to an 

inadvertent restart, are detected in this configuration and will result in 

an inhibition of the operation.

Automatic start (see Fig. 9)

•  The automatic start is programmed by connecting the feedback circuit 

to the terminals. If the feedback circuit is not required, establish a 

bridge.

•  Caution: Not admitted without additional measure due to the risk of 

gaining access by stepping behind!

•  Caution: Within the meaning of EN IEC 60204-1 paragraph 9.2.5.4.2 

and 10.8.3, the operating mode "automatic start" is only restrictedly 

admissible.  In particular, any inadvertent restart of the machine must 

be prevented by other suitable measures.

Due to the operating principle of the electronic fuse, the cus-

tomer must check that no hazard is caused by an unexpected 

restart in circuits without reset button (automatic reset).

J

S

S34

S33

K

B

K

A

S14

S

S13

K

B

K

A

Fig. 8

Fig. 9

Содержание SRB 220XV2 V.2

Страница 1: ...versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description To avoid EMC dist...

Страница 2: ...th the output contacts 13 14 and 23 24 meet the following requirements under observation of a B10D value assessment also refer to Requirements to DIN EN ISO 13849 1 control category 4 PL e to DIN EN I...

Страница 3: ...results in the below mentioned switching cycle times tcycle for the relay contacts Diverging applications upon request Contact load nop y tcycle 20 525 600 1 0 min 40 210 240 2 5 min 60 75 087 7 0 min...

Страница 4: ...saved in the SRB 220XV2 the voltage supply must be interrupted for approx 3 seconds ON ON SW1 SW2 1 1 2 2 3 3 4 4 Fig 3 New adjustable drop out delays and cross wire short monitoring for version V 2...

Страница 5: ...iptions and legislations 8 Appendix 8 1 Wiring examples Dual channel control shown for a guard door monitor with two contacts A and B where at least one is a positive break contact with external reset...

Страница 6: ...s between the control circuits are detected Control category 4 to EN 954 1 Category 4 PL e to DIN EN ISO 13849 1 possible Single channel guard door monitoring circuit with interlocking devices to EN 1...

Страница 7: ...s S feedback circuit If the feedback circuit is not required establish a bridge S33 S34 47 13 48 14 KB KA S L1 N KA KC S33 S34 47 13 48 14 KB KC KD KA KB L1 N KA KD KC S Fig 18 Fig 19 Differential con...

Страница 8: ...omponent SRB220XV2 V 2 Description of the component Safety monitoring module for emergency stop circuits and guard door monitoring Relevant Directives Machinery Directive EMC Directive RoHS Directive...

Отзывы: