10.4.6 Room Sensor Calibration
This option allows you to calibrate the room sensor.
You can calibrate the sensor if the temperature reading differs from the actual room
temperature.
Note that changes in room sensor characteristics may damage certain floors.
You can calibrate the sensor with ±17°F or ±10°C in steps of 1°F or 0.5°C in the
following way:
1. Tap the “
Menu
” button on the home screen.
2. Then tap the “
Installer Settings
” button to access the various installer settings.
3. Tap the “
Room Sensor Calibration
” button.
4. Use the “
Arrow Up
” or “
Arrow Down
” button to set the room temperature
actually measured.
5. Confirm that you want to calibrate the sensor with “
√
” or cancel with “
X
”.
If the temperature is confirmed with “√”, a confirmation screen will be displayed
briefly.
The thermostat will automatically return to “
Installer Settings
”.