The 

DIP-switch 8

 is used to enable/disable the recording of messages by means of built-in 

microphone: 
OFF – recording disabled; 
ON – recording enabled. 

5.  Installation and start-up 

Disconnect power before making any electrical connections. 

The INT-VMG module should be installed indoors, in rooms with normal air humidity. 
The description below is applicable to installation of the INT-VMG module which is to be used 
in conjunction with the INTEGRA alarm control panel. If messages are to be triggered by 
means of inputs, the input must be connected with wires to the outputs of the control devices. 
If the module does not have to be connected to the communication bus, skip the steps 2, 3, 
5, 8 and 9. 
1.  Secure the electronics board in the enclosure. 
2. Using the DIP-switches, set the module address and specify the number of messages to 

be triggered via the bus. 

3.  Connect the CLK, DTA and COM terminals with wires to the control panel expander bus. 

To make a connection, it is recommended to use an unscreened straight-through cable. 
When using the twisted-pair type of cable, the CLK (clock) and DTA (data) signals must 
not be sent through one twisted pair. The wires must be run in one cable. The cable 
length should not exceed 1000 m. If it exceeds 300 meters, it may be necessary to use 
several wires connected in parallel for each signal. 

4. Depending on your needs, connect the loudspeaker (to SPEAKER terminals), audio 

amplifier or headset (to LINE socket). 

5.  Connect the tamper contact wires of module enclosure to the TMP and COM terminals. If 

the module is not to monitor the tamper contact status, the TMP and COM terminals 
should be shorted. 

6.  Connect power leads to the +12 V and COM terminals. The supply voltage can be taken 

from the control panel or any power supply unit providing the 12 V DC output voltage. 

7.  Turn on the power supply. The LED designated EA will light up. 
8. Start the expander identification function in the control panel. The module will be 

recognized as an output expander. During the identification procedure, a suitable number 
of outputs and addresses in the system will be assigned to the module. 

9.  Program appropriately the alarm system outputs assigned to the module: 

  select the output function, i.e. specify the circumstances in which the message is to be 

played back; 

  make sure that the "Polarity" option is enabled for the output (if the polarity is 

reversed, the message will not be played back properly); 

  if the message is to be played repeatedly, enable the "Pulsation" option (the message 

will be played as many times, as the output is activated within the preset "Cut-off 
time"). 

Содержание INT-VMG

Страница 1: ...A Maximum current consumption 500 mA Recommended impedance of loudspeaker connected to SPEAKER terminals 8 Ω Maximum power of speaker output 6 W Environmental class according to EN50130 5 II Operating temperature range 10 55 C Maximum humidity 93 3 Dimensions of electronics board 68 x 140 mm Weight 80 g The declaration of conformity may be consulted at www satel eu ce 3 Functional description The ...

Страница 2: ... is assigned to each LED LED is ON see Table 1 LED is OFF 0 The sum of these numerical values corresponds to the message number The messages are numbered from 0 to 31 LED M4 M3 M2 M1 M0 Number 16 8 4 2 1 Table 1 Numbers assigned to the LEDs which are lit ON mini jack socket for connecting a headset or an external audio amplifier connector for future applications connector used in the production pr...

Страница 3: ...in the module if it is connected to the control panel communication bus A number is assigned to each DIP switch in the ON position see Table 2 in the OFF position 0 The sum of these numbers corresponds to the set address These switches allow you to set an address within the range from 0 to 31 DIP switch number 1 2 3 4 5 Number 1 2 4 8 16 Table 2 Numbers assigned to DIP switches in ON position The ...

Страница 4: ...able length should not exceed 1000 m If it exceeds 300 meters it may be necessary to use several wires connected in parallel for each signal 4 Depending on your needs connect the loudspeaker to SPEAKER terminals audio amplifier or headset to LINE socket 5 Connect the tamper contact wires of module enclosure to the TMP and COM terminals If the module is not to monitor the tamper contact status the ...

Страница 5: ...SATEL INT VMG 5 ...

Страница 6: ... down the PLAY button for about 2 seconds The LEDs shown in Figure 3 will blink three times and then will present the currently set volume the more LEDs light up the higher the volume all LEDs are lit the maximum volume no LED is lit the minimum volume 2 Press the NEXT button repeatedly until the desired volume is set 3 Press the PLAY button to exit the volume control function The function will en...

Страница 7: ... Windows system will automatically detect the connection of a new device and will launch the wizard that will guide you through the procedure of installation of drivers for your new hardware The drivers can be downloaded from www satel eu Some versions of the Windows operating system may give you a warning that the driver has not passed the compatibility test Despite these warnings installation of...

Страница 8: ...SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel eu ...

Отзывы: