Operating instructions

Safety sensor

EX-BNS 250-2187

EN

4.  Electrical connection

4.1  General information for electrical connection

The electrical connection may only be carried out by author-

ised personnel in a de-energised condition.

The safety sensors must be wired in accordance with the specified wire 

colours.

4.2  Contact variants

The contact position shows the actuated sensor function when the 

safety guard is closed.

1 NO contact / 2 NC contact

EX-BNS 250-12Z-2187-3G/D

GY 13

GN 21

WH 31

14 PK
22 YE
32 BN

4.3  Connection

For safety-monitoring modules with antivalent inputs, the wires of the 

safety sensor must be wired as follows:

NO contacts: GY (13) und PK (14) 

at the "NO input" of the safety-

monitoring module

NC contacts: GN (21) und YE (22)

at the "NC input" of the safety-

monitoring module

NC contacts: WH (31) und BN (32)

can be used for signalling 

purposes.

In this way, the coding of the safety sensor is ensured.

5.  Set-up and maintenance

5.1  Functional testing

The safety function of the safety components must be tested. The fol-

lowing conditions must be previously checked and met: 

1. The installation is executed according to the instructions

2. The connection is executed correctly

3. The safety component is not damaged

4.  The system is free of dirt and soiling (in particular metal chips)

5.  Check cable entry and connections in a  de-energised condition

5.2  Maintenance

In the case of correct installation and adequate use, the safety sensor 

features maintenance-free functionality. A regular visual inspection and 

functional test, including the following steps, is recommended: 

• Check the fitting of the sensor and the actuator

• Remove possible metal chips

• Check the cable for damage.

•  Check cable entry and connections in de-energised condition

Damaged or defective components must be replaced.

6.  Disassembly and disposal

6.1  Disassembly

The safety switchgear must be disassembled in a de-energised condi-

tion only.

6.2  Disposal

The safety switchgear must be disposed of in an appropriate manner in 

accordance with the national prescriptions and legislations.

Содержание EX-BNS 250-2187

Страница 1: ...anufac turer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instruc tions manual the country specific installation standards as well as all prevailing safety regulations and accident prevention rules Further technical information can be found in ...

Страница 2: ...safety monitoring module is technically possible To connect multiple safety sensors check if au thorised the NC contacts of channel 1 are wired in series and the NC contacts of channel 2 are wired in series The channels 1 and 2 must be wired separatedly to the safety monitoring module Recommended suitable safety monitoring modules The following safety monitoring modules of the AES AZR and SRB seri...

Страница 3: ...spacer must be used The use of non magnetic fixing screws is rec ommended as well Do not subject the safety sensor and actuator to extreme vibrations and shocks Keep away from metal chips The mounting distance between two sensors should always be at least 50 mm Please observe the specifications for the maximum impact energy in the technical data 3 2 Dimensions All measurements in mm Safety sensor ...

Страница 4: ...maintenance 5 1 Functional testing The safety function of the safety components must be tested The fol lowing conditions must be previously checked and met 1 The installation is executed according to the instructions 2 The connection is executed correctly 3 The safety component is not damaged 4 The system is free of dirt and soiling in particular metal chips 5 Check cable entry and connections in ...

Страница 5: ...vant EC Directives 2006 42 EC EC Machinery Directive 94 9 EC EC Explosion Protection Directive ATEX Person authorized for the compilation of the technical documentation Oliver Wacker Möddinghofe 30 42279 Wuppertal Place and date of issue Wuppertal September 24 2012 Authorised signature Philip Schmersal Managing Director EC Declaration of conformity Translation of the original Declaration of Confor...

Страница 6: ...o KG Industrielle Sicherheitsschaltsysteme Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Отзывы: