background image

SAVANNAH STOKER v3 INSTRUCTION MANUAL 

2015.01 Copyright © Sound Solutions, LLC.  All Rights Reserved.  Find us on Facebook.com/SavannahStoker , Pelletheads.com and LetsTalkBBQ.com                                                              

8

                  

Operational Parameters Defined, continued from page 7 
 

6.3.4

 

“t”  Cycle time  

Cycle time 

“t”

 is a time period (in seconds) the controller uses to 

calculate the auger’s runtime. This is also known as the duty cycle. 
Default is 20 seconds. 
   
Example: If the cycle time parameter is set to 

t=20

, and the controller 

has determined the output for the next cycle should be 25%, the auger 
will run for 5 seconds at the start of the next cycle and will be off for the 
remaining 15 seconds of the cycle.  
 

Notes:

 The default value for the cycle time is 20 seconds. This gives the 

best  performance  for  most  stock  configured  grills.  The  controller  also 
runs  the  auger  a  minimum  amount  each  duty  cycle  to  maintain  the  fire 
much like a pilot light. The minimum amount is controlled by parameter 

OutL

”, and the maximum limit is controlled by parameter “

OutH

”.  

 
If  the  cycle  time  is  less  than  20  seconds  the  auger  may  not  run  long 
enough during each duty cycle to maintain the fire. Before lowering the 
value  of  either  the  cycle  time  or  OutL,  refer  to  section  6.4  “How  to 
Determine the Lowest Stable OutL Value”.    
 
Larger  cycle  times  typically  give  larger  temperature  swings  except  on 
large insulated cookers where a cycle time of 45 or 60 may have to be 
used.  
 
 

6.3.5

 

“Sn” Sensor Input Selection 

Sn

 is used to define the type of input sensor used. 

  

Pt

 = The default value for the temperature sensor (PT1000 RTD) 

shipped with the controller and for the sensor used with the stock 
controller.  

K

 =  K-Type thermocouple.  

 

  

6.3.6

 

“Pb” Sensor Calibration Offset  

Pb

  is  used  to  set  an  input  offset  to  compensate  the  error  produced  by 

the sensor. Use this to calibrate the sensors PV reading. 

 
 

6.3.7

 

“OutL” and “OutH” Auger Runtime Limits  

OutL

  and 

OutH

  are  runtime  limits  of  the  auger.  The  value  is  a 

percentage of the total cycle time, parameter “t”.  
  

OutL

 is the minimum % of the cycle time the auger will run at the start of 

each cycle. Default is 17%. A minimum run time is required to maintain 
the fire. See the top of the next column. Example: With a cycle time t=20, 
and 

OutL

=17, the auger will run for 17% of the 20 second cycle time or 

3.4 seconds. 
 

OutH

 is the maximum % of the cycle time the auger will run.   

Default  is  100%.  The  high  limit  is  used  to  help  reduce  temperature 
overshoots that will occur at start-up, after the cooking chamber door is 
opened, and after the target temperature is increased. The default value 
works well with most grills. On small grills better performance is achieved 
with a lower value of 70 or 80.  
 
 

 
 

 
CAUTION: 

 

A pellet grill requires a minimum amount of fuel feed 
per cycle time to maintain the fire.  
 
 

If 

OutL

  is  too  low  the  fire  will  go  out;  too  high  and  the  smoking 

temperature  will  be  too  hot  on  very  hot  days.  The  default  value 
will  give  satisfactory  results  with  most  stock  pellet  grills.  If  you 
need to change the 

OutL

 value refer section 6.4.  

 

6.3.8

 

“C-F” Selecting Fahrenheit or Celsius 

Parameter 

C-F

 is used to change between Celsius and Fahrenheit. 

F= Fahrenheit (default) 
C= Celsius 
If changing to Celsius, Change the value of “P”, See Section 6.3.3 

 

6.3.9

 

“FAnS” Fan Speed 

FAns

 is used to change the fan speed. 

3= Normal fan speed 
2= Medium Fan Speed 
1= Low Fan Speed. (not recommend except for cold smoking) 

 

6.3.10

 

 “Fant”  Fan Shut Off Temperature 

The unit is degree.  When the controller is turned off, the fan will 
continue to run until the cooking chambers temperature is cools down to 
the temperature set by 

Fant

. For example, if the 

Fant

 is set to 130, the 

display will flash between "Hot" and “current smoker temperature", until 
the smoker temperature drops to below 130 degree. 

 

6.4

 

How to Determine the Lowest Stable Value for OutL

1)

 

Start the grill normally. Set the target temperature to 225°F. Let the 
temperature stabilize for 20-30 minutes. 

2)

 

Change the parameter values of:  t=20 and OutL = 10.  

3)

 

Change the controller to Manual mode.  See section 5.2 

4)

 

Press the ▼or ▲KEYs to set the value in the lower display to 17. 

5)

 

The grill’s temp will slowly lower until it stabilizes. This could take 
30-45 minutes or longer. If the grill’s temperature (PV) drops below 
160° raise the output value by 2. 

6)

 

After the temperature becomes stable; take the average 
temperature; then, do one of the following. 
a)

 

If the average is between 170-180°, do nothing.  

You have a found the stable value for OutL.  
Enter the lower display value as the OutL parameter value.  

b)

 

If above 180° lower ▼the SV value by 1, retest 

c)

 

If above 190° lower ▼the SV value by 2, retest 

d)

 

If below 170° raise  ▲the SV value by 1, retest 

e)

 

If below 160° raise  ▲the SV value by 2, retest 

 

 
 
 
 
 
 
 
 
 
 
 

Содержание STOKER v3

Страница 1: ...40VAC 3A Igniter Output Zero crossing SSR 100 240VAC 10A Power supply 100 240VAC 50 60Hz Power consumption 300 Watts at startup 60 Watts normal operation Ambient temperature 0 50 C 32 122 F Fuse 5x20m...

Страница 2: ...oller to the pellet hopper saving the screws for use later 2 Gently pull the controller away from the hopper while sliding it slightly to the right Rotate the left side toward you so the circuit board...

Страница 3: ...point will stop flashing after no KEY is pressed for 3 seconds You can press the A M KEY to move the flashing decimal point to the desired digit that needs to change Then press the or KEY to change SV...

Страница 4: ...ller is in the Automatic Control Mode Pressing the A M KEY will switch the controller to Manual Control Mode When in Manual Control Mode the first digit to the left will change to an M to indicate Man...

Страница 5: ...Ys will lower or raise the auger runtime Note Manual mode will be running the last output value when the controller was in Automatic Mode The runtime cannot be set lower than the OutL parameter value...

Страница 6: ...acteristics of your barbecue Chart and save your cook data Set alarms on your computer Ramp temperatures up down by time or food temperature and more The author posts on the Virtual Weber Bulletin Boa...

Страница 7: ...note the controller uses an enhanced version of PID control algorithms Tuning of the controller is different than traditional PID controllers The parameters are explained below Before adjusting any o...

Страница 8: ...second cycle time or 3 4 seconds OutH is the maximum of the cycle time the auger will run Default is 100 The high limit is used to help reduce temperature overshoots that will occur at start up after...

Отзывы: