Other possible problems are:
If error E4 or E6 is displayed, there is
a problem with the bench sensor. If
only one sensor is installed, the steam-
er cannot be used. The user can
confirm the error by pressing the
on/off button, after which the heater
will function normally, but the steamer
cannot be used.
The user switches the steamer on and
“dry” is displayed immediately. Check
that the “empty” and “tank level”
terminals from the heater are
connected with the “empty” and the
“tank level” in the Power Controller.
The steamer is on and “dry” is
displayed, even though there is plenty
of water in the tank. Make sure that
terminals “empty” and “tank level” are
correctly connected to the right
terminals in the Power Controller.
The steamer is switched on and “dry”
is displayed immediately. Make sure
that the “WB” terminal from the heater
is connected with the “tank level” in
the Power Controller. Check that the
“UB” terminal from the Power
Controller is connected to the “empty”
terminal in the Power Controller.
When the user turns the steamer on
and “Fill” is displayed continuously, the
wiring needs to be checked. Make sure
that the “UB” terminal from the
controller is connected to the “empty”
terminal in the Power Controller. In
addition, the “WB” terminal from the
heater needs to be connected to the
“tank level” in the Power Controller.
The control unit is attempted to be
switched on with the power button and
nothing happens or the software
version/logo is displayed shortly. The
problem may be low battery that does
not have enough power to display
“LbAt”. Change the battery inside the
Power Controller.
Door open symbol is displayed with
high warning tone, when door sensor
is not installed. - Check that door
switch terminals are connected with
each other by wire in the power
controller. (See fig. 2/Sensors. Note
that the connections is not present in
the drawing.
English
The control unit is working fine, but the
heater does not turn on. Check the
electricity supply to the heater. Check
that the wires for the sensors are
placed into the correct terminals in the
control unit.
The control unit cannot display the
relative humidity* (only when the
combined sensor is installed). The
combined sensor cannot be
recognised. The wires for the sensor
are placed in the wrong terminals.
Control unit doesn’t turn on and
clicking sound can be heard. Check
that the N2 in jumper is connected with
N (refer to technical diagram). Check
also that fuse F1 (near transformer) is
tightly in fuse holder.
User presses a button and “----“ is
shown in the display. This indicates that
the key pad is locked. Unlock the
buttons by pressing up and down
arrow keys at the same time for more
than 5 seconds. A high beep will
confirm the activation and the
deactivation.