
PAGE 55
© 2015. All rights reserved. Used under license by Schlüter-Systems L.P.
10.4.5 Floor Sensor Calibration
This option allows you to calibrate the floor sensor.
You can calibrate the sensor if the temperature reading differs from the actual floor
temperature.
Note that changes to floor sensor characteristics may damage certain floors.
You can calibrate the sensor with ±17°F or ±10°C in steps of 1°F or 0.5°C in the
following way:
1. Tap the “
Menu
” button on the home screen.
2. Then tap the “
Installer Settings
” button to access the various installer settings.
3. Tap the “
Floor Sensor Calibration
” button.
4. Use the “
Arrow Up
” or “
Arrow Down
” button to set the floor temperature
actually measured.
5. Confirm that you want to calibrate the sensor with “
√
” or cancel with “
X
”. If the
temperature is confirmed with “√”, a confirmation screen will be displayed briefly.
The thermostat will automatically return to “
Installer Settings
”.
Содержание DH E RT 102/BW
Страница 30: ...PAGE 30 2015 All rights reserved Used under license by Schlüter Systems L P Page intentionally left blank ...
Страница 36: ...PAGE 36 2015 All rights reserved Used under license by Schlüter Systems L P Page intentionally left blank ...
Страница 37: ...PAGE 37 2015 All rights reserved Used under license by Schlüter Systems L P Page intentionally left blank ...
Страница 50: ...PAGE 50 2015 All rights reserved Used under license by Schlüter Systems L P Page intentionally left blank ...