Savant Power System Wiring and Installation Deployment Guide
Copyright 2022 Savant Systems, Inc
009-2222-02 | 080122
- 8 -
3.3. (OPTIONAL) CT and VT Placement
CT (Current Transformer) and VT (Voltage Transformer) placement is critical for correct data transmission to the SmartEnergy Monitor.All Savant
Prow Confirm that VT and CT wiring placements match the diagram and the table below.
Savant Power System with Generator
SEM CT
Physical Connection
Circuit Name
CT Size
Classification
1 / 2
ATS Normal Input
Grid Feed
250A
Feed
3 / 4
ATS Emergency Input
Generator Power
150A
Production
NOTE:
Generator circuit CT rating is inverted.
Savant Power System with Schneider ESS
SEM CT
Physical Connection
Circuit Name
CT Size
Classification
1 / 2
ATS Input
Grid Feed
250A
Feed
3 / 4
ATS Output
Total Consumption
150A
Total Consumption
For more information on SEM-2015 wiring and configuration instructions, search the Savant Knowledgebase for the
.