technicians  about  the  fault.  Further  operation  of  the  module  may  pose  hazard  to  the 
health  or  life  of  the  operator  and  may  damage  the  module  as  well  as  the  connected 
load. 

 buttons for manual control of the channels 

– see Table 2. 

Button 

Operation 

Reaction 

 

short press 

switch on 

long press 

dim up 

 

short press 

switch off 

long press 

dim down 

 +

 

short press 

detection of load connected to the channel 

The module will interpret button press as a long one when the button is held down longer 
than for 1 second. 

Table 2. 

The  brightness  value  set  by  using  buttons  is  not  saved  to  the  non-volatile  memory  of  the 
module. 

Starting  detection  of  the  connected  load  by  using  the  buttons  is  only  possible  when  the 
automatic  mode  of  load  detection  is  selected  for  the  channel  in  the  ETS  program  (see  full 
module manual). 

You  can  also  use  the  buttons  to  restore  factory  settings  of  the  module  (see  “Restoring  the 
module factory settings

”)

 red  LED 

–  ON  when  a  physical  address  is  being  assigned  by  using  the  ETS  program.  The 

address assignment can be activated manually with the 

 button on the enclosure or remotely 

from the ETS program. 

 programming button (to be used to assign the physical address). 

 terminal to connect the KNX bus. 

1.1  Load types 

The module is designed for use with the following load types: 

 

– resistive (R), 

 

– inductive (L), 

 

– capacitive (C). 

After  connecting  the  mains  voltage,  the  module  can  automatically  recognize  the  type  of  connected 
load.  How  the  connected  load  will  be  detected  is  defined  separately  for  each  channel  in  the  ETS 
program (see the full manual to the module). 

It  is  recommended  that  automatic  detection  of  the  connected  load  be  performed. 
Selecting  an  incorrect  type  of  load  for  the  channel  may  damage  the  module  and  the 
connected load. 

You  can  combine  different  types  of  loads  within  the  lighting  groups  connected  to  one  channel. 
Resistive  (R)  and  inductive  (L)  loads,  as  well  as  resistive  (R)  and  capacitive  (C)  loads  can  be 
combined into groups. For detailed information, see the full manual. 

You  must  not  combine  inductive  loads  with  capacitive  ones.  Connecting  the  loads  of 
this type to one channel will damage the module. 

Содержание KNX-DIM21

Страница 1: ...channel dimming actuator Quick installation guide Full manual is available on www satel eu Firmware version 1 01 knx dim21_sii_en 12 19 SATEL sp z o o ul Budowlanych 66 80 298 Gda sk POLAND tel 48 58...

Страница 2: ...ized by the manufacturer shall void your rights under the warranty SATEL aims to continually improve the quality of its products which may result in changes in their technical specifications and softw...

Страница 3: ...ing light sources supplied with DC current as this might damage the module and the connected load load circuit terminals L1 L2 N LEDs to indicate channel status troubles and green red see Table 1 LED...

Страница 4: ...ress is being assigned by using the ETS program The address assignment can be activated manually with the button on the enclosure or remotely from the ETS program programming button to be used to assi...

Страница 5: ...ith a common neutral point 1 3 Enclosure The module occupies 4 units on the 35 mm DIN rail 2 Installation Disconnect power before making any electrical connections The module is designed for indoor in...

Страница 6: ...the module The module is supplied with voltage from the KNX bus and requires no additional power supply 4 Connect a computer running ETS program to the KNX bus and configure the module To configure t...

Страница 7: ...so forbidden Making connections as shown in Fig 5 I or 5 II may cause damage to the modules and the connected load 3 Restoring the module factory settings 1 Press simultaneously the four channel statu...

Страница 8: ...d 600 W VA Connections Maximum wire cross section 2 5 mm2 Maximum tightening torque 0 5 Nm KNX parameters Maximum time of reaction to telegram 20 ms Maximum number of communication objects 58 Maximum...

Отзывы: