schmersal SLC 425I Скачать руководство пользователя страница 9

9

EN

SLC 425I

Operating instructions

Safety light curtain

2.9.5 Saving the data

After the reconfiguration, the data to be saved are prepared by selec-

ting the button   "Save settings". To avoid unintentional saving of the 

data, every intentional save procedure must be confirmed by clicking an 

additional button

"Confirm within 10 seconds by clicking this button"

within 10 seconds

If the change is confirmed within 10 seconds, the new configuration 

is transferred to the SLC 425I safety light curtain. If it is not confirmed 

within this timeframe, the settings that were saved before the change 

was made will be maintained without any change.

After the data transmission, the following confirmation is displayed. You 

are simultaneously asked to save the configuration data in the form of 

a text file.

This saving procedure is recommended so that configuration changes 

can be reproduced at a later moment. Click the (yes) button with your 

mouse to confirm.

You now can save the configuration setting onto your PC or laptop.

2.9.6 Muting applications

Arrangement of the muting sensors

MS1

MS2

MS3

MS4

Material

Muting lamp

Belt

Reflektor
Muting Sensor

SLC 425I-E/R

Reflector
Muting sensor

SLC 425I-E/R

MS1

MS2

MS3 MS4

S

E

S3

S2

S1

S1

S2

Material

Carrier

Belt

S1 = distance of the inner MS to SF

S2 = distance between two MS

S3 = material length

MS 1 = muting sensor 1

MS 2 = muting sensor 2

MS 3 = muting sensor 3

MS 4 = muting sensor 4

BWS = ESD (electro-sensitive safety device)

S = transmitter; E = receiver

VB= belt speed (m/s)

Minimum distances muting sensors

For the evaluation of the signals (MS) in the control system, a minimum 

distance is required for the muting sensors.

The minimum signal length between the sensors, which are fitted 

closest to the SLC 425I, must be at least 50 ms. This corresponds to a 

minimum distance of 100 mm at a belt speed of 2.0 m/s.

The minimum signal length of the outer sensors must be over 50 ms. 

The signal propagation delay between the muting sensors may be 3 

seconds at the most (depending on the chosen setting).

The mounting distance of the inner sensors to the protection field of the 

SLC 425I must be chosen as small as possible.

The sensors (transmitter/receiver) of the SLC 425I must be fixed as 

close as possible to the conveyed material to avoid the creation of 

gaps. Otherwise, there is a risk that persons can slip between the 

material and the MS arrangement into the hazardous area during the 

muting cycle.

In case of different material widths, the gap between the sensors (trans-

mitter/receiver) of the SLC 425I and the material must be protected with 

an additional cover.

Muting with 2 sensors, parallel arrangement

The arrangement shows the muting application with two parallel 

arranged muting sensors. This arrangement enables the material to be 

transported in only one direction, out of the hazardous area.

MS1

MS2

S

E

S3

S2

S1

Hazardous area

Additional safety guard

Carrier

Belt

Material

S1 = distance MS 1 to SF

S2 = distance MS 1 to MS 2

S3 = material length

MS 1 = muting sensor 1

MS 2 = muting sensor 2

S = transmitter; E = receiver

VB= belt speed (m/s)

SF = protection field

S3 > S1 + S2

S1 = belt speed VB (m/s) * 0.05 s

The muting cycle is as follows:

MS2- MS1- SF- end

Selectable options:

Belt stop, override, protection ield area

Factory setting

Shortened muting cycle, i.e. the muting 

cycle is terminated when the protection ield 

is released.

This arrangement is only authorised when the muting sensors 

are installed inside the hazardous area.

Содержание SLC 425I

Страница 1: ...ning notice could lead to physical injury and or damage to the machine 1 4 Appropriate use The products described in these operating instructions are developed to execute safety related functions as part of an entire plant or machine It is the responsibility of the manufacturer of a machine or plant to ensure the correct functionality of the entire machinery or plant Content 1 About this document ...

Страница 2: ...applies to the following types SLC 425I E R RFBC No Option Description xxxx Protection field heights in mm available lengths 0170 0250 0330 0410 0490 0570 0650 0730 0810 0890 0970 1050 1130 1210 1290 1370 1450 1530 1610 1690 1770 14 30 Resolution 14 mm 30 mm Note only for resolution 30 mm Only if the information described in this operating instructions manual are realised correctly the safety func...

Страница 3: ...n in case of trailing edge Start interlock 250 1500 ms adjustable LED indications transmitter Transmitting status LED indications receiver OSSD ON OSSD OFF restart signal reception blanking multifunction Connection M12 Connector plug with metal thread receiver 8 pole transmitter 4 pole male Muting sensors 2 pc M8 3 pole Muting lamp M8 3 pole Ambient temperature 10 C 50 C Storage temperature 25 C 7...

Страница 4: ... LED OSSD OFF red LED restart yellow flashing 2 8 3 Contactor control EDM The contactor control monitors the controlled switching elements auxiliary contacts of the contactors of both outputs This monitoring is realised after each interruption of the protection field and prior to the restart enabling of the outputs In this way malfunctions of the relays are detected e g contact welding or contact ...

Страница 5: ...ial movement in the protec tion field e g material ejection or process controlled material move ment This extension of the object detection increases the resolution In this way the physical resolution changes into an effective resolution This effective resolution must be used to calculate the safety distance This effective resolution must be used to calculate the safety distance Calculation of the...

Страница 6: ...o the hazardous area In this way the material passes through the accesses and the protection field of the SLC 425I without disabling the outputs This function is only authorised for the above described application For other applications no warranty claims shall be accepted This document includes information for the adequate and proper by passing of the protection field of an ESD and is reserved to...

Страница 7: ...onverter must be connected to the SLC 425I and a PC or laptop Please use the NSR 0801 BUS converter manual for the connection Operating mode set up for muting mode After the correct connection of the muting sensors and the NSR 0801 the following parameters must be set by means of the PC software in the muting function menu field in accordance with your application Operating mode and transport dire...

Страница 8: ...tching on 24 VDC at pin 8 of the recei ver A status change of the muting sensors switching output when the function is active causes the muting function to be switched off The function is deactivated upon delivery The belt stop time can be set from 1 to 30 minutes Override This function enables bridging the outputs of the SLC 425I in case of failure voltage interruption material jamming The functi...

Страница 9: ...quired for the muting sensors The minimum signal length between the sensors which are fitted closest to the SLC 425I must be at least 50 ms This corresponds to a minimum distance of 100 mm at a belt speed of 2 0 m s The minimum signal length of the outer sensors must be over 50 ms The signal propagation delay between the muting sensors may be 3 seconds at the most depending on the chosen setting T...

Страница 10: ...erial transport in both directions The muting figure with each time 2 muting sensors shows a symmetri cal arrangement before and after the protection field of the SLC 425I 2 10 Operating mode cyclic operation 1 to 8 cycles are available They are selected by means of the PC software and the NSR 0801 The factory setting is two cycle operation and a 30 sec cycle time Adequate and appropriate applicat...

Страница 11: ...ptop Please use the NSR 0801 BUS converter manual for the connection Click with your mouse on the cyclic function field to select the cyclic function upon delivery the muting function is activated Therefore the muting function must be deactivated After selection of the cyclic function the following parameters must be set in the menu window Cycles The number of required operator interventions in th...

Страница 12: ...guard Approach speed Resolution of the safety light curtain Safety light curtain SLC 425I The safety distance for resolutions 14 mm up to 40 mm is calculated by means of the following formula 1 S 2000 mm s T 8 d 14 mm S Safety distance mm T Total reaction time machine run on time reaction time of the safety guard relays etc d Resolution of the safety light curtain The approach speed is covered wit...

Страница 13: ...3857 3 4 1 Minimum distance to reflecting surfaces During the installation of the safety light curtain the effects of reflecting surfaces must be taken into account In case of an incorrect installati on interruptions of the protection field could possibly not be detected which could lead to serious injuries The hereafter specified minimum distances with regard to reflecting surfaces metal walls fl...

Страница 14: ... 992 964 1028 SLC 425I E R0890 XX RFBC 890 1008 1072 1044 1108 SLC 425I E R0970 XX RFBC 970 1088 1152 1124 1188 SLC 425I E R1050 XX RFBC 1050 1168 1232 1204 1268 SLC 425I E R1130 XX RFBC 1130 1248 1312 1284 1348 SLC 425I E R1210 XX RFBC 1210 1328 1392 1364 1428 SLC 425I E R1290 XX RFBC 1290 1408 1472 1444 1508 SLC 425I E R1370 XX RFBC 1370 1488 1552 1524 1588 SLC 425I E R1450 XX RFBC 1450 1568 163...

Страница 15: ...Relay for processing the switching outputs OSSD 1 OSSD 2 MK Machine contact belt stop optional S1 Command device button for enabling restart override E1 Power supply 24 VDC 10 4 1 1 Connector configuration Receiver Transmitter Cable Muting Mode RECEIVER SLC connector male M12 8 pole Signal Designation Description 5 8 4 3 2 1 7 6 1 WH Release Override Input 2 BN 24 VDC Power supply 3 GN OSSD 1 Safe...

Страница 16: ...en the function is activated S1 Command device for restart E1 Power supply 24 VDC 10 Upon delivery the contactor control function is deactivated The function is activated by means of the NSR0801 BUS converter and the PC software 4 2 1 Connector configuration Receiver Emitter Cable Cyclic operation RECEIVER SLC Connector male M12 8 pol Signal Designation Description 5 8 4 3 2 1 7 6 1 WH Start butto...

Страница 17: ...I and the machine must be known in order to be able conducting an inspection If the fitter the planning technician and the operator are different persons please make sure that the user has the necessary information at his disposal to be able conduct the maintenance 5 3 Regular check A regular visual inspection and functional test including the following steps is recommended 1 The safety light curt...

Страница 18: ...ting for signal at output WA Restart only for cyclic operation ON Request actuation of the start button Request refer to start condition Flashing 2 Hz Request for operator intervention Flashing 0 25 Hz Check machine contact Signal reception ON flashing Signal reception too low check alignment and installation height between transmitter and receiver cleaning the black profile cover OFF Alignment be...

Страница 19: ...n i e locking Check the configuration settings by means of the NSR 0801 BUS converter repeat the teach process with blanking 6 3 Extended diagnostic By means of the optional configuration software and the NSR 0801 BUS converter an extended diagnostic can be executed The software provides the status information of the component and can represent the individual light lines This feature enables an op...

Страница 20: ... 30 42279 Wuppertal Notiied body for the prototype test TÜV Nord Cert GmbH Langemarckstr 20 45141 Essen ID n 0044 EC prototype test certiicate n 44 205 10 555867 005 Safety Control GmbH Am Industriepark 33 D 84453 Mühldorf Inn Telefon 49 0 86 31 187 9 60 Telefax 49 0 86 31 187 9 61 E Mail info safetycontrol com Place and date of issue Wuppertal February 1 2010 Authorised signature Christian Sprang...

Отзывы: