Storage Battery Systems, Inc. MANUAL PSC
18
VMIN
+ or -
Adjust the Minimum Output Voltage
Default value is 0
VMAX
+ or -
Adjust the Maximum Output Voltage
IMAX
+ or -
Adjust the Maximum Output Current
Remote V sens
SET
Toggle On/Off the Remote Voltage
Sensing
Off
Load sharing
SET
Toggle On/Off the Load Sharing
Off
Negative slope
regulation
Tcomp
SET
Toggle On/Off Temperature
Compensation
Off
LCD pwr save
SET
Toggle On/Off LCD power save
After 5 min of inaction on LCD goes on
power save
Off
Remote Eq
SET
Toggle On/Off Remote Equalization
Off
AH display
SET
Toggle On/Off Ampere/Hour display
Off
Bat cap
+ or -
Adjust the Ampere/Hour capacity of
Battery
Readings:
Use
à
or
ß
keys to scroll the Reading sub-menus.
SET
to enter menu.
EXIT
to return to previous menu.
DISPLAY
Press
ACTION
Default Value
Frequency
Actual frequency
Active
AC display
L
N
Display AC voltage
Display AC current
Off
Off
AH meter
Display Ampere/ Hour in percent
Display Ampere/ hour
Off
Off
** : If FIXED CHARGER mode is on “OFF” position then no alarms, float, equalize modes are accessible.
(i.e. software exits set up mode after having chosen variable current or/and voltage)