Fire damper BSK-RPR-EU
Technical documentation
Models and dimensions
Construction subject to change
No return possible
Version: 2021-07-01 | Page 6
Damper leaf projecting ends
BSK-RPR-EU-S
Figure 5: Damper blade projecting ends BSK-RPR-EU-S
No-
minal
size
ø
D
Operating
side
(BS)
Non-operating side
(NBS)
L=455 / 580
L=455
L=580
100
98
256
x
107
Y
232
y
125
123
244
95
220
140
138
236
87
212
160
158
226
77
202
180
178
216
67
192
200
198
206
57
182
224
222
194
45 *
170
250
248
181
32 *
157
280
278
166
17 *
142
315
313
149
0 *
125
355
353
129
20 *
Y1
105
400
398
106
43 *
82
450
448
81
68 *
57
500
498
56
93 *
32 *
* Extension piece (on site) necessary
Table 3: Damper blade projecting ends BSK-RPR-EU-S
"a"= 50
mm:
Minimum distance between the front edge
of the open damper blade and the finishing
protective grating (ASG-RF/-RS)
Use
Table 4: Usability
BSK-RPR-EU-F
Figure 6: Damper blade projecting ends BSK-RPR-EU-F
No-
minal
size
ø
D
Operating
side
(BS)
Non-operating side
(NBS)
L=375 / 500
L=375
L=500
100
98
216
x
67
Y
192
y
125
123
204
55
180
140
138
196
47 *
172
160
158
186
37 *
162
180
178
176
27 *
152
200
198
166
17 *
142
224
222
154
5 *
130
250
248
141
8 *
Y1
117
280
278
126
23 *
102
315
313
109
40 *
85
355
353
89
60 *
65
400
398
66
83 *
42 *
450
448
41 *
108
*
17 *
500
498
16 *
133
*
8 *
Y1
* Extension piece (VT-RF) necessary
Table 5: Damper blade projecting ends BSK-RPR-EU-F
The fire damper type BSK-RPR-EU can be installed as shown in the following table
Use
Installa-
tion
Material/Model
Minimum
thickness
mm
Minimum
distance
mm
Fire resistance
class
Notes
Page °
WALL
solid
Apparent
density
≥ 450kg/m³
in
Wet installation in, for example,
concrete; masonry according to EN
1996 or DIN 1053; solid plaster
wall boards according to EN 12859
150
next to each other: 50
1)
EI 120 (v
e
i
o) S
Wall: 75
Ceiling: 75
1)
The allowed minimum distance of the fire dampers to one another is at least 50 mm. However, due to the construction, the distance
has to be adapted for BSK-RPR-EU-F, if necessary.
NBS
BS
NBS