16
ENG
17
ENG
Option
4.3 PIPE LENGTH
ORIGIN
DISTANCE IN LINEALS m.
Models
Load R-407C (kg) Lines (‘‘)
15 m (4 curves)
20 m (6 curves)
30 m (8 curves)
50 m (6 curves) Max. Height (m)
Cool
Heat
Gas
Liq. % Aprox. R-407C Oil % Aprox. R-407C Oil % Aprox. R-407C Oil % Aprox. R-407C Oil
Over Under
(g)
(g)
(g)
(g)
(g)
(g)
(g)
(g)
IU
IU
050
1,7 2,0
5/8” 3/8” 99 250 ---
98
400
---
96 800 20
92 1.500 50
45
20
---
---
---
---
---
---
---
---
---
---
---
---
---
---
065
1,6 1,9
5/8” 3/8” 98 250 ---
96
400
---
92 800 ---
87 1.500 50
45
20
3/4” 3/8” 100 300 ---
99
500
---
97 800 20
94 1.500 50
085
2,3 2,6
3/4” 3/8” 100 300 ---
97
500
---
94 800 20
89 1.500 50
45
20
7/8” 3/8” 102 300 ---
101 500
---
99 900 20
96 1.600 50
105
2,8 3,55
3/4” 3/8” 97 300 ---
95
500
---
92 800 20
85 1.500 50
45
20
7/8” 3/8” 101 300 ---
100 500
---
98 900 20
94 1.600 50
105T
2,8 3,55
3/4” 3/8” 97 300 ---
95
500
---
91 800 20
85 1.500 50
45
20
7/8” 3/8” 101 300 ---
100 500
---
98 900 20
94 1.600 50
130
3,8 4,2
3/4” 1/2” 96 500 ---
93
850
20
88 1.500 50
80 2.800 100
45
20
7/8” 1/2” 102 500 ---
100 900
20
97 1.500 50
91 2.900 100
180*
-- 6,0
7/8” 1/2” 96 900 ---
93 1.500 20
88 2.700 50
80 5.100 100
45
20
7/8” 1/2” 102 900 ---
100 1.500 20
97 2.700 50
91 5.100 100
230*
-- 8,4
1-1/8” 5/8”
(1)
97 1.500 ---
95 2.500 ---
92 4.500 50
87 8.500 100
45
20
1-3/8” 5/8”
(1)
102 1.800 ---
101 3.000 ---
99 5.400 50
97 10.200 100
(1) It isn’t necessary to isolate this line of liquid.
(* Without loading, value for 7.5 m. Model 180: 120 g/m; Model 230: 200 g/m)
4- OUTDOOR UNIT INSTALLATION