Product Description

The Q.RCU-D-xx series are versatile communicating sensors which 

provide a user-friendly interface as well as precise temperature sensing.

Tailored for occupants, the Q.RCU-D-xx intuitive design features 

coloured LED indicators to provide user feedback, rotary knobs to 

adjust the setpoint offset and fan speed, and a push-button to apply 

occupancy override.

As a multi-function room device, the sensor can be expanded with 

a combination of up to 4 Q.RCU-D-L Light or Q.RCU-D-B Blind add-

on push-button modules, for lighting and shade/sunblind control, 

making it an ideal all-in-one addition to the Room Control solution. 

This document describes the hardware installation procedures for the 

Q.RCU-D-xx sensors. This line of communicating sensors consists of 

the following models:

 -

Q.RCU-D-TS

 -

Q.RCU-D-TSO

 -

Q.RCU-D-TSOF

This document also covers the installation of Q.RCU-D-L Light and 

Q.RCU-D-B Blind add-on modules.

General Installation Requirements

For proper installation and subsequent operation of the device, pay 

special attention to the following recommendations:

 -

 It is recommended that the device(s) be kept at room temperature 

for at least 24 hours before installation to allow any condensation 

that may have accumulated due to low temperature during 

shipping/storage, to evaporate.

 -

Upon unpacking the product, inspect the contents of the carton 

for shipping damages. Do not install damaged devices.

 -

The device is designed to operate under environmental 

conditions that are specified in its datasheet. 

 -

Ensure proper ventilation of device and avoid areas where 

corroding, deteriorating or explosive vapors, fumes or gases may 

be present..

 -

Do not drop the device or subject it to physical shock.

 -

If the device is used and/or installed in a manner not specified by 

SBC, the functionality and the protection provided by the device 

may be impaired.

 -

To ensure reading accuracy, handle sensor with care and avoid 

installing on a vibrating surface.  

Make connections to the sensor last. Yanking the cable 

while it is attached to the sensor can damage the con-

nector.
Any type of modification to any SBC product will void the 

product’s warranty.

Take reasonable precautions to prevent electrostatic 

discharges to the device when installing, servicing or 

operating it. Discharge accumulated static electricity by 

touching one’s hand to a securely grounded object be-

fore working with the device.

Q.RCU-D-TSOF

Q.RCU-D-TSO

Q.RCU-D-TS

Содержание Q.RCU-D Series

Страница 1: ...ommendations Itisrecommendedthatthedevice s bekeptatroomtemperature for at least 24 hours before installation to allow any condensation that may have accumulated due to low temperature during shipping storage to evaporate Upon unpacking the product inspect the contents of the carton for shipping damages Do not install damaged devices The device is designed to operate under environmental conditions...

Страница 2: ... 20 58 2 28 82 3 23 5 0 20 10 0 40 5 0 20 7 0 28 7 0 28 mm inches Figure 2 Q RCU D xx Back plate view 84 3 30 55 2 17 Ø7 0 28 12 0 47 23 0 90 2 0 08 23 0 90 4 0 16 25 0 98 75 2 95 22 0 87 Figure 3 Q RCU D L Light Blind add on modules Front view and side view 4 0 16 9 0 35 5 0 20 38 1 50 9 5 0 37 mm inches Figure 4 Q RCU D L Light Blind add on modules Back plate view 2 8 Installation Guide 26 604_E...

Страница 3: ...l if necessary 9 Unplug the Q RCU D L Light Blind add on modules from the back plate if applicable 10 Pull all RJ 45 cables and digital wires if applicable 15 cm 6 out of the wall and insert them through the central hole of the back plate 11 Screw the back plate onto the wall Do not over tighten 12 Set the Subnet ID and the EOL termination with the dipswitch as explained in section Setting the Q R...

Страница 4: ...em responsiveness This may be the origin of a certain delay which could be an issue for commands needing a fast response such as lighting and shades sunblind commands 2 The indicated adressing ranges are specific for each group of device 4 different Subnet ID codifications are used on the Q RC Subnetwork 1 for Q RCU LCD sensors 1 for Q RCU D xx and Q RCU DC xx sensors 1 for Q RCS MS PL multi senso...

Страница 5: ...ch cable fitted with RJ 45 connectors If you make your own patch cable use Cat 5e cable and crimp the RJ 45 connectors at both ends of the cable either as T568A or T568B Table 2 T568A and T568B Terminations for an RJ 45 Connector Pin T568A at both cable ends T568B at both cable ends Pair Color Pair Color 1 3 white green stripe 2 white orange stripe 2 3 green solid 2 orange solid 3 2 white orange s...

Страница 6: ...hain topology is acceptable for the room device subnetwork bus T connections are not allowed Onla the EOL terminations of the last subnetwork bus device are set to ON All other subnetwork bus devices must have their EOL terminations set to OFF The controller must be the first device on the Cat 5e Cable Subnetwork bus as its internal EOL termination is permanently enabled See Table 2 Number of room...

Страница 7: ... Directive applies to standalone products for example products that can function entirely on their own and are not a part of another system or piece of equipment For this reason SBC products are exempt from the WEEE Directive Nevertheless SBC products are marked with the WEEE symbol indicating devices are not to be thrown away in municipal waste Products must be disposed of at the end of their use...

Страница 8: ...y Saia Burgess Controls AG 2016 All rights reserved Postal address for returns from customers of the Swiss Sales office Saia Burgess Controls AG Service Après Vente Bahnhofstrasse 18 3280 Murten Switzerland Saia Burgess Controls AG Bahnhofstrasse 18 3280 Murten Switzerland T 41 26 580 30 00 F 41 26 580 34 99 www saia pcd com support saia pcd com www sbc support com 8 26 604 ENG01 02 2016 Technical...

Отзывы: