Operating instructions

Safety-monitoring module

AES 2285

EN

1.6  Warning about misuse

In case of inadequate or improper use or manipulations of  

the safety-monitoring module, personal hazards or damages 

to machinery or plant components cannot be excluded.  

The relevant requirements of the standards ISO 14119  

and ISO 13850 must be observed.

1.7  Exclusion of liability

We shall accept no liability for damages and malfunctions resulting from 

defective mounting or failure to comply with this operating instructions 

manual. The manufacturer shall accept no liability for damages result-

ing from the use of unauthorised spare parts or accessories.

For safety reasons, invasive work on the device as well as arbitrary re-

pairs, conversions and modifications to the device are strictly forbidden; 

the manufacturer shall accept no liability for damages resulting from 

such invasive work, arbitrary repairs, conversions and/or modifications 

to the device.

The safety-monitoring module must only be used when the enclosure is 

closed, i.e. with the front cover fitted.

2.  Product description

2.1  Ordering code

This operating instructions manual applies to the following types:

AES 2285

Only if the information described in this operating instructions 

manual are realised correctly, the safety function and therefore 

the compliance with the Machinery Directive is maintained.

2.2  Special versions

For special versions, which are not listed in the order code below 2.1, 

these specifications apply accordingly, provided that they correspond to 

the standard version.

2.3  Destination and use

The safety-monitoring module for integration in safety circuits is 

designed for fitting in control cabinets. It is used for the safe evaluation 

of the signals of positive break position switches for safety functions 

or magnetic safety sensors on sliding, hinged and removable safety 

guards as well as emergency stop control devices. Up to 6 safety 

guards can be monitored by means of the AES 2285 safety-monitoring 

module.

Design

The safety-monitoring module has a multichannel structure. It includes 

safety relays with monitored positive action contacts. The NO contacts  

of the relays, which are wired in series, build the enabling contacts.  

6 signalling outputs signal the position of the corresponding safety guard.

The entire concept of the control system, in which the 

safety component is integrated, must be validated to the 

relevant standards.

2.4  Technical data

General data:

 

Standards:

 

IEC 60204-1, IEC 60947-5-1, IEC 60947-5-3,  

ISO 13849-1, IEC 61508,  

BG-GS-ET-14, BG-GS-ET-20 

Climate resistance:

 

EN 60068-2-78

Mounting:

 

snaps onto standard DIN rail to EN 60715

Terminal designations:

 

IEC 60947-1

Material of the housings:

 

Plastic, glass-fibre reinforced  

thermoplastic, ventilated

Material of the contacts:

 

AgCdO, self-cleaning, positive drive

Weight:

 

300 g

Start conditions:

 

Automatic or start button 

Feedback circuit (Y/N):

 yes

Pull-in delay for automatic start:

 

typ. 120 ms

Pull-in delay with reset button:

 

typ. 30 ms

Drop-out delay in case of emergency stop:

 

typ. 20 ms / max. 35 ms

Drop-out delay on "supply failure":

 

On request

Mechanical data:

 

Connection type:

 

Screw connection

Cable section:

 

min. 0.25 mm² / max. 2.5 mm²

Connecting cable:

 

rigid or flexible

Tightening torque for the terminals: 

 

0.6 Nm

With removable terminals (Y/N):

 yes

Mechanical life:

 

10 million operations

Electrical life: 

 

Derating curve available on request

Resistance to shock:

 

10 g / 11 ms

Resistance to vibrations  

 

to EN 60068-2-6:

 

10 ... 55 Hz,  

amplitude 0.35 mm

Ambient conditions:

 

Ambient temperature:

 

– 25 °C … +45 °C

Storage and transport temperature:

 

–40 °C … +85 °C

Protection class:

 

Enclosure: IP40  

Terminals:  IP20  

Clearance: IP54

Degree of pollution:

 2

EMC rating: 

 

to EMC Directive

Electrical data:

 

Contact resistance in new state: 

 

max. 100 mΩ

Power consumption:

 

max. 3.6 W / 6.6 VA

Rated operating voltage U

e

:

 

24 VDC –15%/+20%,  

residual ripple max. 10%

Rated operating current I

e

:

 

0.125 A

Rated insulation voltage U

i

:

 

250 V

Rated impulse withstand voltage U

imp

:

 

4 kV

Thermal test current I

the

:

 

6 A

Fuse rating for the operating voltage: 

 

F1: internal electronic trip,  

tripping current > 1 A; reset after  

disconnection of the supply voltage 

Monitored inputs:

 

Cross-wire detection (Y/N): 

 

Yes

Wire breakage detection (Y/N): 

 

Yes

Earth leakage detection (Y/N): 

 

Yes

Number of NO contacts:

 

1 … 6

Number of NC contacts:

 

1 … 6

Cable length:

 

1,500 m with 1.5 mm², 

2,500 m with 2.5 mm²

Conduction resistance:

 

max. 40 Ω

Outputs:

 

Number of safety contacts:

 2

Number of auxiliary contacts:

 1

Number of signalling outputs:

 6

Содержание AES 2285

Страница 1: ... the versions listed below or for the applications authorised by the manufacturer Detailed information regarding the range of applications can be found in the chapter Product description 1 5 General safety instructions The user must observe the safety instructions in this operating instructions manual the country specific installation standards as well as all prevailing safety regulations and acci...

Страница 2: ... NO contacts of the relays which are wired in series build the enabling contacts 6 signalling outputs signal the position of the corresponding safety guard The entire concept of the control system in which the safety component is integrated must be validated to the relevant standards 2 4 Technical data General data Standards IEC 60204 1 IEC 60947 5 1 IEC 60947 5 3 ISO 13849 1 IEC 61508 BG GS ET 14...

Страница 3: ... and the insulation of the feed cables must be designed for the highest voltage which can occur in the device Wiring examples see appendix 5 Operating principle and settings 5 1 Operating principle after the operating voltage is switched on With the guard door closed or the emergency stop command devices unlocked the enabling paths are closed as soon as the start button is pushed During the start ...

Страница 4: ...1x year Damaged or defective components must be replaced 7 Disassembly and disposal 7 1 Disassembly The safety monitoring module must be disassembled in a de energised condition only Push up the bottom of the enclosure and hang out slightly tilted forwards 7 2 Disposal The safety monitoring module must be disposed of in an appropriate manner in accordance with the national prescriptions and legisl...

Страница 5: ...l of magnetic safety switches according to IEC 60947 5 3 see Fig 5 The control system recognises wire breakage and earth faults in the control circuit Cross wire shorts between the control circuits are detected Category 3 PL d to ISO 13849 1 possible EMERGENCY STOP Door switches Magnetic reed switches S11 S22 S11 S74 S12 S74 S73 S73 S31 S42 S31 S84 S32 S84 S83 S83 S51 S62 S51 S94 S52 S94 S93 S93 A...

Страница 6: ...2 S11 S22 NO contacts 1 S73 S74 NO contacts 2 S73 S74 Bridges S31 S32 S42 S51 S52 S62 Number of sensors to be monitored 3 Pin configuration NC contacts 1 S11 S12 NC contacts 2 S11 S22 NC contacts 3 S31 S32 NO contacts 1 S73 S74 NO contacts 2 S73 S74 NO contacts 3 S83 S84 Bridges S31 S42 S51 S52 S62 Number of sensors to be monitored 4 Pin configuration NC contacts 1 S11 S12 NC contacts 2 S11 S22 NC...

Страница 7: ...85 Description of the component Safety monitoring module for emergency stop circuits guard door monitoring and magnetic safety switches Relevant Directives Machinery Directive EMC Directive RoHS Directive 2006 42 EC 2014 30 EU 2011 65 EU Applied standards DIN EN 60947 5 3 2014 EN ISO 13849 1 2008 DIN EN ISO 13849 2 2013 Notified body for the prototype test DGUV Test Prüf und Zertifizierungsstelle ...

Страница 8: ... A Schmersal GmbH Co KG Möddinghofe 30 D 42279 Wuppertal Postfach 24 02 63 D 42232 Wuppertal Phone 49 0 2 02 64 74 0 Telefax 49 0 2 02 64 74 1 00 E Mail info schmersal com Internet http www schmersal com ...

Отзывы: