AZS 2305

Operating instructions

Fail-safe delay timer

EN

8.2  Integral System Diagnostics (ISD)

The safety monitoring modules LED display to show the different 

switching conditions and faults. The following tables show the different 

switching conditions.

Tables switching condition indication

Diagnostic LED

System condition

The LED is red.

Comparison time value channel I with time 
value channel II faulty (setting coding and 
sliding switches)

The LED is green.

Enabling paths closed

LED flashes yellow  
(0.5 Hz)

Input signal in starting position,  
enabling paths opened

The yellow LED is flas-
hing (refer to table 2).

Time rating realised, maximum residual 
time value can be derived from table 2

Table error indications

Indication (orange) 

LED

Error

Cause

1 impulse

Input signal S14/
S22 at S1

Feeder cable for signal 
input S1 defective;
Error during signal 
change*

2 impulses

Time processing

Time value channel I 
too high

3 impulses

Time processing

Time value channel II 
too high

4 impulses

Interference at 
inputs, no safe 
evaluation

Too high capacitive or 
inductive interference 
at the inputs or the 
supply voltage lead

5 impulses

One or both relays 
did not close within 
the monitoring time

Too low operating 
voltage U

e; 

Defective relay

6 impulses

Relays not deacti-
vated upon signal 
change

Welded relay contact

7 impulses

Dynamic monitoring 
of both channels 
(cross-monitoring) 
failure

Internal data transmis-
sion interrupted

*  Signal change:  

The signal change has only occurred at one input or the signal change 

has occurred at both inputs with intervals of over 5 seconds.

Deleting the error message

The fault message is deleted once the fault has been rectified and after 

the input signal S1 has been switched to starting position to check the 

various functions.