ABOUT THE CABLES
- if cables have to be inserted through metal walls, use a cable duct or cable bushes ;
- do not lay cables loose or with sharp bends on electrically conductive materials ;
- do not lay together 230VAC mains and 12VDC cables in the same cable duct ;
- the specified minimum cable cross-section must be complied with (see chapter « cable section ») ;
- secure cables properly ;
- lay cables in a such way that they are not exposed to the risk of damage ;
- for disconnecting the device set the mains switch to « OFF » and unplug from the mains. It must
always be within hand reach.
- when 230VAC supply wire is damaged, it must be replaced by our after sales department or by a
person having the required qualifications.
CABLES SECTIONS :
The mounting of a magneto-thermic circuit breaker is necessary to protect the 230VAC
supplying
III
INSTALLATION AND PUTTING INTO OPERATION
The charger must be installed in a well-ventilated location (minimum 15 cm on each side and 10 cm
on the top) and must not be covered.
The charger has 4 fixing holes on the rear part.
The connection for the uses and for the battery on the charger is made by FASTON terminals.
The connection of the 230VAC goes to the circuit breaker.
-
If wires length there and back (+ and -) is inferior to 10 meters ; then wires section has to
be 2,5mm
2
.
-
If wires length there and back (+ and -) is between 10 and 20 meters ; then wires section
has to be 4mm
2
.