Wiring EY-modulo4 Room Operating Unit to a VAV for VAV Balancing 

5.2 

The EY-modulo4 Room Operating Unit EY-RU483F001 can be used as a hand-held device to 
perform VAV balancing. The communications terminals (1 and 2) within the EY-RU483F001 (or 
any other sensor with a communications jack) must be connected to the SMRT+ and SMRT-
inputs of the VAV before the communications jack can be used (Figure 5). Typically, these 
connections should have been made when the VAV and EY-RU483F001 were first installed in 
the building. 

To wire an EY-RU483F001 to a VAV via an EY-RU481 (or any other sensor with a 
communications jack) do the following: 

Remove the front plate of the EY-RU483F001. 

1. 

Connect the two (2) wires that terminate with the 1/8“ audio cable to the T1 and T2 output 

2. 

terminals of the EC-Smart-Sensor-VAV. 

Remove the front plate of the EY-RU481 and insert the 1/8“ audio cable into the 

3. 

communications jack. Verify that the communication terminals (1 and 2) within the EY-
RU481 are wired to the SMRT+ and SMRT-terminals of the VAV controller. The other 
terminals within the EY-RU481 should already be connected as described in the EY-
RU481 Hardware Installation Guide. 

1/8"

Com.

Jack

1 2 3 4 5 6

1 2

B11611

Terminal description

Fig. 5 

Depending on the sensor model, there may be a different number of wire terminals. 
Refer to the individual sensor’s hardware installation guide for further details.  

B11616

EC-Sensor

Smart-Sensor

1/8" Com. Jack

1

SMRT-

SMRT+

VAV Controller

2

SMRT

Wiring EY-RU483F001 to a VAV via an EY-RU481 

Fig. 6 

Содержание EY-RU482F001

Страница 1: ...ssages for commissioning and toggle temperature units between C and F The SAUTER EY RU483F001 can be permanently installed on a wall or used as a hand held air balancing tool that can be connected through a standard wall mounted room sensor Using the SAUTER EY RU483F001 as a hand held unit technicians can directly perform VAV balancing right near the point of control The SAUTER EY RU482F001 commun...

Страница 2: ... humidity from 0 to 95 non condensing Ensure proper ventilation of device and avoid areas where corroding deteriorating or explosive vapors fumes or gases may be present The device must be oriented with the ventilation slots towards the top to permit proper heat dissipation Take reasonable precautions to prevent electrostatic discharges to the device when installing servicing or operating the devi...

Страница 3: ...cables 6 out of the wall and insert them through the central hole of the back plate 4 Align the back plate with the wall and mark the location of the two mounting holes on the 5 wall Make sure to orient the proper side of the back plate facing upwards Remove the back plate and drill holes in the wall if necessary 6 Install anchors in the wall if necessary 7 Make sure that the mounting surface is f...

Страница 4: ...ccess mounting hole 4 Security Srew Device Wiring 5 The EY modulo4 Room Operating Unit can be wired in three 3 different ways depending on its desired use Directly to a controller for use as a wall mounted sensor Indirectly to a VAV through another sensor for VAV balancing Directly to a controller for use as a wall mounted sensor and to provide access to the LON network ...

Страница 5: ...EY modulo4 Room Operating Unit There are 4 connection 1 terminals and a 1 8 communications jack within the device B11618 T1 T2 LON LON 1 8 Com Jack Smart Sensor terminal description Fig 3 Connect the T1 and T2 output terminals of the Smart Sensor to SMRT and SMRT input 2 terminals on the controller B11619 SMRT SMRT T1 T2 Smart Sensor Controller Wiring Smart Sensor to a controller Fig 4 The maximum...

Страница 6: ...ate of the EY RU483F001 1 Connect the two 2 wires that terminate with the 1 8 audio cable to the T1 and T2 output 2 terminals of the EC Smart Sensor VAV Remove the front plate of the EY RU481 and insert the 1 8 audio cable into the 3 communications jack Verify that the communication terminals 1 and 2 within the EY RU481 are wired to the SMRT and SMRT terminals of the VAV controller The other termi...

Страница 7: ...Unit 1 Connect the LON output terminals of the EY modulo4 Room Operating Unit to the LON1 2 and LON2 input terminals on the controller Connect the two 2 wires that terminate with the 1 8 audio cable to the output terminals 3 of the PCLTA card on the computer Other methods of connecting to the computer are possible Insert the 1 8 audio cable into the communications jack of the EY modulo4 Room 4 Ope...

Страница 8: ...not communicate on large network Network length Check that the total wire length does not exceed the specifications of the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks Wire type Check that the wire type agrees with the specification of the Junction Box and Wiring Guideline for Twisted Pair LonWorks Networks Network wiring problem Double check that the wire connections are c...

Страница 9: ...t wiring problem Check that the wiring is correct according to this manual and according to the peripheral device s manufacturer Configuration problem Refer to the device s user guide for more information Hardware Installation Guide 9 While all efforts have been made to verify the accuracy of information in this manual SAUTER is not responsible for damages or claims arising from the use of this ma...

Отзывы: