Storage Battery Systems, Inc. MANUAL PSC
1
PSC-SERIES
BATTERY CHARGER
USER’S MANUAL
Страница 1: ...Storage Battery Systems Inc MANUAL PSC 1 PSC SERIES BATTERY CHARGER USER S MANUAL...
Страница 2: ...VIA KEYPAD OVERVIEW 9 MENU STRUCTURE QUICK OVERVIEW 11 MENU DETAILED FUNCTIONS 13 MAIN MENU 13 Equalize 13 LCD Contrast 13 Reset alarms and relays 14 Adjust 14 Control 14 Alarms 15 Level 2 17 Reading...
Страница 3: ...Storage Battery Systems Inc MANUAL PSC 3 Procedure 26 WARRANTY 28 ANNEXES 29 ELECTRIC DIAGRAM 29 PART LIST 29 MECHANICAL DRAWINGS 29 TEST REPORT 29...
Страница 4: ...TANT SAFETY INSTRUCTIONS Keep these instructions in a safe place this manual contains important safety and operating instructions AC and DC currents are present in this system even with indicators and...
Страница 5: ...lowed room temperature K i e 50 C 323 K Tk Temperature of input cooling air To 273 K H Altitude km Avoid placing the system in direct sunlight N B to insure adequate ventilation and safe access make s...
Страница 6: ...e neutral tension positive neutral tension Keep a log of manipulations i e VFLOAT and VEQUALIZE values entered alarm messages alarm and SCR blinking leds All input and output breakers must be on OFF p...
Страница 7: ...lter section Shunt current and voltage reading sent to the control board F1 a fuse protects the SCR s and diodes Control Board the PC20 21 series control board provides automatic charge control precis...
Страница 8: ...rm is active on the charger exact failure message appears and the red led blinks to warn the user In case of multiple alarms the PSC display unit shows sequentially all the warning messages There is a...
Страница 9: ...ple From that point if you press any key of F1 to F4 only once you reach the menu screen F1 Ok gives you access to Float Equalize menu Press F4 Exit to step back to the menu From the menu you may reac...
Страница 10: ...gh the following functions Reset Alarm present only in case of alarm Adjust Reading Relay test Contrast LCD And pressing F3 4 times will make the screen scroll in the opposite direction back to the fo...
Страница 11: ...nt of the charger and should be done only by qualified technician Control F1 Ok Float 124 9 for example F2 I Lim 23 3A Eq 131 5 On TEQ 08 H LVEQ 106 1V On TALimEq 05mn On AC Eq On T Float 30 D availab...
Страница 12: ...50V Nom AMP 25 A DCV cal 132 0V DCA cal 0 0A AC display Off ACV cal 78 4V ACA cal 539 5A VMIN 0 0V VMAX 160 0V IMAX 02 2A Remote V sens Off Load sharing Off Tcomp Off LCD Pwr save Off Remote EQ Off AH...
Страница 13: ...t key for sub function F2 Scroll Down sub menu Go UP next selection F3 Scroll Up sub menu Go DOWN last selection F4 Return to previous menu Exit Return last selection Main menu Use or keys to scroll t...
Страница 14: ...ord must be valid to access Control Alarms and reading sub menu Control SET Go to Control adjustments Alarms SET Go to alarm adjustments Level 2 SET Go to level 2 sub menu Control Use or keys to scrol...
Страница 15: ...o 7 0 8 x Vfloat On No 3 LVDis relay xxx or NEXT NEXT On Off NEXT or Adjust Low Voltage Disconnect level V Go to Relays selection toggle menu Toggle Low voltage Disconnect Select relays number 1 to 7...
Страница 16: ...toggle menu Toggle Low External temperature level Alarm Select relays number 1 to 7 ACVH relay xxx or NEXT NEXT On Off NEXT or Adjust High AC Voltage level alarm Go to Relays selection toggle menu To...
Страница 17: ...hen Off all values are displayed When On only values that are set to On are displayed NomVolt or Adjust the Nominal Voltage displayed Once values is set Nominal Voltage is not displayed Factory preset...
Страница 18: ...goes on power save Off Remote Eq SET Toggle On Off Remote Equalization Off AH display SET Toggle On Off Ampere Hour display Off Bat cap or Adjust the Ampere Hour capacity of Battery Readings Use or ke...
Страница 19: ...show the structure RAM of the PCOM card R mean readable and W mean writable Variable Address dec Bytes Status Vout 00 2 R Vfloat Vref setting value 01 2 W R Vequalize setting value 02 2 W R Volt low...
Страница 20: ...1 R Status Alarm low external temperature 23L 1 R Status Alarm High temperature of card 24H 1 R Status Alarm Battery Discharging 24L 1 R Status Alarm I Lim 25H 1 R Status Alarm Equalize 25L 1 R Statu...
Страница 21: ...cate that the charger is in Equalize mode see table 3 To change operation mode Float or Equalize via RS 232 parameter Eq in Adjust Control submenu must be ON and parameter Remote RS 232 in Adjust Leve...
Страница 22: ...em computer or in this case the SBS PCOM card The cable needed for the RS 232 communication must have a maximum length of 15 2m 50 ft with DB9 male connector at the PCOM card end and to other end on t...
Страница 23: ...t verify that the AC breaker is closed ON verify that the AC supply is of correct voltage and frequency verify the DC output fuse verify the output and input connections replace control board PC20 21...
Страница 24: ...ner equipped with a yearly small brush removes accumulated dust especially around ventilation openings B C visually verify the condition of all yearly components B C verify all connections If necessar...
Страница 25: ...of cells 18 Current limit adjust the current limit to the test report value Nickel cadmium battery A B C Float voltage Vf Number of cells x 1 42 v cell 25 6 v Equalize voltage Ve Number of cells x 1 5...
Страница 26: ...DC output maximum current Im Example Suppose that you have 18 Ni Cad cells for your specific Ni Cad or lead acid please use the information provided by the battery supplier Constant voltage Float volt...
Страница 27: ...t relays number 1 to 7 20 4 V On No 3 GNDF relay xxx or NEXT NEXT On Off NEXT or Adjust Negative Ground Fault level mA Go to Relays selection toggle menu Toggle Negative Ground Fault Select relays num...
Страница 28: ...efective and shall not apply to products which must be repaired or replaced due to normal wear misuse negligence wreckage accident any act of god or to products which have been repaired or altered out...
Страница 29: ...Storage Battery Systems Inc MANUAL PSC 29 ANNEXES Electric diagram Part list Mechanical Drawings Test report...