ExMax-...-CY  

ExMax-...-CYF 

Special options 

... -CTS 

... -VAS

Electrical connection

All actuators are equipped with a universal supply unit working at a voltage of 24 VAC/DC. 

The safety operation of the spring return function works if the supply voltage is cut.  

An over-current protection fuse < 10 A has to be provided by installer. 

Note: the initial current is appr. 2 A for 1 second.

Installation

Ex area – 

zone 1, 2, 21, 22

Safe area

Parameters, adjustments and failure indication

Parameter selection

Functions, adjustments and parameters

Type

Running times

Position of switch (S)

Torques

Example: 

ExMax-15.30-CY

Requested parameter: 

Torque 

30 Nm

Motor running time  30 s/90°

Result:

Switch position  

07

Switch – Push button – Lamp 

for adjustment 

(behind the blanking plug)

10-position switch (S)
Push button (T)
3-colour LED

Supply 24 VAC/DC ± 10 %

Set point

Optional feedback

Supply 24 VAC/DC ± 10 %

Set point

Optional feedback

Modulating – with spring return 

SB 6.1

Modulating – without spring return 

SB 6.0

Self adjustment:

To adjust the signal input /output to the angle of 

rotation of the damper/valve the button (T) must 

be pushed for a minimum of 3 sec.

Self adjustment:

To adjust the signal input /output to the angle of 

rotation of the damper/valve the button (T) must 

be pushed for a minimum of 3 sec.

24...240 VAC/DC

24...240 VAC/DC

Attention

During commissioning apply a self adjustment drive. 

Regard duty cycle at motor running times!

Never use spring return actuators without external load.

A)  Self adjustment of angle of rotation 

Turn switch (S) to position 02 (low torque) or 07 (high torque). Press button (T) for 

a minimum of 3 seconds. The actuator drives to both end positions and detects the 

blocking positions. The LED flashes GREEN during adjustment. 

The adjustment takes about 60 seconds (30 sec. “On”, 30 sec. “Off”).

B)  Selecting motor running time and torque 

Adjust parameters only if actuator is in idle state or without applied potential. 

Turn switch (S) to the position required for the intended operation acc. to table 

above. The selected parameters will be carried out at the actuator’s next operation. 

C)  Additional information for operation 

The rotation direction (clockwise/counter clockwise) depends on left/right 

mounting of the actuator to the damper. 

▪  Do not open the cover when circuits are live

▪  Connect potential earth

▪  

Close all openings to ensure enclosure protection

▪  Clean only with damp cloth, avoid dust accumulation

3 / 4

Содержание ExMax CY Series

Страница 1: ...e range of accessories The ExMax actuators are a revolution for safety control and shut off dampers VAV systems ball valves throttle valves and other motorized applications for HVAC systems in chemical pharmaceutical industrial and offshore onshore plants for use in Ex areas zone 1 2 gas and zone 21 22 dust Highest protection class ATEX and IP66 protection small dimensions only 3 5 kg weight unive...

Страница 2: ... kΩ Feedback signal UU 0 10 VDC at 2 000 Ω Adjustment of Y and U In case of external mechanical limitation of the angle of rotation it is possible to perform an adjustment drive started by pushing the button T Spring return F spring return upon voltage interruption Spring return response time up to 1 sec after voltage interruption Spring return running time F 10 s 90 Safety operations at 10 sec F ...

Страница 3: ...DC 10 Set point Optional feedback Modulating with spring return SB 6 1 Modulating without spring return SB 6 0 Self adjustment To adjust the signal input output to the angle of rotation of the damper valve the button T must be pushed for a minimum of 3 sec Self adjustment To adjust the signal input output to the angle of rotation of the damper valve the button T must be pushed for a minimum of 3 s...

Страница 4: ...uctions If the equipment is used in a manner not specified by the manufacturer the safety protection provided by the equipment may be impaired For electrical installations design selection and erection EN IEC 60079 14 can be used For electrical connection an Ex e terminal box is required e g ExBox Attention If the actuator is put out of operation all Ex rules and regulations must be applied You ha...

Отзывы: