S100 Series Inverter
Built-in type
User Manual
Страница 1: ...S100 Series Inverter Built in type User Manual User Manual ...
Страница 2: ...ption 2 1 2 External dimensions 2 1 3 Product specification 3 CHAPTER 2 WIRING 4 2 1 Basic wiring diagram 4 2 2 Main circuit wiring 5 2 3 Precautions for wiring 6 CHAPTER 3 LIST OF DESCRIPTIONS FOR FUNCTIONAL PARAMETERS 7 CHAPTER 4 TROUBLE SHOOTING 15 4 1 Alarm and corrective measures 15 ...
Страница 3: ...ge to inverter or machine may be resulted CAUTION Do not perform a withstand voltage tests for components of inverter it can cause semi conductor components to be damaged by high voltage Never connect the output terminals U V W to AC power supply IC of CMOS on control circuit of the inverter shall be damaged by electrostatic influence Do not touch main circuit board 2 Products receiving All produc...
Страница 4: ...60Hz OUTPUT 3PH 0 240V 1 0KVA 2 5A FREQUENCYRANGE 1 0 400Hz Designed by Taiwan Savch Electric SAVCH ELECTRIC CO LTD Model Input power supply Spec Output power supply Spec Output frequency Product series S 100 2S 0 4 G 0 4 0 4kW 0 75 0 75kW SAVCH G constant torque load 220V single phase 1 2 External dimensions Uint mm ...
Страница 5: ... operating signal External terminals Various operation modes combined by M0 M1 M2 and M3 RS485 communication board Multi function input terminal Step speed reference 0 15 selection forward reverse jog reference acceleration deceleration prohibited reference switching of first second acceleration deceleration selection of counter program operation external B B NC NO selection pulse input two kinds ...
Страница 6: ...agram Wiring of inverter can be divided into two parts the main circuit and control circuit Users must connect terminals as diagram shows The following diagram is the standard wiring diagram of S100 series inverter Main circuit power supply ...
Страница 7: ...5 2 2 Main circuit wiring Control circuit wiring diagram Wire gauge 12 20AWG Torque 5KG CM Wiring Diagram ...
Страница 8: ...in correspondence and if the inverter output is forward run reference while motor is at reverse run change any two of the motor U V or W then the motor will forward run Confirm the voltage and max capacity that is available to be supplied of the power supply system Never connect or dismantle any wiring when the digital operator is in display or power supply indicator is still ON Extend the deceler...
Страница 9: ...c 2 Displaying program operation content X tt 3 Displaying DC BUS voltage U 4 Displaying output voltage E 5 Displaying rotating speed r 6 Reserved 7 Module temperature 8 Charging resistance temperature 9 Display the current carrier frequency 0 0 05 Proportional constant setting 0 1 to 160 1 0 0 06 Software Version Only for reading 0 07 Input parameter password protection 0 to 999 0 0 08 Setting pa...
Страница 10: ...de parameters Set during running available Parameter Parameter functions Setting range Factory setting 2 00 Master frequency reference source setting 0 Keys on keypad 1 Input DC 0 to 10V by external terminals AVI 2 Reserved 3 Reserved 4 Operated by RS485 communications interface 5 Operated by RS485 communications interface Frequency memory 6 Controlled by UP DOWN 7 Controlled by UP DOWN Frequency ...
Страница 11: ...tion Terminal AVI stop mode 0 Deceleration stop 1 Coast to stop 2 Holding operation command after deceleration stop 0 2 08 Reserved 2 09 Motor sound Carrier frequency 2 to 12kHz 6 2 10 REV run inhibition 0 Rev run available 1 Rev run inhibited 2 Fwd run inhibited 0 2 11 Reserved 2 12 Power on start 0 Operation available 1 Operation unavailable 0 3 Output Function Parameters Set during running avai...
Страница 12: ...ward run Normally open M1 reverse run Normally open M2 stop Normally closed 5 External fault EF normally open interface input N O 6 External fault EF normally closed interface input N C 7 RESET alarm 8 Select multi frequency 1 9 Select multi frequency 2 10 Select multi frequency 3 11 Select multi frequency 4 12 Reserved 13 Accel decel inhibition command 14 Select 1ST and 2nd Accel Decel time 15 Ex...
Страница 13: ...5 10 Multi frequency 11 0 0 to 400Hz 0 0 5 11 Multi frequency 12 0 0 to 400Hz 0 0 5 12 Multi frequency 13 0 0 to 400Hz 0 0 5 13 Multi frequency 14 0 0 to 400Hz 0 0 5 14 Multi frequency 15 0 0 to 400Hz 0 0 5 15 Pattern Operation Mode 0 Pattern operation inactive 1 Active Stop after operating for 1 cycle 2 Active Pattern operation performs in cycles until STOP command input 3 Active Stop after opera...
Страница 14: ...2 during constant speed running stop running after detection 3 Over torque detection OL2 during acceleration continue to run after detection 4 Over torque detection OL2 during acceleration stop running after detection 0 6 03 Over torque detection Detection level 30 to 200 150 6 04 Over torque detection time 0 1 to 10 0s 0 1 6 05 Electrical thermal overload protection for Motor Select motor charact...
Страница 15: ...g Braking time setting at stopping 0 0 to 60 0S 0 0 8 03 DC braking Braking starting frequency 0 0 to 400Hz 0 0 8 04 Restart after momentary power failure Mode selection 0 Stop running after momentary power loss 1 Run continuously after momentary power loss inverter tracks downwards from frequency after power loss 2 Run continuously after momentary power loss inverter tracks upwards from frequency...
Страница 16: ...800 bps 1 Baud rate 9600 bps 2 Baud rate 14400 bps 3 Baud rate 19200 bps 4 Reserved 1 9 02 Transmitting fault treatment 0 Warning and running continuously 1 Warning and deceleration to stop 2 Warning and coasting to a stop 3 No warning and running continuously 0 9 03 No response error detection time 0 Not detected 1 20 1 to 20s 0 9 04 Communications format 1 ASCII mode 0 ASSII mode 8 N 1 1 ASSII m...
Страница 17: ...Increase acceleration time 1 09 1 11 6 Check there is no over load to motor Ou Inverter detects Over voltage at DC high voltage side 1 Check input voltage is within rated voltage range of inverter and see that no voltage surge occurs 2 If over voltage occurs at DC high voltage side of inverter caused by inertia back up voltage deceleration time shall be increased OH Inverter detects over heat exce...
Страница 18: ...ergency stop Depress RESET key after alarm eliminated CF1 Inner memory IC data writing alarm 1 Supply power again after power off 2 Factory maintenance and overhaul CF2 Inner memory IC data reading alarm 1 Depress RESET key and reset parameter to factory setting 2 If unavailable search for factory maintenance and overhaul CF3 Inverter detects wiring fault with seven categories from CF3 1 to CF3 7 ...
Страница 19: ...ry Address 3 Zixin Road Jiangnan Hi Tech Industrial Park Quanzhou Fujian China Tel 0595 24678267 Fax 0595 24678203 Service Network Website www savch net Qualification Received ISO9001 and CE recognition 520000013267 V2 3 2021 05 21 All rights reserved Subject to change without further notice Sales service contact address ...