Important: Counter-rotation of the blinds must be deactiva-

ted!

 

The automatic wind control always remains active and 

always works with absolute priority. This means that the 

system cannot be endangered by excessive wind - even in 

the event of accidental incorrect operation.

 

The reaction time in the event of wind is pre-programmed 

and is 1 - 15 seconds, depending on the amount of excess 

wind. The response time when reaching sun light intensitiy 

threshold can be individually adjusted by a simple program-

ming procedure (factory setting 10 min.).

 

The motor running time can also be programmed for individu-

al adaptation to the awning used (factory setting 90s).

 

If the SMS 2 or SMS U2 is used as group control, this can 

also be set in a programming process. In this case, the 

controller only releases the outputs as soon as the wind level 

falls below the set limit value.

Controls and indicators

Light intensity threshold setting

Setting range 20,000 –100,000 lx

Adjuster for counter-rotation of blinds (SMS 2 only) 

Duration of the counter-flow pulse 0.1 - 1.3s or Off (function 

deactivated) 

Status indicator LEDs:

SMS U2: 

A blinking red LED ( ) W indicates wind speed abo-

ve the threshold level; blinking green ( ) indicates brightness 

above the threshold level.

SMS 2:

 Blinking red ( ) with LED W indicates wind speed 

above the threshold level, with LED B light level above the 

brightness threshold, and with LED D light level below the 

twilight threshold.

LEDs 14 and 24 indicate the corresponding motion direction.

Status indicator LEDs 

 LED off

 LED lit red

 LED blinks red

 LED lit green

 LED blinks green

 LED blinks alternating red/green

Twilight threshold setting (SMS 2 only)

Setting range 1 – 70 lx

Wind speed threshold setting

Setting range 10 – 70 km/h

Содержание SMS 2

Страница 1: ...2 settings When a set limit value is exceeded the control LED starts flashing and the awning is activated after the response time has elapsed The details of the individual operating modes can be found...

Страница 2: ...ming process In this case the controller only releases the outputs as soon as the wind level falls below the set limit value Controls and indicators Light intensity threshold setting Setting range 20...

Страница 3: ...responding This type of switch off only deactivates the sun automation The safety relevant wind monitoring remains fully functional Light sensor Automatic sunlight control can be completely disabled b...

Страница 4: ...en control or data cables such as I Y St Y 2x2x0 6 can be used length max 50m The low voltage for the sensor supply is generated directly in the respective controller An additional external power supp...

Страница 5: ...ame time This takes you to the second programming step and saves any previous settings you have made Step 2 Adjust the motor run time SMS U2 LED lit red SMS 2 LED W lit red The factory default motor r...

Страница 6: ...vated Blind counter rotation function SMS 2 only Local inputs are level controlled when the button is pressed briefly and edge controlled when the button is pressed long Countercurrent pulse tg is tri...

Страница 7: ...tes wind direction Leaves and wind vanes are stationary 2 6 11 Light breeze Wind felt on exposed skin Leaves rustle Wind vanes begin to move 3 12 19 Gentle breeze Leaves and small twigs constantly mov...

Страница 8: ...ections Socket terminals with captive screws M2 Clamping range 0 25 mm 1 5 mm Strip length 6 0 mm 6 5 mm Screwing torque 0 20 Nm Dimensions 43 x 43 x 18 5mm SMS U2 Part no EAN Type Designation SMSU29...

Отзывы: