29.
Press and release the ENTER key: the parameters shall be copied from the controller into the peripheral device (the process
usually requires a few seconds; if an error should be present, the System alarm LED (see paragraph 5.2 LED warning
lights) shall light up and an Err. value shall be input in the Key Par (in the "Diagnostic" sub-menu) parameter.
30.
Disconnect the peripheral device
To copy the USB peripheral device parameters to the controller, proceed as follows:
31.
Check that the power is on.
32.
Connect the peripheral device to the controller.
33.
Access the "Backup/Restore" sub-menu, then choose "Parameters key" (Choose "Backup Memory" for the backup memory)
34.
Press and release the UP or DOWN key to select "Restore from the key".
35.
Press and release the ENTER key: the parameters shall be copied from the peripheral device into the controller (the process
usually requires a few seconds; if an error should be present, the System alarm LED (see paragraph 5.2 LED warning
lights) shall light up and an Err. value shall be input in the Key Par (in the "Diagnostic" sub-menu) parameter.
36.
Disconnect the peripheral device
Copying the peripheral device parameters tp the controller is allowed provided that the controllers firmware coincides.
To exit the procedure, proceed as follows:
37.
Press and release the ESC key repeatedly; any changes shall not be saved.
Disconnect the power supply after changing the configuration.
6.2
Configuration of a controller through a remote user interface
The following procedures show an example of how to configure a controller through a remote user interface (in the example,
RDB 900
F901
) and its user interface.
Proceed as follows:
1.
Disconnect the power supply of the controller and the interface.
2.
Connect the controller to the interface through the CAN CANBUS port; see chapter 4 “ELECTRIC CONNECTION”.
3.
Keep the ESC and RIGHT keys pressed for 2 sec.
4.
Connect the power supply of the controller and the interface.
5.
When the interface display shows the following menu, release the ESC and RIGHT keys.
RDT 900 F901
Parameters
Contrast
CAN Network
Modbus
Info
Debug
6.
Press and release the UP or DOWN key to select "CAN Network".
7.
Press and release the ENTER key.
8.
Press and release the ENTER key again to set the password
9.
Press and release the DOWN key repeatedly to set "
-19
".
10.
Press and release the ENTER key again.
11.
Set the "NW Node" parameter using the UP or DOWN keys to select the parameter and the ENTER key to change and
confirm the relevant value.
The default address of the CAN node of a controller is 1 (operate on the remote user interface to set the "NW Node" parameter to
[ 1 ]
1
).