modu600-LO
Functionality and operation
36/60
R: 02, V: 01
D100408262
value and the set unit are displayed on the
modu600-LO
. If the unit is missing or the
connection is broken, the unscaled value and unit are displayed.
For analogue outputs (AO), the manual override is only shown as a % of the nominal
range.
Hint:
To ensure that the display with the unit is correct, do not forget to configure the signals
correctly with CASE Engine. This is particularly relevant when measuring a variable
resistance.
Example:
HW Values
Example Value
BACnet Object Parameter
Example Value
Min. HW Value
100
Min. Present Value (MinPV)
0 %
Max HW Value
2500
Max Present Value (MaxPV)
100 %
From this one calculates:
𝑠𝑙𝑜𝑝𝑒 =
(𝑀𝑎𝑥𝑃𝑉 − 𝑀𝑖𝑛𝑃𝑉)
(𝑀𝑎𝑥𝐻𝑊 − 𝑀𝑖𝑛𝐻𝑊)
=
(100 − 0)
(2500 − 100)
= 0.04167
𝑜𝑓𝑓𝑠𝑒𝑡 = 𝑀𝑖𝑛𝑃𝑉 − 𝑠𝑙𝑜𝑝𝑒 × 𝑀𝑖𝑛𝐻𝑊 = 0 − 0.04167 × 100 = −4.167
These parameters slope and offset must be entered in the signal configuration. This
setting is valid while the values used for calculation remain unchanged, e.g. MinPV or
MaxPV.
y = 0,0417x - 4,1667
-20
0
20
40
60
80
100
120
0
500
1000
1500
2000
2500
PV
(e
. g.
%
)
HW Wert (e. g.
)
Linear
Содержание EY6LO00F001
Страница 1: ...modu600 LO Operating instructions D100408262 ...
Страница 2: ......
Страница 3: ...modu600 LO D100408262 R 02 V 01 3 60 modu600 LO Operating instructions D100408262 ...
Страница 16: ...modu600 LO Hardware description 16 60 R 02 V 01 D100408262 Installation instructions ...
Страница 52: ...modu600 LO FAQ 52 60 R 02 V 01 D100408262 ...
Страница 59: ...modu600 LO Annexe D100408262 R 02 V 01 59 60 ꞋꞌꞍ fifl ...