Technical data S-Bus

Bus system  

 

S-Bus

Transmission rate  

4800-9600-19 200-38 400-57 600-115 200. 

     

 

The transmission Baud rate is automatically detected

Transmission mode  

Data

Bus length (max.)  

1200 m (without repeater)

Response time:    

Write: up to 60 ms

     

 

Read: up to 60 ms

  The communication is ready 30 s after the power on

  The use of energy meter in bus with intensive communication could reduce the performance of the bus

  Refresh time for the data is 5 s. For this reason one energy meter should be not polled faster as 5 s  

  254 devices could be connected to the S-Bus. With more than 128 devices, a repeater should be used 

  The interface don’t have a terminal resistor, this must be provided external 

  For a description of the used registers please look at the register page

Data transmission

  Only «read/write» register instructions are recognized 

  Only one register can be written at the same time 

  The device will respond «NAK» if more than 1 register is written 

  Up to 10 Registers could be read at the same time 

  The device will respond «NAK» if more than 10 registers are read 

  The device will not respond to any unknown query 

   The device has a voltage monitoring system. In case of voltage drop,  

registers are stored in EEPROM (transmission rate) etc.

Changing the S-Bus direct on device

  In the menu, go for «U» 

  Push long (≥ 2 s) 

 «SBUS-ADR» 

  Push short 

 S-Bus a1, push long 

 S-Bus a10 

  If the desired address is reached, wait until the main display appears again.

English

Содержание Saia PCD ALD1B5FS

Страница 1: ...0 Imp kWh Pulsiert entsprechend der bezogenen Leistung Hinweise vor dem Anschliessen Um Feuchtigkeit im Zähler durch Kondenswasser zu ver meiden den Zähler vor dem Anschliessen ca eine halbe Stunde bei Raumtemperatur akklimatisieren Achtung Diese Geräte dürfen nur durch eine Elektrofachkraft installiert werden andernfalls besteht Brandgefahr oder Gefahr eines elektrischen Schlages EG Konformitätse...

Страница 2: ...ter benutzt werden Die Schnittstelle hat keinen Abschlusswiderstand dieser sollte extern bereitgestellt werden Die verwendeten Register sind in der Registerliste beschrieben Datenübertragung Nur lese schreib Register Befehle werden erkannt Es kann immer nur ein Register auf einmal beschrieben werden Das Gerät wird ein NAK zurückgeben wenn mehr als ein Register auf einmal beschrieben wird Es können...

Страница 3: ...ing standard EN50470 Environment Mechanical M2 Electromagnetic E2 Notes before connecting In order to avoid moisture in the meter due to condensate build up acclimatise the meter at room temperature for about half an hour before connecting Attention These devices must only be installed by a professional electrician otherwise there is the risk of fire or the risk of an electric shock Declaration of...

Страница 4: ...th more than 128 devices a repeater should be used The interface don t have a terminal resistor this must be provided external For a description of the used registers please look at the register page Data transmission Only read write register instructions are recognized Only one register can be written at the same time The device will respond NAK if more than 1 register is written Up to 10 Registe...

Страница 5: ...corrente 2000 impulsi kWh Impulsi secondo l uscita indicata Dichiarazione di conformità CE Noi Saia Burgess Controls SA CH 3280 Morat Svizzera dichiarammo in nostra propria responsabilità che i prodotti ALD1B5FS00A3A00 di quali si riferisce questa dichiarazione rispondono alla direttiva 2004 22 CE MID e alle normative seguente normativa EN50470 Parte 1 e 3 Contatori elettronici Octobre 2006 ESD su...

Страница 6: ...interfaccia non ha alcuna resistenza terminale questa dovrebbe essere disponibile esternamente Per una descrizione dei registri utilizzati consultare la Pagina Registri Trasmissione dei dati Vengono riconosciute solo le istruzioni read write register Può essere iscritto solo un registro alla volta L apparecchio risponderà con un NAK se viene iscritto più di un registro alla volta Possono essere le...

Страница 7: ...ourant consommation pos courant récupération neg U V Tension I A Courant 2000 pulses kWh Impulsions en fonction de la puissance absorbée Déclaration de conformité CE Nous Saia Burgess Controls SA CH 3280 Morat Suisse déclarons sous notre propre responsabilité que les produits ALD1B5FS00A3A00 pour lesquels cette déclaration se référe sont conformes à la directive 2004 22 CE MID et aux normes suivan...

Страница 8: ...ombre d appareils est supérieur à 128 utiliser un répéteur L interface n est pas dotée d une résistance de terminaison celle ci doit être mise à disposition de façon externe Les registres utilisés sont décrits dans la liste de registres Transfert de données Seules les instructions de type registre lecture écriture sont reconnues Un seul régistre peut être écrit à la fois L appareil renverra un sig...

Страница 9: ...of wires twisted D max 1200 meters D B U V P P P kW kW kW I A 2000 Imp kWh kWh kWh ALD1B5F T T 5560 L1 N B U V P P P kW kW kW I A 2000 Imp kWh kWh kWh ALD1B5 F T T 431951390E 230 VAC 4 319 5139 0E 03 2017 Subject to change without notice ...

Страница 10: ...7 x Error flags 0 No error 1 Error 18 x Not used will give 0 19 x Energy direction register 0 energy direction consumption 4 energy direction feeding back 20 x Counter total energy consumption 10 2 kWh multiplier 0 01 Ex 00912351 009123 51 kWh 21 x Counter total energy feeding back 10 2 kWh multiplier 0 01 Ex 00912351 009123 51 kWh 22 x Not used will give 0 23 x Not used will give 0 24 x Effective...

Страница 11: ...Menu to display the value on LCD Start T Tariff consumption T Tariff feeding back P Instantaneous power ...

Страница 12: ...Back to Start Back to Start U Voltage I Current 20 s 3 s 2 s ...

Отзывы: