![sauter EY6LO00F001 Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/sauter/ey6lo00f001/ey6lo00f001_operating-instructions-manual_1203002017.webp)
modu600-LO
Functionality and operation
D100408262
R: 02, V: 01
17/60
7
Functionality and operation
7.1
Supported functions
modu600-LO
is used to display and override signals on a modulo 6 I/O module.
The following properties are supported:
•
Automatic transfer of the state of the I/O module
•
Display of the state of the I/O module via LED
•
Override of output signals (local operation, manual operation)
•
Reset of overridden outputs (AUTO mode)
•
Graphical display of the values of all I/O
•
Graphical display of special states (alarm, override) based on the associated
BACnet object
•
List-display of the I/O labels as per engineering
•
Graphical detailed view of individual I/O
•
Live chart of the signals
•
Use of unoccupied I/O
•
Keeping the local operation after the station is switched off (stand-alone with
modu601-LC
)
•
Default value possible in the stand-alone state (if configured)
•
Backlight automatically dimmed (ECO mode)
•
SAUTER logo when booting
•
Firmware updated automatically from the station (upon reboot only)
•
Compatibility with all modu6** I/O modules
Important information
modu600-LO operates at Hardware (field) level, while BACnet represents the application
(automation) level. Hence, local (modu600-LO
2
, modulo 6 App) overrides have priority
over all other systems that can drive the output signals. In the case of BACnet Objects,
they identify the overridden statu
s and set the status flag property “override “ to TRUE.
Any value set to the priority array, e. g. AUTO mode (for SAUTER, priority 16) or manual
operation over BMS (usually priority 8) is ignored, as long as a modu600-LO or modulo
6 App override is active.
2
From firmware version 1.2.3 and the associated
modu600-LO
and modulo 6 app versions, the
modu600-LO
and modulo 6 app are regulated according to the last-wins principle.
Содержание EY6LO00F001
Страница 1: ...modu600 LO Operating instructions D100408262 ...
Страница 2: ......
Страница 3: ...modu600 LO D100408262 R 02 V 01 3 60 modu600 LO Operating instructions D100408262 ...
Страница 16: ...modu600 LO Hardware description 16 60 R 02 V 01 D100408262 Installation instructions ...
Страница 52: ...modu600 LO FAQ 52 60 R 02 V 01 D100408262 ...
Страница 59: ...modu600 LO Annexe D100408262 R 02 V 01 59 60 ꞋꞌꞍ fifl ...