SEC-M500 Elevator Controller 

User manual

 

 

 

 

User Manual

 

Содержание SEC-M500

Страница 1: ...SEC M500 Elevator Controller User manual User Manual ...

Страница 2: ...4 08 SAVCH electric provide a full range of technical support for our customers All users could contact with the nearest SAVCH office or service center also could contact with our headquarters directly SAVCH Electric reserves the copyrights and all rights Subject to change without further notice ...

Страница 3: ...l calling display board SEC E01 13 3 3 Car board SEC C01 15 4 Operation interface 19 4 1 Brief introduction 19 4 2 Operation introduction 20 4 3 Instruction of permission login 22 5 Function parameter list 23 6 Function parameter description 31 1 User menu 31 2 Setup menu 33 3 Running menu 39 4 Time menu 45 5 Option menu 48 6 Debug menu 49 7 View menu 52 7 Failure indication and countermeasures 55...

Страница 4: ...e even death may be caused CAUTION If not used correctly serious damage to inverter or machine may be resulted DANGER Never connect wires while power on Do not check components or signal for circuit board during operation Do not dismantle or change inner wire circuit or components unnecessarily CAUTION Do not perform a withstand voltage test for components of inverter it can cause semi conductor c...

Страница 5: ...The product must be tested under finishing install the electrical protection and electrical safety circuit Wet hands are strictly prohibited to operate Otherwise it might get electrocuted Otherwise it may cause an electric shock The shaft way self leaning acts only when the electrical input signal is normal and the car is located in the bottom Before testing of automate operation system please ens...

Страница 6: ...mable materials Extreme low temperatures Extreme high ambient temperatures Above 40 Large impelling Salt or saline Rain moisture Iron chips and dust Electromagnetic waves and ultra high angle rays For example locations of welding machines and etc Oil cool Below 10 degrees Celsius Force Force Force Force Force Force Salt 40 ...

Страница 7: ...ling When the running direction changed system cancels all car callings 10 Re leveling when the door is open The lift stop at the floor station a large number of persons or goods entering and leaving The leveling fluctuated because of the elastic deformation of elevator Wire Rope and the rubber System allows run automatically at the speed of re leveling to leveling station in the state of the door...

Страница 8: ...is as below signal orientation driver selection orientation without automatic close door by pass function and so on 25 VIP operation When VIP operation the elevator can not response to hall calling and only for one target floor in each operation 26 History fault record It recorded 20 faults including fault content time and so on Firefighting and safety 27 Firemen operation When fire mode back to b...

Страница 9: ...it of the terminal station and the limit of first level down speed And before each starting the pulse on the floor is calibrated 36 LCD HMI Board with keyboard LCD display Chinese English Compared with the digital tube the information display is more comprehensive and clear which makes it easy for users to interact with each other 37 Host learning At the mode of inspection users set this function ...

Страница 10: ...7 3 PRODUCT INTRODUCTION 3 1 Main control panel SEC M500 3 1 1 External dimension Figure 3 1 outlook of main control panel SEC M500 Figure 3 2 installation dimension of main control panel SEC M500 ...

Страница 11: ... 3 2 power terminal distribution J1 1 24V DC24V positive pole power J1 2 24VGND DC24V power negative pole power J1 3 24VGND DC24V power negative pole power J1 4 24V DC24V positive pole power Common optical input SEC M500 has 26 common optical isolation inputs at J2 J3 J4 Figure 3 3 common optical Circuit diagram Table 3 3 input feature Input Photoelectric coupling isolation Type of voltage input 1...

Страница 12: ...intenance state 1 0 X9 J3 1 Down landing signal under maintenance state you can point to run the elevator down to the lower limit signal action the elevator stops running 0 1 X10 J3 2 Up landing signal under maintenance state you can point to run the elevator uplink up to the limit signal action the elevator stops running 0 1 X11 J3 3 Operation contactor feedback it is effective when running conta...

Страница 13: ... definition of the port logical properties have not changed you need to return the port logic back to the dynamic signal c If Alternate input function setting is the same as the default function the standby input function port is priority and the default function port is invalid spare input port setting should be paid attention d The active level of all inputs is 24V GND High speed optocoupler inp...

Страница 14: ...e of input Photoelectric coupling isolation Type of voltage input 1 signal AC70 120V 0 signal AC0 70V Type of current input 1 signal 4 10mA 0 signal 0 2mA Delay 10ms Input frequency 100Hz Allow length of wire Shield 1000 meters Non shield 800 meters Table 3 8 distribution Iterm Terminal Type Definition default working state Logic level X27 J6 1 Digital input Safe safety circuit high voltage acquis...

Страница 15: ...mon terminal of relay contacts Y1 J7 2 Digital output Running output COM1 Y2 J7 3 Digital output Brake output COM1 Y3 J7 4 Digital output Input control COM1 Y4 J7 5 Digital output Brake keep contactor control output COM1 Y5 J8 2 Digital output Down landing signal COM2 Y6 J8 3 Digital output Up landing signal COM2 Y7 J8 4 Digital output Section speed 1 COM2 Y8 J8 5 Digital output Section speed 2 CO...

Страница 16: ...board SEC E01 3 2 1 External dimension Figure 3 7 outlook SEC E01 of hall calling display board Figure 3 8 installation dimensions of hall calling display board SEC E01 3 2 2 Port instruction The hall calling display board unit is as a device for displaying the number of floors and other information Meanwhile hall calling signal and response lamp are handled by hall calling display board unit The ...

Страница 17: ... button and indicator light wiring of hall call Fire and elevator lock wiring Figure 3 11 the display board fire elevator lock and indicator light wiring of hall call Distribution Table 3 11 distribution Port Function J5 Power supply and communication port J1 Up landing calling button port J2 Down landing calling button port J3 Fire input signal port J4 Lift locking input signal port ...

Страница 18: ...lay F that means the front door address setting is available and you can observe the address from 0 increments When arrive at the floor you want to set press the button finish the setting If user presses Continously the button behind the display panel four times the board will display B that means the back door address setting is available The other operation is same to front door setting 3 3 Car ...

Страница 19: ...er lamper The SEC C01 is equipped with 16 input ports when voltage is low it is effective two empty relay and four open collector output ports as function input and output ports Button wiring Figure 3 14 button wiring Answer lamp wiring Figure 3 15 answer lamper wiring Input port Figure 3 16 input port ...

Страница 20: ... input J10 Power DC24V negative power input A J10 Communication A Communication A B J10 Communication B Communication B X1 J6 1 Digital input Light load signal input X2 J6 2 Digital input Full load signal input X3 J6 3 Digital input Overload signal input X4 J6 4 Digital input Driver signal input X5 J6 5 Digital input By pass signal input X6 J6 6 Digital input Special for fire signal input ...

Страница 21: ...ital input Door 2 open limit signal input X15 J5 7 Digital input Door 2 close limit signal input X16 J5 8 Digital input Light curtain 2 Y1 J4 1 Digital utput Power management output Y2 J4 2 Digital utput Bell control output Y3 J4 3 Digital utput Door open indicator Y4 J4 4 Digital utput Door close indicator Y5 J4 5 Digital utput Beep output Y6 J4 6 Digital utput Keep door open indicator Fn J7 J8 D...

Страница 22: ...uction Table 4 1 Key introduction Key Introduction ESC 1 Return to the previous menu 2 Cancel the input when input data UP 1 Move up a option when select function 2 1 at current number when input data DOWN 1 Move down a option when select function 2 1 at current number when input data RIGHT 1 Move right a option when select function 2 Move the cursor left when input data ENTER 1 Enter when select ...

Страница 23: ...eter selection User parameters function parameters operating parameters time parameters optional parameters commissioning parameters monitoring parameters etc 7 parameters for option Each parameter option also has sub menu of second third level function selection Detailed function After entering the corresponding specific function the specific function parameter value can be viewed and modified 4 ...

Страница 24: ...21 4 2 2 Spare input X21 function set ...

Страница 25: ...eters User level Value range Default value Value instruction Remark Ordinary user 000000 99 9999 000000 Common user can modify the parameters for the corresponding permissions but the debug mode and senior user parameters can not be used Advance user 000000 99 9999 000000 Senior user can modify the parameters that ordinary users can modify but also can enter the debug mode which refers to the debu...

Страница 26: ... The debug mode is available under senior password state Super user 1 3 000000 999999 000000 1 Input the password then the 7 major directories are available 2 Only 7 contents 3 Input passwords first Speed command mode 2 0 1 0 0 Multi speed mode 1 reserve analog mode Parameter backup reset 3 0 3 0 0 no effect 1 Restore factory fault value 2 Restore to user backup value 3 Back up user parameters Lan...

Страница 27: ...nput port X21 X26 Spare output selection 8 0 Select function of output port Y15 Y18 Input Type Enter 9 Set input port X1 X26 Set Indication 10 Select the display code for each floor Set Stop Floor 11 0 stop 1 no stop Set Jump Floor 12 0 no jump 1 jump Door Select 13 0 no open 1 open Locks selection 14 0 2 0 0 Lock is effective only under low voltage 1 Lock is effective only under high voltage 2 Lo...

Страница 28: ...ns as closing under normal situation Forced Close 19 0 1 1 Light curtain block 0 No action 1 Action Inspect Open function 20 0 3 3 0 No effect 1 Maintenance order close 2 Maintenance to open normally 3 Both effect Inspect Open Button function 21 0 1 1 0 Effective at level 1 Effective at any place Brake Limit FB 22 0 1 0 0 Close 1 Open Load Setting 23 0 1 0 0 As per loading signal of connection or ...

Страница 29: ... DecelDistanceS 14 0 9 990 m 1 500 DecelDistanceS 15 0 9 990 m 1 500 DecelDistanceS 16 0 9 990 m 1 500 Leveling Adj 17 0 99 mm 0 Speed command 1 the mode function is reserved speed order mode analog mode Car Speed 1 0 200 6 000 m s 1 000 Motor Speed 2 50 9999 rpm 1440 Encoder Pulses 3 100 9999 ppr 1024 Max Running speed 4 0 200 6 000 m s 1 000 Inspection Speed 5 0 000 0 500 m s 0 250 Emergency spe...

Страница 30: ...own landing decrease down adjustment Down Adj 19 0 000 0 100 m 0 050 DAC Update 20 0 001 0 100 Sec 0 010 4 Time menu Item No Range Unit Default value Remark RunDelayTime 1 0 9 9 Sec 0 1 When enable is effective delay to give direction Brake On Time 2 0 9 9 Sec 0 1 Start Spd Time 3 0 9 9 Sec 0 2 Brake Off Time 4 0 9 9 Sec 0 1 Stop Time T1 5 0 9 9 Sec 0 6 Stop then extend last release running contac...

Страница 31: ...g time Landing WTD 21 5 99 Sec 50 It is fault if one level enter door area and the other does not enter door area 5 Option menu Item No Range Unit Default value Remark Emergency run 1 0 1 0 0 None 1 Emergency run reserve Car Function Sel 2 0 4 0 0 Disable 1 EnInDriverMode 2 Enable In Auto 3 AllMode Enable 4 EnBeepIn Driver Advance Door Open 3 0 1 0 0 No 1 Yes reserve Re level When Open 4 0 1 0 0 N...

Страница 32: ...ault value Remark Self learning start 1 User calling 2 1 total floor quantity When user calling enable both hall calling and car calling disable Enable user calling 2 1 0 1 0 0 Disable user calling 1 Enable User Calling User call open 2 2 0 1 0 0 Disable 1 Enable User call Enter 2 3 0 total floor quantity the present floor The car calling and hall calling functions can be simulated Automatic runni...

Страница 33: ...up call information Hall Down Call 7 Check hall down call information Com1 State 8 Check the communication point connected with communication port 1 Com2 State 9 Check the communication point connected with communication port 2 Reserve 10 Reserve 11 Floor Height 12 Check the floor height of each one Level Length 13 m 0 Use to check after self learning Down Spd Limit 14 m 0 Up Spd Limit 15 m 0 Down...

Страница 34: ... Range 0 MultiSpdMode 1 AnalogMode Reserved This parameter is control inverter mode and frequency given mode 3 Para Reset Default value 0 Range 0 Disabled 1 Reset to Def reset all parameters to default value factory default value 2 Reset to Bak reset all parameters to user backup value 4 Bak UserPara save all parameters to the user backup area 4 Language Sel Default value 0 Range 0 Chinese 1 Engli...

Страница 35: ... precedence over the service time that is the service time is invalid when the service number is valid Enter into below screen when the service number is not set ServiceNumTips 00000000 Enter into below screen when the service number is set ServiceNumTips 00000000 Random number Remaining number Enter into below screen when the service time is not set ServiceTimeTip 2000 00 00 00 Enter into below s...

Страница 36: ...Range 0 Single elevator 1 Parallel A elevator 2 Parallel B elevator In parallel for the AB elevator running mode A elevator as the main control elevator performs the scheduling control B elevator as the salve elevator accept the scheduling of A elevator 6 Ctrl Type Default value 0 Range 0 Full Collective 1 Up Collective 2 Down Collective Full Collective Hall Up Call Hall Down Call are both Respons...

Страница 37: ...uto 16 Insp Up 17 Insp Down 18 Down Leveling 19 Up Leveling 20 MotorOverH 21 Reserved 22 InvRunning FB 23 InvFaultSignal 24 Fire signal 25 LiftLockSignal 26 DoorOpenButton 27 DrClose Button 28 Dr1 Open Limit 29 Dr1 CloseLimit 30 Light Curtain1 31 Door2Openlimit 32 Dr2 CloseLimit 33 Light Curtain2 34 Overload 35 Full load 36 Light load 37 Driver Ctrl 38 Bypass 39 VIP ...

Страница 38: ...ort function the Spare Sel has a higher priority than the default port 8 SpareOutputSel Default value 0 Range 0 Disable 65 Speed 1 66 Speed 2 67 Speed 3 68 Up Cmd 69 Down Cmd 70 Reset Inverter 71 Run Contactor 72 Inv Run Enable 73 Front Door Open 74 Front Door Close 75 Back Door Open 76 Back Door Close 77 Brake Ctrl 78 Brake Hold Ctrl 79 Inv Power Ctrl 80 Light Ctrl 81 Reserved Reserved 88 Reserve...

Страница 39: ...Enter Default value 0 Range 0 Normal closed is enabled 1 Normal open is enabled Can set the InputTypeEnterto X1 X26 10 Displayset Indication Default value 0 Range 0 Display 0 1 Display 1 2 Display 2 47 Display 47 48 Display 48 49 Display B1 50 Display B2 51 Display B3 52 Display B4 53 Display A 54 Display B 55 Display C 56 Display D 57 Display E 58 Display F 59 Display 1 60 Display 2 61 Display 3 ...

Страница 40: ...arallel set the no stop floor that is required to jump 13 Door Select Default value 0 Range 0 Non open 1 Open 14 Locks Correct Default value 0 Range 0 Only Enable LV 1 Only Enable HV 2 All Enabled 15 Safety Correct Default value 0 Range 0 Only Enable LV 1 Only Enable HV 2 All Enabled 16 Auto Level Sel Default value 3 Range 0 None 1 Refer to Load Reserved 2 Up Landing 3 Down Landing 4 Short Landing...

Страница 41: ...cked Default value 1 Range 0 Close 1 Open 20 Insp Door Enter Default value 3 Range 0 Disabled 1 Insp Cmd Close 2 Open Insp2Auto 3 All Enabled 21 Insp Open Button Default value 1 Range 0 Enable In Dr Zone 1 All Enabled 22 Brake Limit FB Default value 0 Range 0 Close 1 Open 23 Load Setting Default value 0 Range 0 Given by load SW 1 Given by load SW and load fuzzy determination This function is reser...

Страница 42: ...f call layers in the car exceeds 2 that is all the number are cancelled 3 Running menu MultiSpdMode 01 Car Speed m s Default value 1 000 Range 0 200 6 000 This parameter is related to calculating the elevator speed therefore it needs to be set correctly 02 Motor Speed rpm Default value 1440 Range 50 9999 This parameter is related to calculating the elevator speed therefore it needs to be set corre...

Страница 43: ...8Y9 output when inspection 09 User Spd Sel Default value 5 Range 0 8 Select the inverter step speed control by Y7Y8Y9 output when user define the floor 10 V0 Spd Sel Default value 6 Range 0 8 Select the inverter step speed control by Y7Y8Y9 output when the distance is single floor 11 V1 Spd Sel Default value 7 Range 0 8 Select the inverter step speed control by Y7Y8Y9 output when the distance is d...

Страница 44: ...C M500 control SAVCH elevator dedicated inverter S3500 take the multi step speed logic control timing diagram Figure 6 1 speed logic time chart a b The time interval from running the contactor effective to a given enabling b c Specifies the time interval for a given run direction c d The time interval from the given direction to the brake output ...

Страница 45: ...efault value 1 500 Range 0 9 990 The distance from single speed to deceleration speed in advance 15 DecelDistanceS m Default value 1 500 Range 0 9 990 The distance from double speed to deceleration speed in advance 16 DecelDistanceS m Default value 1 500 Range 0 9 990 The distance from multi step speed to deceleration speed in advance The following table shows the recommended deceleration distance...

Страница 46: ...ue 1024 Range 100 9999 This parameter is related to calculating the elevator speed and needs to be set correctly 4 MaxRunningSpd m s Default value 1 000 Range 0 200 6 000 The running speed is not more than this speed 5 Insp Speed m s Default value 0 250 Range 0 000 0 500 The running speed when the elevator is during inspection 6 EmergencySpd m s Default value 0 250 Range 0 000 0 630 The running sp...

Страница 47: ...Range 0 100 9 999 Start the beginning of the initial bending time 13 S Curve T2 s Default value 1 100 Range 0 100 9 999 Start the end of the initial bending time 14 S Curve T3 s Default value 1 100 Range 0 100 9 999 Decelerate the beginning of the initial bending time 15 S Curve T4 s Default value 1 100 Range 0 100 9 999 Decelerate the end of the initial bending time 16 Slowdown Adj m Default valu...

Страница 48: ... when down the down leveling adjust 20 DACUpdateTime s Default value 0 010 Range 0 001 0 100 The time interval when the analog output is updated 4 Time menu 1 RunDelayTime s Default value 0 1 Range 0 9 9 After the inverter enabling how long it extend before giving direction 2 Brake On Time s Default value 0 1 Range 0 9 9 After the running signal is given how long it extends before brake output 3 S...

Страница 49: ...op how long it extends before opening 9 BrakeHold Time s Default value 1 0 Range 0 9 9 The delay time from brake output to brake hold 10 Door Open Time s Default value 10 Range 2 99 Door Open Time 11 DoorOpen Time s Default value 10 Range 1 99 The time from car run to door open time when the open is on 12 DoorOpen Time2 s Default value 10 Range 1 99 The time from outgoing call to door open time wh...

Страница 50: ...alue 1 Range 0 9 9 It indicates the bell hold time 18 Homing Time min Default value 10 Range 0 60 The car has no run operation to reach this time and is not in the Homing floor Return to homing floor operation When it is 0 it is disabled 19 PulseLost Time s Default value 1 Range 0 1 5 0 Non zero speed and non zone state to monitor the pulse loss and output alarm 20 Car Stuck Time s Default value 4...

Страница 51: ...The second function of the buzzer except output alarm 3 AdvanceDrOpen Default value 0 Range 0 Close 1 Open This function is reserved 4 Re levelWhenOp Default value 0 Range 0 Close 1 Open This function is reserved 5 LandS W Select Default value 1 Range 0 P2P Level 1 Up Down Level This function is reserved 6 StartTimeEnter Default value Range 24hour mode 7 StopTime Enter Default value Range 24 hour ...

Страница 52: ...on of the parameters reserved is the planning development function but the current version can not support the function temporarily 6 Debug menu 1 Calibration Default value Range EnterPush enter button to perform Parameter acquisition This is the installation location of the flat plate In principle the control system enter into stop processing immediately once collect the up and down level after t...

Страница 53: ...tem has normal operating conditions h All safety components are working properly upper and lower limit limit device is reliable i No dirt in the well After meet the above conditions set the parameters the calibration starts After confirmation start the calibration the elevator will run to the max speed with the inspection speed from the bottom with the first level under the forced deceleration swi...

Страница 54: ...heck the input attributes of SpeedLimit SW Err70 FloorNumErr 1 Check the maximum number of the setting floor 2 check the number of separate plate 3 check the installation position of the separate plate Err71 Scale2 Small Within 10mm pulse number should meet the standard0 p 255 Err72 Scale2 Large Err73 FloorDataErr Err74 No Pulse No pulse input during operation Note Besides other failure will be po...

Страница 55: ...t learning needs to be carried out in maintenance mode The output contactor and frequency converter enable output when entering the host learning 7 View menu 1 Fault Report Default value Range Inquiry history fault report 2 Running Report Default value Range Check the running times 3 I O InputState Default value Range The valid state is indicated by and the invalid state is indicated by 4 I O Outp...

Страница 56: ...d state is indicated by 8 Com1 State Default value Range The valid state is indicated by and the invalid state is indicated by 9 Com2 State Default value Range The valid state is indicated by and the invalid state is indicated by 10 Reserved Default value Range 11 Reserved Default value Range 12 FFloor Height Default value Range Inquiry the height of each floor indicated by pulse number it can be ...

Страница 57: ...ault value Range It can be checked after calibration 16 Down SpdLimit2 m Default value Range It can be checked after calibration 17 Up Spd Limit2 m Default value Range It can be checked after calibration 18 Device Number Default value Range This function is reserved 19 Soft Version Default value Range ...

Страница 58: ...ystem stuck 3 Crane does not work or slippery Close button or check reset 8 Inv Fault Inv Fault 1 Inverter works out of work 2 Inverter parameter error 3 The fault signal port logic attribute is set incorrectly Auto reset 9 NoInvRunFB Inverter run command error 1 Inverter works out of work 2 Inverter parameter error 3 The fault signal port logic attribute is set incorrectly Auto reset 10 LostInvRu...

Страница 59: ...e counter is enabled The high speed running time between adjacent two door zones exceeds the time set by the car stuck timer No reset stop to keep fault 20 MotorOverH Motor Over Heat 1 Motor temperature detection switch enabled the motor overheat 2 The motor temperature detection signal port logic attribute is set incorrectly reset after recovery to normal 21 MotorReverse Reserved Reserved Reserve...

Страница 60: ... JZD is not output the brake feedback point has signal input brake contactor stuck 2 When there is output JZD the brake feedback point no signal input brake contactor brake off Auto reset 34 Brake On Err Brake On Error 1 When the brake contactor brake on the brake limit is disabled 2 Brake limit signal port logic attribute setting is wrong Auto reset 35 BrakeOff Err Brake Off Error 1 When the brak...

Страница 61: ...nd input Auto reset 47 ParameterErr Parameter Error 1 Encoder pulse is set incorrectly 2 Elevator rated speed setting is wrong Hold until the setting is correct 48 UpLimit2Low Up Limit position too Low Up limit installation position is too low Auto reset 49 DnLimitHigh Down limit position too high Down limit installation position is too high Auto reset 50 MemoryFault Memory Fault Data memory is da...

Страница 62: ...e 1 The distance between the two level sensor is too large 2 Level separate plate is too long Auto reset 67 LevelLineErr Door signal input at the same time 1 Wiring error 2 The two level sensor signal port logice attributes is set incorrectly Auto reset 68 UpLimitWork2 Up limit work before the calibration starts Wiring error or car position is wrong Auto reset 69 CarPositionE Car position error wh...

Страница 63: ... Quanzhou Factory Address 3 Zixin Road Jiangnan Hi Tech Industrial Park Quanzhou Fujian China Tel 0595 24678267 Fax 0595 24678203 Service Network Website www savch net Qualification Received ISO9001 and CE recognition All rights reserved Subject to change without further notice Sales service contact address ...