Saunier Duval ISOMAX F 28 E Скачать руководство пользователя страница 26

26

REPLACEMENT OF PARTS

• Remove slotted metal clips from heat exchanger con-
nection pipes.
• Undo nut securing pipe from heat exchanger to 3-
way valve/bypass housing.
• Swing pipe away from 3-way valve/bypass housing
and pull down to disengage from heat exchanger pipe.
• Pull down pipe from pump to heat exchanger to dis-
engage from heat exchanger pipe.
• Slide heat exchanger forwards and remove from
boiler, 

 see diagram 11.

• Fit replacement heat exchanger in reverse order to
removal.
• Reconnect electrical connector to high limit thermo-
stat.
• Open isolating valves on flow and return connections,
refill, vent and pressurise boiler.
• Check for leaks.

To replace combustion chamber insulation

• Remove combustion chamber cover as de-
scribed in ‘

Routine Cleaning and Inspection

’.

• Remove heat exchanger as described previously.
• Remove fan and flue hood as described in ‘

Rou-

tine Cleaning and Inspection

’.

Front panel:

• Lift front insulation panel free from retaining lugs
on combustion chamber cover.

Rear panel:

• Pull rear insulation panel free from retaining lug
at rear of combustion chamber by tilting forward.
• Fit replacement insulation panels in reverse or-
der to removal
• Refit combustion chamber cover.

Side panels:

• Pull out side panels.

To replace burner

• Remove burner as described in '

Routine Clean-

ing

 

and Inspection

'.

Assemble replacement burner, supplied in parts, as
follows:
• Fit burner injectors to burner injector bar and
tighten.

Note: 

Make sure that injector size, marked on each

injector, is the same as that given in ‘

Technical Data

for the type of gas being used.
• Fit injector bar into burner, secure with retaining rods.
• Fit replacement burner into boiler in reverse or-
der to removal.

To replace burner injectors

• Remove burner as described in '

Routine Clean-

ing and Inspection

'.

• Pull out injector bar retaining rods and separate
injector bar from burner.
• Unscrew and remove injectors from injector bar.
• Fit replacement injectors to injector bar and
tighten.

Note:

 Make sure that injector size, marked on each

injector, is the same as that given in ‘

Technical Data

for the type of gas being used.
• Reassemble burner and fit into boiler in reverse
order to removal.

To replace ignition electrode

• Remove burner as described in ‘

Routine Clean-

ing and Inspection

’.

• Undo and remove screw securing electrode onto
burner.
• Fit replacement electrode onto burner in reverse
order to removal.
• Refit burner into boiler in reverse order to removal.

To replace flame sense electrode

• Remove burner as described in ‘

Routine Clean-

ing and Inspection

’.

• Undo and remove screw securing electrode onto
burner.
• Fit replacement electrode onto burner in reverse
order to removal.
• Refit burner into boiler in reverse order to removal.

Diagram 11

Ech 040

To replace central heating expansion vessel

Replacement of the expansion vessel is not possi-
ble with the boiler on the wall.
Remove boiler from wall as described in '

To replace

storage vessel thermistor'.

• Undo pipe coupling on expansion vessel.
• Supporting expansion vessel, unscrew and re-
move screw securing expansion vessel to boiler.
• Lift vessel out of boiler.
• Fit replacement vessel to boiler in reverse order
to removal, ensuring that sealing washer is fitted to
pipe connection before tightening.
• Ensure that expansion vessel charge pressure is
0.5 bar (7.5 psi) using a pressure gauge. If neces-
sary, increase pressure using a car or cycle tyre
pump connected to the Schrader valve.
• Refit boiler onto fixing jig, tighten all connections
ensuring that all sealing washers are fitted before
tightening.
• Reconnect flue making sure that all joints are
properly connected.
• Open isolating valves on flow and return connec-
tions, refill, vent and pressurise boiler.
• Check for leaks.
• Reconnect all electrical connections and restore
electrical supply.
• Open gas cock, operate boiler and re-check all
joints for soundness.

To replace high limit thermostat

• Locate high limit thermostat on heating flow pipe
on left hand side of boiler.
• Disconnect electrical connection from thermostat
• Unclip thermostat from heating flow pipe.
• Fit replacement thermostat in reverse order to re-
moval.
• Refit connection to thermostat.

Содержание ISOMAX F 28 E

Страница 1: ...1 THIS IS A CAT I2E APPLIANCE 01773 828100 IN WARRANTY TECHNICAL HELPLINE 01773 828400 ISOMAX...

Страница 2: ...installation 9 10 Boiler location 11 Boiler installation 12 Flue installation 12 13 Electrical installation 14 Commissioning 15 18 Safety devices 18 19 Settings 20 USERS SECTION Mandatory warning for...

Страница 3: ...ends etc For further information contact your supplier Substances Hazardous to Health The adhesives and sealants used in this appliance are cured and give no known hazard in this state INSULATION PADS...

Страница 4: ...ure that The boiler is connected to the electrical supply The gas service cock is open Then follow the instructions below Press the On Off button 1 Hab 264 1 1 The pressure must be between 1 and 2 bar...

Страница 5: ...ctrical supplies are left connected The frost protection device will light the boiler when the temperature of the boiler water falls below 6 C When the temperature reaches 16 C the boiler stops Note T...

Страница 6: ...automatically variable from 10 4 kW to 27 6 kW from 35 484 BTU H to 94 170 BTU H Storage capacity 43 l Maximum hot water temperature 60 C Minimum hot water temperature 37 C Specific flow rate for 30...

Страница 7: ...y air pockets and facilitate permanent venting of the installation Bleed fittings must be provided at every high point of the system and on all radia tors The total volume of water permitted for the h...

Страница 8: ...estic heat exchanger 18 Heating pump 19 Heating expansion vessel 20 Heating thermistor 21 Overheat safety thermostat 22 Flame sensor electrode 23 Fan 24 Domestic safety valve 6 bar 25 Loss of water se...

Страница 9: ...e diam 15mm Water connection Connect the copper connections supplied to the fixing jig fittings see diagram 7 Connect the sys Sch 173a Diagram 8 tem pipework to the boiler observing the correct flow a...

Страница 10: ...y using the mixing valve supplied to provide hot water at boiler hot water set temperature to one tap and thermostatically controlled hot water to another tap s To pipe the hot water supply using the...

Страница 11: ...tions with internal and external access use a 10 5 mm diameter core drill For installations with internal access only use a 125 mm diameter core drill Important When cutting the flue hole and when ext...

Страница 12: ...5 mm to inner pipe measurement Calculation of cutting lengths when flueing to the right or left Measure wall thickness e mm see diagram 11 For right hand applications Measure distance from inside face...

Страница 13: ...olar onto D and press down to lock into position Secure clips with screws provided Important If the flue has been cut ensure that there are no burrs that could damage the O ring For flue systems less...

Страница 14: ...g This appliance must be wired in accord ance with these instructions Any fault arising from incorrect wiring cannot be put right under the terms of the Saunier Duval guarantee External controls The I...

Страница 15: ...d that any air is purged from the supply at the gas inlet test point on the gas valve see diagram 18 Filling the system 4 I O 0 0 bar 1 L afficheur indique 0 bar de pression et clignote Le t moin lumi...

Страница 16: ...2 bar Re fill system as necessary I O 1 5 bar mode Hab 265 8 5 7 6 Bleed each radiator to re move the air re tighten bleed screws Open various hot water taps to bleed system Leave the cap on the pump...

Страница 17: ...o 87 C Visual indication of set temperature Lighting the boiler Press the mode button to select the winter symbol 1 3 2 Adjust heating temperature to maximum Check that any external controls if fitted...

Страница 18: ...75 060 24 81 890 26 88 710 28 95 540 Setting the maximum heating temperature The maximum heating temperature can be preset at commissioning stage to suit the type of heating system For example for us...

Страница 19: ...the fault has been cleared Overheat safety In case of boiler overheating the overheat ther mostat will turn the boiler off The thermostat lo cated on the heat exchanger flow pipe will need to be manu...

Страница 20: ...alve coil Remove the protective cover from the gas valve adjuster Turn nut B see diagram 23 CLOCKWISE To increase the pressure ANTICLOCKWISE To decrease the pressure After adjustment refit the cover t...

Страница 21: ...rew the three screws securing combustion chamber cover to combustion chamber see dia gram 2 Remove combustion chamber cover from boiler Undo but do not remove two burner support screws at rear of burn...

Страница 22: ...ure that all joints are properly connected Cold water inlet filter Drain down hot water circuit of boiler only as fol lows Close isolating valve throttle m on cold water isolating cock see diagram 3 N...

Страница 23: ...and restore electrical supply Open gas cock operate boiler and re check all joints for soundness To replace fan Remove fan as described in Routine Cleaning and Inspection Fit replacement fan in rever...

Страница 24: ...valve head Pull out slotted metal clip from valve body and remove valve head from body Fit replacement valve head in reverse order to removal Note 1 When refiting clip ensure that letters OK are as sh...

Страница 25: ...ram 9 Undo two screws securing modulating coil to gas valve and remove coil Diagram 9 Fit replacement coil in reverse order to removal Refit electrical connections in reverse order to re moval the pol...

Страница 26: ...injector size marked on each injector is the same as that given in Technical Data for the type of gas being used Reassemble burner and fit into boiler in reverse order to removal To replace ignition...

Страница 27: ...exchanger 18 Heating pump A B C D E D1 D1 D1 D2 D1 D3 2 3 6 4 26 7 5 8 9 1 12 13 10 28 15 14 16 18 17 19 20 22 21 23 11 25 24 27 19 Heating expansion vessel 20 Heating thermistor 21 Overheat safety th...

Страница 28: ...ctor 1 20 mm Inlet pressure 20 mbar Maxi Burner pressure 13 8 mbar Mini Burner pressure 2 16 mbar Gas rate maximum 3 20 m3 h Gas rate minimum 1 32 m3 h Heating Hot water output automatically variable...

Страница 29: ...de CTN1 hot water thermistor CTN2 heating thermistor CTN3 accumulator thermistor K4 overheating safety Pr air pressure switch Ex fan accessories Opt option card CD remote control SE external sensor HL...

Страница 30: ...t area To carry out the electrical test gain access to the main Printed Circuit Board PCB as described pre viously and measure the voltages according to table 1 The ISOFAST has an on board fault diagn...

Страница 31: ...detection 05 Overheating 06 Central heating thermistor wiring fault 07 Domestic hot water thermistor wiring fault 08 Storage vessel thermistor wiring fault 09 System pressure sensor fault 10 Fan fault...

Страница 32: ...bar between 93 and 143 SPARE PARTS When ordering spare parts quote the part number and description stating the appliance model number and serial number from the data badge Short parts list No Descrip...

Отзывы: