21
4
If Praxi 100 X AC drive is the last device on the bus, the bus termination must be set. Locate the
DIP switches to the top of the control unit (see figure below).
Turn the right most switch to position “1”. Biasing is built in the
termination resistor. See also step 6.
NOTE:
When planning the cable runs, remember to keep the
distance between the fieldbus cable and the motor cable at a
minimum of 30 cm.
5
The bus termination must be set for the first and the last device of the fieldbus line. See picture below and step 4. We
recommend that the first device on the bus and, thus, terminated, was the Master device.
Modbus RTU
= Bus termination
Termination
activated
Termination
activated
with
DIP switch
Termination
deactivated
Praxi 100 Praxi 100 Praxi 100 Praxi 100
Praxi 100