background image

E X P L O S I O N P R O O F

www.schischek.com

Schischek GmbH

 Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

ExMax-S-CY_en

V04 –  19-Nov-2018

ExMax-...-CY  

ExMax-...-CYF 

Special options 

... -CTS 

... -VAS

Technical data 

ExMax- 5.10 -CY 

ExMax- 15.30 -CY 

ExMax- 5.10 -CYF 

ExMax- 15 -CYF

Approbations

Special solutions and accessories

...-CTS

 

Types in aluminium housing with seawater resistant coating, 

 

parts nickel-plated

...-VAS

 

Types in stainless steel housing, parts nickel-plated 

ExBox-Y/S...

  Ex-e terminal boxes for zone 1, 2, 21, 22

MKK-S

 

Mounting bracket for boxes type ...Box-... directly on actuator

ExSwitch

 

2 external aux. switches, adjustable for zone 1, 2, 21, 22

HV-S...

 

Comfortable manual override for...Max actuators size S

KB-S

 

Clamp for damper shafts Ø 10...20 mm and 

 10...16 mm

AR-12-xx

 

Reduction part for 12 mm square connection to 11, 10, 9 or 8 mm shafts

Kit-S8

 

Cable glands nickel-plated

Adaptions

  for dampers and valves on request 

Torque motor (min.)

 

5 / 10 Nm selectable on site 

15 / 30 Nm selectable on site 

5 / 10 Nm selectable on site 

15 Nm

Torque spring (F)

 

– – 

min. 10 Nm 

min. 15 Nm

Torque blockade

 

In blockade and end positions torques are higher than above specified torques for motor and spring.

Dimensioning of external load

 

Upon spring return the external load should be max. 80 % of torque spring (F).

Supply voltage / frequency

 

24 VAC/DC ± 10 %, self adaptable, frequency 50...60 Hz ± 20 %

Power consumption

 

max. starting currents see 

Extra information (in acc. with voltage, I

 start

 >> I

 rated 

), approx. 5 W holding power, approx. 16 W for heater

Protection class

 

Class I (grounded)

Angle of rotation and indication

 

95° incl. ~ 5° pretension, mechanical value indication

Working direction

 

Selectable by left/right mounting to the damper/valve shaft

Motor running times

 

7,5 / 15 / 30 / 60 / 120 s/90° selectable on site

Motor

 

Brushless DC motor  

Control mode Y

 

4…20 mA , galvanic separation between supply and Y-signal

Feedback signal U

 

0…10 VDC

Resistance of Y and U signals

 

Input signal:

 Y

U

 0...10 VDC at 10 k

Feedback signal:

 U

U

 0...10 VDC at 2.000...∞ Ω

Adjustment of Y and U

  

In case of external mechanical limitation of the angle of rotation, it is possible to perform an adjustment drive started by pushing the button (T)

Spring return (F)

 

– – spring return upon voltage interruption

Spring return response time

 

– – up to 1 sec. after voltage interruption

Spring return running time (F)

 

– – ~ 10 s/90°

Safety operations at 10 sec. (F)

 

– – min. 

10,000 

acc. to construction of damper and ambient

Axle of the actuator

 

Double square 12 × 12 mm, direct coupling, 100 % overload protected and self locking up to 15 Nm

Electrical connection

 Cable 

~ 1 m, wire cross section 0.5 mm², equipotential bonding 4 mm².

  

Connections in hazardous areas require an Ex-e terminal box!

Diameter of cable

 

~ Ø 8 mm 

~ Ø 8 mm 

~ Ø 8 mm 

~ Ø 8 mm

Cable gland

 

M16 × 1.5 mm

Manual override

 

Use delivered socket wrench, max. 4 Nm 

Heater

 Integrated, controlled h

eater for ambient temperature down to max. −40 °C 

Housing material

 

Aluminium die-cast housing, coated. Optional with seawater resistant coating (...-CTS) or stainless steel housing, 

 

 1.4581 / UNS-J92900 / similar AISI 316Nb (...-VAS)

Dimensions (L × W × H)

 

210 × 95 × 80 mm, for diagrams see 

Extra information

Weight

 

~ 3,5 kg aluminium housing, stainless steel ~ 7 kg

Ambients 

Storage temperature −40…+70 °C, working temperature −40…+40 °C at T6 and −40…+50 °C at T5

Humidity

  

0...90 % rH, non condensing

Operating 7,5 sec. motor run time 

at 24 V: S3 – 50 % ED intermittent mode (ED = duty cycle)

                ≥ 15 sec. motor run time

 at 

15 / 30 / 60 / 120 s 100 % of ED is permitted

Self adjustment

 

Before initial operation you need to start the self adjustment mode for “gentle” blockade and adjustment of rotation angle

Wiring diagrams

 

SB 6.0 

SB 6.0 

SB 6.1 

SB 6.1 

Scope of delivery

 Actuator, 4 screws M4 × 100 mm, 4 nuts M4, Allen key for simple manual override

Parameter at delivery

 

5 Nm, 30 s/90° 

15 Nm, 30 s/90° 

5 Nm, 30 s/90° 

15 Nm, 30 s/90°

ATEX Directive

  

2014/34/EU

EU-Type Examination

  EPS 17 ATEX 1 132 X

IECEx Conformity

  

IECEx EPS 17.0065X

Marking Gases

  

II 2 (2) G    Ex db [ib Gb] IIC T6, T5 Gb

 

Types ...-CTS  II 2 (2) G    Ex db [ib Gb] IIB T6, T5 Gb

Marking Dusts

  

II 2 (2) D    Ex tb [ib Db] IIIC T80°C, T95°C Db

CE Marking

 

 CE 

0158 

EMC Directive  

2014/30/EU

Low Voltage Directive

  2014/35/EU

Enclosure Protection

   IP66 

in acc. with EN 60529

2 / 4

Содержание ExMax CY Series

Страница 1: ...e range of accessories The ExMax actuators are a revolution for safety control and shut off dampers VAV systems ball valves throttle valves and other motorized applications for HVAC systems in chemical pharmaceutical industrial and offshore onshore plants for use in Ex areas zone 1 2 gas and zone 21 22 dust Highest protection class ATEX and IP66 protection small dimensions only 3 5 kg weight unive...

Страница 2: ... kΩ Feedback signal UU 0 10 VDC at 2 000 Ω Adjustment of Y and U In case of external mechanical limitation of the angle of rotation it is possible to perform an adjustment drive started by pushing the button T Spring return F spring return upon voltage interruption Spring return response time up to 1 sec after voltage interruption Spring return running time F 10 s 90 Safety operations at 10 sec F ...

Страница 3: ...DC 10 Set point Optional feedback Modulating with spring return SB 6 1 Modulating without spring return SB 6 0 Self adjustment To adjust the signal input output to the angle of rotation of the damper valve the button T must be pushed for a minimum of 3 sec Self adjustment To adjust the signal input output to the angle of rotation of the damper valve the button T must be pushed for a minimum of 3 s...

Страница 4: ...uctions If the equipment is used in a manner not specified by the manufacturer the safety protection provided by the equipment may be impaired For electrical installations design selection and erection EN IEC 60079 14 can be used For electrical connection an Ex e terminal box is required e g ExBox Attention If the actuator is put out of operation all Ex rules and regulations must be applied You ha...

Отзывы: