Fire damper BSK-RPR 

 

 

Additional operating instructions according to ATEX 2014/34/EU

 

 

Models and dimensions

 

Construction subject to change 

 

No return possible 

Version: 2020-09-01 | Page 10 

Information regarding assembly and commissioning 

Prior  to  being  installed  in  the  ventilation  system,  the  fire 
damper must be checked for damage. Damaged fire dampers 
must not be installed. 
 
The  device  may  only  be  used  in  accordance  with  its  desig-
nated use in air ventilation systems for supply air and return 
air. 
 
Use only approved fastening material for mounting. 
 
No additional parts may be  
fastened to the fire damper. 
 
The  fire  damper  must  be  connected  to  the  ventilation  duct 
network on both sides in electrically conducting fashion. 
 
In  order  to  avoid  the  risk  of  static  charges,  the  fire  damper 
must  be  connected  to  the  on-site  equipotential  bonding  on 
the grounding connection provided for this purpose. 
 
Make sure that the ventilation systems are not subjected to 
any anomalous operating conditions, such as vibrations, pres-
sure surges or high proportions of solids in the medium. 
 
 

Information regarding functional check

 

and inspec-

tion 

Proper functional check increases operational safety and the 
service  life  of  the  device.  This  is  why  the  devices  should  be 
subjected to regular inspection. 
 
If inspection dates are prescribed by law, they must be com-
plied with. 
 
The operating personnel must be informed, prior to starting 
functional check and inspection work. 
 
The personal safety measures must be looked up in the safety 
data sheet. Hazard caused by contact or  inhaling hazardous 
substances  must  be  excluded  by  taking  appropriate  safety 
measures. 
 
Prior to functional check or inspection, all system components 
up- and downstream of the device must be switched off and 
secured against being switched on again. 

 
 
The following inspection criteria must be observed: 

 

Visual inspection of the device 

 

Check the fastening of the device 

 

Check the electrical connections 

 

Check  the  grounding  connection  for  tight  fit  and  good 
contact 

 

Functional control 

 

For  additional  inspections,  please  refer  to  the  technical 
documentation  or  additional  instructions  for  functional 
check 

 

Use and electrical connection of actuators in areas 
subject to explosion hazards 

Only ATEX-approved electrical equipment according to ATEX 
Directive 2014/34/EU for the zones 1, 2, 21, 22, such as actu-
ators,  terminal  boxes  and  thermocouples  according  to  our 
specifications may be used for SCHAKO KG devices. 
 
The connection lines must be installed for permanent use and 
in  such  a  way  that  they  are  sufficiently  protected  from  me-
chanical and thermal damage. 
 
Devices  with  explosion-protected  actuators  and  terminal 
boxes  have  to  be  attached  over  the  external  potential  con-
necting terminal to the potential equalisation provided by the 
customer with at least 4 mm² cooper solid-core. 
 
The electrical connection lines of the actuators  
must  be  connected  in  a  terminal  box  according  to  ATEX  Di-
rective 2014/34/EU for the zones 1, 2, 21, 22, if the electrical 
connection is made in an explosive area. 
 
The dimensioning of the conductor cross-sections must be ob-
served. 
 
The  actuators  are  maintenance-free  with  respect  to  their 
function, but the test specifications according to ATEX direc-
tives  
or factory regulations must be observed. 
 
 

 

Содержание BSK-RPR

Страница 1: ...RPR 2020 09 01 CLASSIFICATION AND STANDARDS Classification according to EN 13501 3 depending on the mounting situation EI 90 ve ho i o S Product standard EN 15650 Test standard EN 1366 2 PERFORMANCE D...

Страница 2: ...Contents Construction subject to change No return possible Version 2020 09 01 Page 2 TABLE OF CONTENTS Table of Contents 2 General conditions 3 Description 4 Models and dimensions 5 Type plate 11 Ord...

Страница 3: ...d DESIGNATED USE The devices have been designed for use in ventilation systems in areas subject to explosion hazards according to the ATEX marking Device group II Zones 1 2 and 21 22 These devices are...

Страница 4: ...ilation system by means of ventilation ducts either on one or on both sides When connected on one side security grille made of non flammable building materials EN13501 1 must be provided on the opposi...

Страница 5: ...amper blade 3 Hand lever 4 Locking profile 5 Release device 6 Fusible link 7 Mounting frame AR 8 Actuator unit 9 Earthing connection 10 Actuator ExMax 5 10 BF X14 X15 11 Safety temperature limiter Rub...

Страница 6: ...le Version 2020 09 01 Page 6 BSK RPR S with mounting frame AR Figure 4 Dimensions of the BSK RPR S with mounting frame AR Figure 5 Dimensions of BSK RPR S with installation frame AR with actuator ExMa...

Страница 7: ...5 58 13 40 7 03 14 85 280 278 6 31 16 55 7 79 18 03 7 17 17 41 8 65 18 89 315 313 7 14 18 40 8 62 19 88 8 13 19 39 9 61 20 87 355 353 8 08 20 53 9 56 22 01 9 19 21 64 10 67 23 12 400 398 9 09 22 89 1...

Страница 8: ...ula tions Technical data actuator ExMax 5 10 BF X14 X15 Power supply 24 240 V AC DC 10 each self adaptable Frequency 50 60 Hz 20 Power consumption Holding max 20 W Heating capacity approx 16 W Current...

Страница 9: ...t be necessary e g for large wall and ceiling thicknesses When connecting duct components a fastening type must be selected that causes no damage to the fire damper or its accessories During mounting...

Страница 10: ...by contact or inhaling hazardous substances must be excluded by taking appropriate safety measures Prior to functional check or inspection all system components up and downstream of the device must be...

Страница 11: ...damper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Type plate Construction subject to change No return possible Version 2020 09 01 Page 11 TYPE PLATE Figure 10 BSK RPR type...

Страница 12: ...02 MODEL S Plug in connection F Flanged connection 03 NOMINAL SIZE 100 125 140 160 180 200 224 250 280 315 355 400 450 500 in mm always three digits 04 LENGTH 580 or 455 S model 500 or 375 F model in...

Страница 13: ...ess 120 mm metal post includes R04 I R22 Installation kit type GDL for wall thickness 125 mm metal post includes R04 I R23 Installation kit type GDL for wall thickness 140 mm metal post includes R04 I...

Страница 14: ...amper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Certificate of conformity Construction subject to change No return possible Version 2020 09 01 Page 14 CERTIFICATE OF CONFO...

Страница 15: ...Fire damper BSK RPR Additional operating instructions according to ATEX 2014 34 EU Certificate of conformity Construction subject to change No return possible Version 2020 09 01 Page 15...

Страница 16: ...43 Luxembourg L 2343 Luxembourg A 1060 Wien PL 05 500 Piaseczno Phone 352 403 157 1 Phone 352 403 157 1 Phone 43 1 890 24 62 Phone 48 22 7263570 Fax 352 403 157 66 Fax 352 403 157 66 Fax 43 1 890 24 6...

Страница 17: ...ilippendichtung 5 Abbildung 4 Abmessungen BSK RPR S mit Anbaurahmen AR 6 Abbildung 5 Abmessungen BSK RPR S mit Anbaurahmen AR mit Antrieb ExMax 5 10 BF X14 X15 6 Abbildung 6 Abmessungen BSK RPR F 6 Ab...

Отзывы: