background image

List of symbols 

52 ASVxxx 

11 

 

The next step is to check that the damper moves easily. Release the 
damper lock on the ASV and move the damper in both directions as far as 
it will go. You should be able to move the damper without much effort. If 
not, try to unjam the damper by moving it back and forth. If the damper will 
not move, repair it. 

 

 

Fig. 3: Releasing the lock 

 

 

Note: Most VAV boxes (e.g. Trox) do not need any maintenance. 

 

Note down any improper modifications and eliminate them.  

3.3

 

Testing the damper using the CASE VAV parameterising software 

 

Connect the ASV unit to the PC with the USB-RS-485 adapter and start up 
the latest CASE VAV software. Use the SLC protocol to connect to the 
VAV compact controller. The current SLC address of the device can be 
found in the commissioning protocol. First adjust the angle of rotation on 
the ASV and note down the working range. Then use the “Manual 
operation” function and set the damper to “Open” and “Closed”. You can 
see the position of the damper blade from outside using a marking on the 
damper spindle. If not, you can derive the position of the damper blade 
using the actual values of the volume flow. The maximum volume flow 
must be reached when the damper is open. If the function is not 
c

ompletely working, you can use the “Angle of rotation” and “Adjust angle 

of rotation” functions to move to the two limit switches of the actuator and 
calculate the angle of rotation again. Test the damper again. 

 

If the end positions (open, closed) are still not reached, release the lock of 
the ASV 115 and check the alignment of the damper adapter to the 
damper blade (see Fig. 2). 

 

Note down the results. 

3.4

 

Measurement of the duct pressure 

 

In manual mode, completely close the damper of the VAV box and use the 
T-hoses to connect the pressure gauge on the (+) hose to the differential 
pressure outlet of the VAV box. Measure in relation to atmospheric 

Содержание ASV 52 Series

Страница 1: ...ASV VAV compact controller Maintenance manual 52 ASVxxx ...

Страница 2: ......

Страница 3: ...troller9 3 2 Mechanical inspection of the VAV compact controller 10 3 3 Testing the damper using the CASE VAV parameterising software11 3 4 Measurement of the duct pressure 11 3 5 Zero adjustment of the differential pressure transmitter in the ASV and comparison of the measured value 12 3 6 Measuring the volume flow at max and min 12 4 Completion of service 13 4 1 Service report 13 5 Procedure dia...

Страница 4: ...List of changes 4 52 ASVxxx List of changes Date Rev Ver issue Change Section Page ...

Страница 5: ...List of figures 52 ASVxxx 5 List of figures Fig 1 Checking the ASV supply lines 9 Fig 2 Mounting the ASV on the VAV box 10 Fig 3 Releasing the lock 11 Fig 4 Procedure diagram 14 ...

Страница 6: ... ASVxxx List of symbols Information Information relevant to handling the product Internet link Reference to links or applications on the internet Warning instruction Warning instructions are written in front of the action ...

Страница 7: ... VAV boxes must also be included in the maintenance These maintenance instructions cover the following products ASVxxx VAV compact controllers Required information and materials 1 Access to the device cabinet 2 Commissioning certificates of the installed and operated ASVs 3 Room specifications if available 4 Latest CASE VAV software 5 Laptop 6 USB to RS 485 converter 7 2 x T hose 8x1 8 Hose 9 Cali...

Страница 8: ...pment may only be carried out by a qualified electrician or by instructed persons under the guidance and supervision of a qualified electrician in accordance with the regulations of electrical engineering All local regulations and safety precautions must be strictly observed during maintenance WARNING moving parts can cause hand injuries ...

Страница 9: ...e VAV controller Look out for damage dents and leaks on the VAV box and compact controller Check that the supply lines to the ASV and the VAV box are correctly laid see the ASV fitting instructions Fig 4 2 There must not be any kinks in the power cable or hoses Note down any damage anomalies or improper modifications Fig 1 Checking the ASV supply lines ...

Страница 10: ...d on the VAV box and damper adapter is correctly seated Tighten the screw fittings and check the tightening torque of the fixing screw see ASV fitting instructions Fig 4 1 steps 7 8 and 9 Remove any dirt dust and accumulated deposits Fig 2 Mounting the ASV on the VAV box Check the electric contact terminals at the end of the power cable and tighten them ...

Страница 11: ...SV and note down the working range Then use the Manual operation function and set the damper to Open and Closed You can see the position of the damper blade from outside using a marking on the damper spindle If not you can derive the position of the damper blade using the actual values of the volume flow The maximum volume flow must be reached when the damper is open If the function is not complet...

Страница 12: ...e them down Only use certified measuring equipment Observe the stated error of the measuring instrument and note it down along with the recorded measured value If there are still measured values outside the tolerance range make a control measurement at local atmospheric pressure To do this remove the hoses again and select the Online values option in CASE VAV Compare the measured value with the ca...

Страница 13: ...ce report To complete the service print out the configuration certificate by selecting File Print configuration certificate and attach it to the service report Update the XML backup file and the commissioning configuration certificate of the compact VAV controller ...

Страница 14: ...Procedure diagram 14 52 ASVxxx 5 Procedure diagram Fig 4 Procedure diagram ...

Отзывы: