Mounting Instructions

The Q.RCU-D-xx sensors have been specially designed for easy 

installation. However, certain conditions apply when choosing a 

suitable location for the device:

 -

The device should not be installed on an exterior wall.

 -

The device should not be installed near a heat source.

 -

The device should not be installed near an air discharge grill.

 -

The device should not be installed in a place where it can be 

affected by the sun.

 -

Install the device in an area that provides proper device 

ventilation. Nothing must restrain air circulation to the device.

The Q.RCU-D-xx sensor has not been designed for out-

door use.

Installation Procedure

1.   Remove the security screw from the device.
2.   Open the Q.RCU-D-xx sensor by pushing in the tab on the bottom 

of the device and pulling the bottom side of the front plate out.

3.   Open The Q.RCU-D-L Light/Blind module by pulling the front 

plate off (if applicable).

4.   Plug the Q.RCU-D-L Light/Blind add-on modules into the back 

plate (if applicable).

5.   Make sure that the mounting surface is flat and clean.
6.   Align the back plate with the wall and mark the location of the 

mounting holes on the wall (2 holes for the sensor and 1 hole per 

Q.RCU-D-L Light/Blind module are recommended). Make sure to 

orient the proper side of the back plate facing upwards.

7.   Remove the back plate and drill holes in the wall if necessary.
8.   Install anchors in the wall if necessary.
9.   Unplug the Q.RCU-D-L Light/Blind add-on modules from the 

back plate (if applicable). 

10.   Pull all RJ-45 cables and digital wires (if applicable) 15 cm (6”) 

out of the wall, and insert them through the central hole of the 

back plate.

11.   Screw the back plate onto the wall. Do not over tighten.
12.   Set the Subnet ID and the EOL termination with the dipswitch as 

explained in section 

Setting the Q.RCU-D-xx Sensor Subnet ID

.

13.   Connect the one or two RJ-45 cables into the sensor (reversable)
14.   If using digital inputs, connect the digital wires to the digital 

input cable as specified in sectio

About an Q.RCU-D-xx Sensor 

equipped with a digital input cable

, and the digital input cable 

connector into the sensor as shown o

Figure 6: Connectors 

and Dipswitch Locations

.

15.   Gently push excess wiring back into the wall.
16.   Reattach the front plate and make sure it clips tightly into place.
17.   Install the security screw.
18.   Plug the Q.RCU-D-L Light/Blind add-on modules into the back 

plate (if applicable).

19.   Screw the Q.RCU-D-L Light/Blind add-on module(s) onto the 

wall. Do not over tighten (if applicable).

20.   Attach the Q.RCU-D-L Light/Blind add-on modules front plates 

(if applicable).

Device Components

Fan speed 

selection knob

Temperature setpoint 

offset knob

Occupancy 

button

Q.RCU-D-xx Sensor - Front elements

Security screw

Locking tab

Q.RCU-D-x Light/Blind 

add-on electrical connection

Q.RCU-D-x Light/Blind 

add-on mechanical plug

Figure 5:  

Q.RCU-D-xx Sensor - Bottom elements

3

/8

www.sbc-support.com  

 Installation Guide | 26-604_ENG01 02-2016

Saia-Burgess Controls AG

Q.RCU-D-xx Series

Содержание Q.RCU-D Series

Страница 1: ...ommendations Itisrecommendedthatthedevice s bekeptatroomtemperature for at least 24 hours before installation to allow any condensation that may have accumulated due to low temperature during shipping storage to evaporate Upon unpacking the product inspect the contents of the carton for shipping damages Do not install damaged devices The device is designed to operate under environmental conditions...

Страница 2: ... 20 58 2 28 82 3 23 5 0 20 10 0 40 5 0 20 7 0 28 7 0 28 mm inches Figure 2 Q RCU D xx Back plate view 84 3 30 55 2 17 Ø7 0 28 12 0 47 23 0 90 2 0 08 23 0 90 4 0 16 25 0 98 75 2 95 22 0 87 Figure 3 Q RCU D L Light Blind add on modules Front view and side view 4 0 16 9 0 35 5 0 20 38 1 50 9 5 0 37 mm inches Figure 4 Q RCU D L Light Blind add on modules Back plate view 2 8 Installation Guide 26 604_E...

Страница 3: ...l if necessary 9 Unplug the Q RCU D L Light Blind add on modules from the back plate if applicable 10 Pull all RJ 45 cables and digital wires if applicable 15 cm 6 out of the wall and insert them through the central hole of the back plate 11 Screw the back plate onto the wall Do not over tighten 12 Set the Subnet ID and the EOL termination with the dipswitch as explained in section Setting the Q R...

Страница 4: ...em responsiveness This may be the origin of a certain delay which could be an issue for commands needing a fast response such as lighting and shades sunblind commands 2 The indicated adressing ranges are specific for each group of device 4 different Subnet ID codifications are used on the Q RC Subnetwork 1 for Q RCU LCD sensors 1 for Q RCU D xx and Q RCU DC xx sensors 1 for Q RCS MS PL multi senso...

Страница 5: ...ch cable fitted with RJ 45 connectors If you make your own patch cable use Cat 5e cable and crimp the RJ 45 connectors at both ends of the cable either as T568A or T568B Table 2 T568A and T568B Terminations for an RJ 45 Connector Pin T568A at both cable ends T568B at both cable ends Pair Color Pair Color 1 3 white green stripe 2 white orange stripe 2 3 green solid 2 orange solid 3 2 white orange s...

Страница 6: ...hain topology is acceptable for the room device subnetwork bus T connections are not allowed Onla the EOL terminations of the last subnetwork bus device are set to ON All other subnetwork bus devices must have their EOL terminations set to OFF The controller must be the first device on the Cat 5e Cable Subnetwork bus as its internal EOL termination is permanently enabled See Table 2 Number of room...

Страница 7: ... Directive applies to standalone products for example products that can function entirely on their own and are not a part of another system or piece of equipment For this reason SBC products are exempt from the WEEE Directive Nevertheless SBC products are marked with the WEEE symbol indicating devices are not to be thrown away in municipal waste Products must be disposed of at the end of their use...

Страница 8: ...y Saia Burgess Controls AG 2016 All rights reserved Postal address for returns from customers of the Swiss Sales office Saia Burgess Controls AG Service Après Vente Bahnhofstrasse 18 3280 Murten Switzerland Saia Burgess Controls AG Bahnhofstrasse 18 3280 Murten Switzerland T 41 26 580 30 00 F 41 26 580 34 99 www saia pcd com support saia pcd com www sbc support com 8 26 604 ENG01 02 2016 Technical...

Отзывы: