Operating instructions

Safety switch with interlocking function

AZM 200D

EN

6.  Set-up and maintenance

6.1  Functional testing

The safety function of the safety components must be tested. The 

following conditions must be previously checked and met:

1. Fitting of the safety switch and the actuator

2. Check the integrity of the cable entry and connections

3. Check the switch enclosure for damage

6.2  Maintenance

We recommend a regular visual inspection and 

functional test, including the following steps:

1. Check the fixing of the safety switch and the actuator

2. Remove particles of dust and soiling

3. Check cable entry and connections

Damaged or defective components must be replaced.

7.  Disassembly and disposal

7.1  Disassembly

The safety switchgear must be disassembled in a de-energised 

condition only.

7.2  Disposal

The safety switchgear must be disposed of in an appropriate  

manner in accordance with the national prescriptions and legislations.

8.  Appendix

8.1  Wiring example

The application examples shown are suggestions. They however do not 

release the user from carefully checking whether the switchgear and its 

set-up are suitable for the individual application.

SPS/PLC

OUT3

OUT1

OUT2

Y1

Y2

OUT

GND

24V

24V

Y3

Y4

IN

GND

24V

AZM 200.-T-1P2P.

SRB

IN3

IN1

IN2

SRB

S12

A1

S22

A2

+24VDC

0V

S12

A1

S22

A2

+24VDC

0V

Содержание AZM 200D

Страница 1: ...re machine or plant The safety switchgear must be exclusively used in accordance with the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country ...

Страница 2: ...control category 3 or opened PL e control category 4 and maintaining the safe switched off condition of the safety outputs for as long as the safety guard is open Interlocks with power to lock principle may only be used in special cases after a thorough evaluation of the accident risk since the safety guard can be opened immediately on failure of the power supply or upon activation of the main swi...

Страница 3: ... Any mounting position The mounting position however must be chosen so that the ingress of dirt and soiling in the used opening is avoided The unused actuator opening must be sealed by means of the dust proof flap included in delivery Please observe the remarks of the standards EN ISO 12100 EN 953 and EN 1088 The constructor must provide for the necessary strain relief of the connections Admissibl...

Страница 4: ...rol In the power to unlock version of the AZM 200 the safety switch is unlocked when the IN signal 24V is set In the power to lock version of the AZM 200 the safety switch is locked when the IN signal 24 V is set 5 1 Safety switch with diagnostic output Mode of operation of the safety outputs The unlocking of the safety switch causes the safety outputs Y3 and Y4 to be disabled As long as the actua...

Страница 5: ...f On 24 V 24 V 24 V 0 V 24 V Error warning1 solenoid interlock locked 0 V 24 V On Flashes 2 On 24 V1 24 V1 24 V 0 V 0 V Error 0 V 24 V 24 V 0 V On Flashes 2 Off 0 V 0 V 24 V 0 V 0 V 1 after 30 min disabling due to fault 2 refer to flash code Table 2 flash codes red LED Flash codes red Designation Autonomous switch off after Error cause 1 flash pulse Error warning at output Y1 30 min Fault in outpu...

Страница 6: ...tor 2 Remove particles of dust and soiling 3 Check cable entry and connections Damaged or defective components must be replaced 7 Disassembly and disposal 7 1 Disassembly The safety switchgear must be disassembled in a de energised condition only 7 2 Disposal The safety switchgear must be disposed of in an appropriate manner in accordance with the national prescriptions and legislations 8 Appendix...

Страница 7: ...trol 8 PK 8 OR shielded RD LED LED 9 9 Button Input output 10 10 Button Input output 11 11 NC 12 12 Connector plug ST1 M23 8 1 pole Connector plug ST2 M12 8 pole Connector plug ST3 M23 12 pole 1 2 9 3 4 5 6 7 8 5 8 4 3 2 1 7 6 10 12 11 9 8 7 6 5 4 3 2 1 Connecting cables with female connector IP67 M23 8 1 pole 8 x 0 75 mm Connecting cables with female connector IP67 M12 8 pole 8 x 0 23 mm Connecti...

Страница 8: ...ions Relevant Directives Machinery Directive EMC Directive RoHS Directive 2006 42 EC 2014 30 EU 2011 65 EU Applied standards EN 60947 5 1 2004 AC 2005 A1 2009 EN 60947 5 3 2013 ISO 14119 2013 EN ISO 13849 1 2008 AC 2009 EN 61508 Teile 1 7 2010 EN 62061 2005 AC 2010 A1 2013 Notified body for the prototype test TÜV Rheinland Industrie Service GmbH Alboinstr 56 12103 Berlin ID n 0035 EC prototype tes...

Отзывы: