Operating instructions

Safety light curtain / safety light grid

EN

Safety distance to the hazardous area

Limit of the hazardous point

Safety distance (S)

Protection field marking

Tool - upper part

Signal to stop the  

hazardous movement
Standstill of the hazardous 

movement

t

n

 = t

B

 - t

A

Tool - lower part

tA

S

tB

 75 mm = max. distance for protection against stepping over

To prevent persons from stepping over the protection field

this dimension must be imperatively respected and observed.

Safety distance for multi-beam version SLG 220 (beam distance 

300, 400 and 500 mm)

S

Hazardous point

Transmitter

Receiver

Command device

Authorised operation

Mechanical protection

Direction from which the 

hazardous area is accessed

The protection using individual beams must be chosen so that bodies or 

body parts larger than the selected resolution (beam di beam 

diameter 10 mm) of the SLG 220 are detected.

The safety distance is the minimum distance between the SLG 220 and 

the hazardous point, which must be observed in order to ensure that 

the hazardous point can only be reached after the hazardous move-

ment has come to standstill.

Calculation of the safety distance for the multi-beam light grid:

S = ( 1600 mm/s * T ) + 850 mm

S = Safety distance [mm]

T = Stopping time of the m reaction time of the safety light grid

K = Approach speed 1600 mm/s

C = Safety supplement 850 mm

Example:

Reaction time of the SLG 220 = 12 ms

Stopping time of the machine T = 170 ms

S = 1600 mm/s * (170 ms + 12 ms) + 850 mm

S = 1141 mm

The following mounting heights to EN 999 must be observed:

Number of 

beams

Mounting height above reference floor

(Floor) in mm

2

400, 900

3

300, 700, 1100

4

300, 600, 900, 1200

The successor standards of the EN 999 for calculating the 

minimum distances of the safety guards with regard to the 

hazardous point are EN ISO 13855 and EN ISO 13857.

3.4.1 Minimum distance to reflecting surfaces

During the installation, the effects of reflecting surfaces must be taken 

into account. In case of an incorrect installation, interruptions of the 

protection field could possibly not be detected, which could lead to 

serious injuries. The hereafter-specified minimum distances with regard 

to reflecting surfaces (metal walls, floors, ceilings or parts) must be 

imperatively observed.

a= 262 mm

Access direction

Receiver

Obstacle

optical axis

Transmitter

reflecting body

(e.g. material container)

Limit of the hazardous point

a=262mm

Table: Safety distance a

a [mm]

D [m]

0

3

5

10

100

200

300

400

500

600

700

800

900

1000

15

20

The effective aperture angle for the SLC/SLG 220 series is ± 4.0° for 

a mounting distance of > 3.0 m. Calculate the minimum distance to 

reflecting surfaces as a function of the distance with an aperture angles 

of ± 5.0° degrees or use the value from the table below:

The correct combination (type, resolution) of transmitter and 

receiver always must be taken into consideration. If this is 

not observed, this could result in incorrect operation of the 

devices due to mutual interference.

Distance [m] between  

transmitter and receiver

Minimum distance a 

[mm]

0.2 … 3.0

262

4

350

5

437

6

525

Formula: 

a = tan 5° x L [mm]

a = Minimum distance to reflecting surfaces

L = Distance between transmitter and receiver

Содержание SLC 220

Страница 1: ...ct description 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailin...

Страница 2: ...nge 0 3 m 6 m H Range 5 m 30 m high range M Master function S Slave function Only if the information described in this operating instruc tions manual are realised correctly the safety function and the...

Страница 3: ...l reset 20 ms 1 0 s signal trans mission in case of trailing edge Start interlock 250 ms 1500 ms adjustable LED indications transmitter Transmitting status restart LED indications receiver OSSD ON OSS...

Страница 4: ...ton 2 8 3 Fixed blanking The SLC 220 can blank stationary parts in the protection field Multiple protection field areas can be blanked Fixed blanking area E1 R1 The range of the fixed blanking can be...

Страница 5: ...nsion is possible up to max 96 lines and a pro tection field height of 2 45 m with the same resolution The connection of the systems master and slave is realised with the pre wired connector KA 0907 3...

Страница 6: ...the following elements Stopping time of the machine calculation by run on time measure ment Response time of the machine and the safety light curtain and the downstream relay entire safety guard Appr...

Страница 7: ...41 mm The following mounting heights to EN 999 must be observed Number of beams Mounting height above reference floor Floor in mm 2 400 900 3 300 700 1100 4 300 600 900 1200 The successor standards of...

Страница 8: ...2 1289 1 8 SLC 220 E R1375 30 RFB 1375 0 8 1422 1 5 1439 2 0 SLC 220 E R1525 30 RFB 1525 0 8 1572 1 5 1589 2 0 SLC 220 E R1675 30 RFB 1675 0 8 1722 1 5 1739 2 0 All versions with resolution 30 and 80...

Страница 9: ...fety light curtain safety light grid EN Accessories Mounting kit MS 1000 5 5 5 14 25 39 27 46 5 5 8 35 20 Centre support MS 1010 3 8 19 1 42 4 38 1 38 1 43 2 46 5 27 20 30 43 12 8 19 2 5 5 3 5 R 2 5 C...

Страница 10: ...RS485 B grey 24V brown 0V blue RS485 A pink RS485 B grey Signal quality white 24V brown 0V blue OSSD2 yellow OSSD1 green Earth connection Restart interlock active this connection is omitted connect S2...

Страница 11: ...ies Conditions For safety reasons all inspection results must be archived The operat ing principle of the SLC SLG and the machine must be known in order to be able conducting an inspection If the fitt...

Страница 12: ...D OFF contactor control input must show 24V Switch on only after POWER OFF ON 1 flashes Receiver configuration error or communication error Check transmitter and receiver configuration reparameterize...

Страница 13: ...manner in accordance with the national prescriptions and legislations 8 Appendix 8 1 Contact Consultancy Sales K A Schmersal GmbH Industrielle Sicherheitsschaltsysteme M ddinghofe 30 D 42279 Wuppertal...

Страница 14: ...h Loss M ddinghofe 30 42279 Wuppertal Notiied body for the prototype test T V Nord Cert GmbH Langemarckstr 20 45141 Essen ID n 0044 EC prototype test certiicate n 44 205 10 555867 004 Safety Control G...

Отзывы: