5.9.7 Multiple break of protective field during muting cycle
This function increases the systems' availability for variable goods on a pallet. During the active muting cycle the
protective field is guarded and leads to an immediate stop of the muting cycle when no beam is interrupted.
This malfunction is triggered, i.e. when the means of conveyance with an irregular load of material does not damp
all active beams of the protective field for a time longer than 20 ms.
If this function is activated, no break of the muting cycle will occur due to non-damping the beams. The functionally
break is being realised by the respective configuration and as the case may be by the muting sensors.
Combining the parameters with ' shortened muting cycle' is not possible.
Those kind of restrictions will be indicated by the software's pop-up-windows.
After a new configuration the information are prepared for storage by activating the button
To prevent unintentional storage of the information, every intended storage processs must be confirmed by
clicking an additional button
within 10 seconds. If you click this button within the given period, the new configuration will be transmitted to
the safety light grid SLG 425I-P.
If you fail to press the button within the requested time, the information will be cancelled and the settings of
before your change will be stored.
After the data transmission the following confirmation appears. At the same time you will be asked to
save the configuration data as text file.
We urgently recommend to do so. At a later time you will thus be able to trace the configuration changes.
Click on the button (Ja / Yes) with the mouse pointer.
Now you can save the configuration settings on your PC/laptop.
Assembly of muting sensors
Page 12
Subject to technical changes
Save setttings
Confirm storage within 10 seconds
5.11 Muting applications
5.10 Storage of information
Safety light grid SLG 422/ 425I-P
Muting-Sensor
R e f l e c t o r
SLG 425 IP