Saia-Burgess Controls AG  
Bahnhofstrasse 18 
3280 Murten / Switzerland  
T+ 41 026 580 30 00 
www.saia-pcd.com 
 

 
 
 

 

26-008 ENG06   04-2016 

PCD7.L200 Output module with 4 relays, 250VAC/6A

 

 
Description 

The RIO module was developed as a S-Bus data node for local switching tasks. Via a PLC of the type PCDx / PCS1 outputs can be set and manual/auto function monitored. Two 
address switches (x1 / x10) on the front panel allow module addressing and identification. Addresses can be set between 00 and 99. Up to 100 RIO modules and a maximum of 3 
PCD stations can be connected to one bus branch simultaneously. If the bus cycle time is critical, fewer than 30 slaves should be operated in one segment. 
 

Technical data 

Bus system 

S-Bus 

Transmission rate 

1200... 38400 

Transmission mode 

Parity / Data 

Bus length  max.  

1200 m (without  repeater) 

Nominal voltage UN 

18VDC...32VDC / 20VAC...28VAC 

Current consumption 

<50mADC / <80mAAC 

Power consumption 

1.2W / 2VA 

Relative duty cycle 

100 % 

Reaction time 

15 ms 

 

(from receive data to  

 

 send data reaction) 

Recovery time 

< 200ms 

Operating temperature range 

0°C... +55°C 

Storage temperature range 

-25°C...+70°C 

Protective wiring 

Reverse battery protection of service voltage 

 

Reverse battery protection of supply and bus 

 

EMC according to DIN EN 61000-6-2 

Input state indicator 

Yellow LED 

Function indicator 

Green LED for bus activity 

Status indicator 

Red LED for bus error message 

Special features 

Manual control level with revertive 

 

communication via bus; 

Test voltage: 
Relay contact / bus 

4000Veff 

 

Output side 

Number of outputs 

4, electrically isolated “make” contacts 

 

Turn-on voltage 

max 250VAC 

Constant current 

6A per relay, max. 12A 

 

 

Switching frequency 

max. 6/min at rated load 

 

Housing 

Protection class 

Housing IP50 / Terminals IP20 

Humidity class 

F (DIN 40040) 

Connection cross-section 

2.5 mm2 (terminals) 

Plug-in terminal 

1.0 mm2 (screw-type) 

Mounting position 

any 

Weight 

95 g 

Housing dimensions 

WxHxD: 35 x 70 x 74 mm 

Joined without spacing 

After 15 modules have been joined 

 

in sequence, the external supply voltage  

 

must be reapplied. 

 

Data transmission 

All S-Bus instructions (level 1) are recognized. Instructions that have no function in the device are answered with <NAK>.  
The module has integral, automatic baud rate and transmission mode recognition. “Output” 1 to 12 can be called together.

 

 
 

"Display Output / Write Output”  

 

“Display Output”   

Address 

Information  

Address 

Information 

 

 

 

0= Status relay 1 off 

0= relay 1 switched via bus 

 

 

1= Status relay 1 on  

 

1= relay 1 switched via manual control 

 

0= Status relay 2 off 

0= relay 2 switched via bus 

 

 

1= Status relay 2 on  

 

1= relay 2 switched via manual control 

 

0= Status relay 3 off 

0= relay 3 switched via bus 

 

 

1= Status relay 3 on 

 

1= relay 3 switched via manual control 

 

0= Status relay 4 off 

0= relay 4 switched via bus 

 

 

1= Status realy 4 on  

 

1= relay 4 switched via manual control 

 

 „Display Register" 

 

Status register (register 7):

 

 

 

Address 

Information 

 

Bit 0: 

1= Device recognized last transmission 

 

Baud rate (plain text => kBit/s)  

 

 

0= Device did not recognize last transmission 

 

Module address 

 

Bit 1: 

1= Last transmission was a broadcast 

 

Status register 

 

 

0= Last transmission was not a broadcast 

 

Bus timer 

 

Bit 2: 

1= Last transmission came from master 

 

Current transmission mode  (data / parity) 

 

 

0= Last transmission came from a slave 

 

10 

Bus error counter (divided into 4 bytes) 

 

Bit 3: 

1= CRC of last message was correct 

 

 

 

 

 

0= CRC of last message was incorrect 

The following registers can be called together 

 

Bit 5: 

1= Device has executed an internal reset 

(Display Register "x" to "y") 5 to 7  /  8 to 10 

 

 

0= Device function is OK 

 

 

 

 

Bit 8: 

1= Internal bus to EEPROM is OK 

"Write Register"

 

 

 

0= Internal bus not working perfectly

 

Address 

Value 

Baud rate setting (Baud kbit/s) 

Bit 9: 

1= EEPROM data memory is OK 

 

 1 200 

 

0= EEPROM data memory is faulty 

 2 400 

Bit 10: 

1= Baud rate uploaded from EEPROM 

 4 800 

 

0= Baud rate is at default value (9600 Bd.) 

 9 600  

Bit 12: 

Switch 1:  0=Automatic  1=Manuel 

19 200 

Bit 13 

Switch 2:  0=Automatic  1=Manuel 

38 400  

Bit 14 

Switch 3:  0=Automatic  1=Manuel 

 

Bit 15 

Switch 4:  0=Automatic  1=Manuel

 

Address 

Value range 

Meaning 

All other bits are reserved for factory tests. 

 

2 <-> 20 

20 <-> 200 ms 

 

Bus timer (register 8) 

The value displayed indicates how long the module waits until a telegram is complete. The time is shown in 10 ms steps (e.g.: value 20 => a time of 200 ms). The recommended 
time is 100 ms, i.e. a register value of 10. If the time is reduced, modules will react faster to telegrams from the master. If there is a heavy load on the master station, a bus timer 
setting that is too low may lead to lost telegrams. Times of less than 20 ms (value 2) are not permitted. 
Times that reach the master station within 20 ms of the timeout will lead to lost connections. The value is stored in EEPROM and protected against voltage loss. ( Factory setting : 2) 
 

"Write Register" 

"Write Output" 

Address 

Value 

Meaning 

The write output instruction at address 255 is recognized as broadcast message. 

 

Parity mode  

Automatic baud function: “Write or Display output 255” (1 = autobaud active  /  0 = autobaud inactive) 

 

 

Data mode 

 

 

 

(factory setting) 

N.B:

 

 

 

After a power failure, the last baud rate set will be reinstalled.

 

Address 

Value 

Meaning 

 

 

10 

Reset of error 

For further information on the use of modules linked to S-Bus, including all restrictions, see documentation 26/339 E2

 

 

 

 

count register 

 

 

 

 

 

Address 

Value 

Meaning 

 

 

11 

Bustimout deactivated 

 

 

1 – 255 

Time in 1 second steps -> 

switches the outputs to switch state defined in Output 9-12, by no bus activity within the set time will be registered

 

Mounting and commissioning to be conform with 
current regulations: 

 
1. 

Power-off the installation 

2. 

Place module onto 35mm tophat rail and press 
down to engage. 

3. 

Strip insulation from 7mm of cable (max. single 
wire 4mm2, fine strand 2.5 mm2, diameter 
0.3 mm to 2.7mm), insert into binding and 
tighten with a screwdriver. 

 
Connect supply voltage and field bus to plug-in screw 
terminal. 
 

Caution!! 
Plug-in terminal has max. 1.0mm2 connection 
cross-section. Check correct connection of bus 
lines and supply. 
 
The relay output module is EMC proved (electro 
magnetic compatibility)  up to an amplitude of 2000 
V. Voltage peaks caused by higher inductive loads 
may initiate a module reset. In such cases it is 
recommended to protect the relay contacts by an 
additional RC element. 
 

Operational safety: 

Please take care to following points 
for a safety operation: 

-  Maximal cable length  

-  S-Bus member and segment 

division 

-  Potential compensation by one 

single grounding of power supply  

-  Termination of both network sides  

-  Cable shield grounding on one 

side only.  

Connection example 

Supply and Bus concept

 

"Display/Write Output" 
 
"Display Output" 

Adresse 

Information

 

 

Adresse 

Information

 

 

 

 

0= Initial State relay 1 

off  5 

0= Zustand Kanal 1 nach Businfo 

 

 

1= Initial State relay 1 

on 

 

1  Z stand Kanal 1 nach 
 

 

 

      

 

 

 

 

  

 

 

 

 

 

 

 

   

 

 

 

 

  

 

 

 

 

      

 

 

 

 

  

 

 

 

 

      

 

 

 

 

  

 

 

 

 

      

 

 

 

   

   

 

 

 

 

 

  

 

 

 

 

  

 

 

 

 