Warning
Please read these instructions carefully before commencing any work.
This unit must be fitted by a competent and qualified electrician.
Install in accordance with the IEE Wiring regulations and current Building Regulations.
Check the pack and make sure you have all the parts listed.
To prevent electrocution switch off at the mains supply before installing or maintaining this fitting.
Ensure other persons cannot restore the electrical supply without your knowledge.
If replacing an existing fitting, make a careful note of the connections
The mains supply cable must have a minimum cross section area of 1.0mm
2
Cables must be protected using suitable conduit or plastic trunking.
This product complies with IEE Building Regulations part B and is suitable for use in 30, 60 or 90 minute fire rated ceilings.
This luminaire is suitable for use in ambient temperatures of -10°C to +40°C.
This system contains non-replaceable parts and cannot be serviced. If damage occurs the part should be scrapped.
This product is suitable for dimming.
This luminaire can be loosely covered with mineral wool insulation material. However, minimum clearance distances
around the luminaire must be observed: 25mm above the top of the luminaire.
Waste electrical products should not be disposed of with household waste. Please recycle where facilities exist. Check with
your local authority or retailer for recycling advice.
Thank you for purchasing this light fitting. Please read the instructions carefully before use to ensure safe and satisfactory
operation of this product. Please retain these instructions for future reference.
This light fitting is double insulated and does
not require connection to an Earth circuit.
Installation
Existing fittings must be completely removed before installation of a new product. Before removing the existing fitting,
carefully
note the position of each set of wires.
The ceiling surface must be flat and smooth to ensure a good fit.
Note that the switch is turned off before installation.
Ensure that the screws and cable entry points are sealed to maintain the IP rating of the product.
This product is colour changing and can be either warm white (3000K) or cool white(4000K) or daylight white (6000K)
Choose your preferred colour before installing by using the switch on back of the driver.
WW (3000K)
CW (4000K)
DW (6000K)
• Cut a mounting hole
70mm
diameter in the ceiling taking care not to foul any pipes, mains cables or joists beneath the
surface (
Ref. Fig.1
). It is always recommended to cut the hole slightly smaller than the size specified, and then file the hole
until the recessed unit fits snugly. Ensure a minimum ceiling void depth of
57mm
is available.
• Ensure that the product is sitting properly in the hole.
• Open the terminal block cover, Connect the mains supply cable into the terminals (
Ref. Fig. 2
).
• Push the spring clips upwards and fit into the ceiling hole, then push the unit up until firmly in position, ensuring that no
cables are trapped. (
Ref. Fig. 3
).
• Switch on. Your light is now ready for use.
Fig. 1
Fig. 3
Cut hole Dia: 70mm
Minimum cavity depth: 57mm
The terminal block allows for
Loop-in / Loop-out connection.
Terminations:
Live supply to L = ( Brown or Red )
Earth to
= ( Green / Yellow )
Neutral to N
= ( Blue or Black )
L
L
N
N
Fig. 2
Layout
Plan the desired layout of these fittings carefully, ensuring the cables will reach the distances between each light fitting.
Avoid locating any cables in positions that would cause a hazard. Position cables and junction boxes (not supplied) away from
areas where they may be at risk from being cut, trapped or damaged.
The mains supply cable must have a minimum cross section area of 1.0mm
2
.
When more than one downlight is installed, the minimum distance between units is 500mm. the unit must be located a
minimum distance of 50mm from a joist.
This product must be mounted out of arms reach.
This product is suitable for use in outside zones of a
bathroom only. Please see diagram.
If this unit is being fitted in a room containing a bath or
shower, a 30mA RCD must be used - in accordance with
IEE regulations.
Zone 1
Outside zones
0.6m
0.6m
2.25m
Zone 2
Zone 2