Dataloggers SenNet DL150 / DL151 / DL170 / DL171 / DL172. Technical manual
16
Satel Spain
Version 1.01
3.5.
Z-Wave Radio
Optional. Available for models: DL150, DL151, DL170 and DL171
▪
Module: Z-Wave Transceiver Sigma Designs ZM5202
▪
Frequency 868.4 MHz (EN 300 220). Free use in the European Union. Also available in 869.0
MHz for Russia (GKRCh/EN 300 200) and 908.4 MHz (FCC CFR47 P 15.249) for USA
▪
Range tested for up to 40 meters inside buildings and over 100 m in open field.
3.6.
Internal electricity meters
Only for models DL151, DL171 and DL172
▪
For each phase:
o
Voltage, current, power factor (cos(phi))
o
Power (active / reactive / apparent)
o
Energy (active / reactive / apparent)
▪
For the three phases as a whole:
o
Power (active / reactive / apparent)
o
Energy (active / reactive / apparent)
▪
Frequency
▪
Power failure detection (voltage drops or interruptions)
▪
Voltage-peaks detection
3.6.1.
Measurement options
DL151 and DL171 models
Up to 3 three-phase circuits or up to 9 single-phase circuits. Maximum permitted combinations:
▪
3 x three-phase circuits
▪
2 x three-phase + 3 x single-phase
▪
1 x three-phase + 6 x single-phase
▪
9 x single-phase
Model
172
Up to 6 three-phase circuits or up to 18 single-phase circuits. Combinations of single-phase and three-
phase are also possible.
3.6.2.
Voltage
Up to 480 Vac
3.6.3.
Frequency
50 or 60Hz
3.6.4.
Current (intensity)
Current transformers: from 5A to 1500A (type 0.33V)