Floor Sensor Calibration
This option allows you to calibrate the floor sensor.
You should calibrate the sensor if the temperature reading differs from the actual
floor temperature.
Note that changes in the floor sensor characteristics may damage certain floors.
You can calibrate the sensor with +/- 10°C in steps of 0.5°C in the following way:
1. Tap the “
Menu
” button on the home screen.
2. Then tap the “
Engineer Settings
” button.
3. Scroll down and tap the “
Floor Sensor Calibration
” button.
4. Confirm that you want to calibrate the sensor with “
√
” or cancel with “
X
”.
5. If “
√
” is chosen, you must then offset the thermostat to reflect the floor
temperature actually measured.
6. Use the “
Up Arrow
” or “
Down Arrow
” button to set the measured floor
temperature.
7. Confirm the value with “
√
”. A confirmation screen will be displayed briefly.
8. The thermostat will automatically return to “
Engineer Settings
”.