Technical data S-Bus
Bus system
S-Bus
Transmission rate
4800-9600-19 200-38 400-57 600-115 200.
The transmission Baud rate is automatically detected
Transmission mode
Data
Bus length (max.)
1200 m (without repeater)
Response time:
Write: up to 60 ms
Read: up to 60 ms
■
The communication is ready 30 s after the power on
■
The use of energy meter in bus with intensive communication could reduce the performance of the bus
■
Refresh time for the data is 5 s. For this reason one energy meter should be not polled faster as 5 s
■
254 devices could be connected to the S-Bus. With more than 128 devices, a repeater should be used
■
The interface don’t have a terminal resistor, this must be provided external
■
For a description of the used registers please look at the register page
Data transmission
■
Only «read/write» register instructions are recognized
■
Only one register can be written at the same time
■
The device will respond «NAK» if more than 1 register is written
■
Up to 10 Registers could be read at the same time
■
The device will respond «NAK» if more than 10 registers are read
■
The device will not respond to any unknown query
■
The device has a voltage monitoring system. In case of voltage drop,
registers are stored in EEPROM (transmission rate) etc.
Changing the S-Bus direct on device
■
In the menu, go for «U»
■
Push long (≥ 2 s)
➞
«SBUS-ADR»
■
Push short
➞
S-Bus a1, push long
➞
S-Bus a10
■
If the desired address is reached, wait until the main display appears again.