7. Motor Parameters
Set during running available
Parameter
Parameter functions
Setting range
Factory
setting
7-00
Motor(Rated current)
30 to 120%
85
7-01
Motor(No load current)
0 to 90%
30
7-02
Manual torque compensation
setting
0.0 to 30.0%
0.0
7-03
Auto slip compensation setting 0.1 to 10
0.0
7-04
Torque boost cutoff frequency
0~50%
10
7-05~7-09 Reserved
Remark:1. When 7-02 is set to 0, it means no torque boost function.
2. The reference value for 7-02 is parameter 1-02 (maximum output voltage).
3. The reference value for 7-04 is parameter 1-00 (maximum operating frequency).
8. High Function Parameters
Set during running available
Parameter
Parameter functions
Setting range
Factory
setting
8-00
DC braking(Braking level)
0.0 to 100%
0.0
8-01
DC braking(Braking time
setting at starting)
0.0 to 60.0S
0.0
8-02
DC braking(Braking time
setting at stopping)
0.0 to 60.0S
0.0
8-03
DC braking(Braking starting
frequency)
0.0
to 400Hz
0.0
8-04
Restart after momentary power
failure (Mode selection)
0: Stop running after momentary power loss.
1: Run continuously after momentary power
loss, inverter tracks downwards from
frequency after power loss.
2: Run continuously after momentary power
loss, inverter tracks upwards from frequency
after power loss.
0
8-05
(Max allowable time for power
failure)
0.3 to 5.0s
2.0
8-06
(Restart time)
0.3 to 5.0s
0.5
8-07
(Max current setting for speed
tracking)
30 to 200%
150
8-08
Jump frequency 1(Upper)
0.0 to 400Hz
0.0
8-09
Jump frequency 1(Lower)
0.0 to 400Hz
0.0
8-10
Jump frequency 2(Upper)
0.0 to 400Hz
0.0
8-11
Jump frequency 2(Lower)
0.0 to 400Hz
0.0
8-12
Jump frequency 3(Upper)
0.0 to 400Hz
0.0
8-13
Jump frequency 3(Lower)
0.0 to 400Hz
0.0
8-14
Auto-reset(Times)
0 to 10
0
8-15
AVR function selection
0:AVR function available
1:AVR function unavailable
2:AVR function cancelled during deceleration
2
8-16
Reserved