or the entered telephone number is not consistent with that programmed in the control 
panel, the module will not be receiving events sent by the control panel. 

Extended kiss-off

 – some control panels require long acknowledgement of receiving the 

code in Contact ID format. By default, to speed up communication, a short kiss-off 
signal is used in the module. The option is available after selecting the Contact ID 
format. 

4.6.1.2  “Monitored events” tab 

If the box at chosen event is selected, occurrence of the event (and, in case of troubles, 
also the end of trouble) will result in sending codes defined in the “Event codes” tab to the 
monitoring station. The following events can be monitored: 

Internal events: 

– Module restart 
– Power supply failure (the trouble is reported with a delay, as defined in the 

“Inputs/Outputs” tab) 

–  Power supply restore 
– Low battery 
– Battery OK 
–  Loss of communication with Station 1 
– Restore of communication with Station 1 
–  Loss of communication with Station 2 
– Restore of communication with Station 2 
–  Test transmission (this event requires defining test transmission rules) 
–  Supply output overload 
–  End of supply output overload 

Inputs restore: 

–  Inputs 1 – 8. 

Outputs turning off 

–  Outputs 1 – 4. 

4.6.1.3  “Event codes” tab 

The tab makes it possible to define codes for the module generated events. 
For the 4/2 format, all codes can be defined. For the Contact ID format and SIA, the codes 
are factory defined. 

Contact ID 

The user can change the codes of events generated after violation of the module inputs 
and after activation of the outputs. Defining the code to be sent on input violation/output 
activation will automatically generate a code which will be sent at the input end of 
violation/output deactivation. You can enter the new Contact ID code manually or use the 
code editor. To open the code editor window, click on the button marked with three dots. 

SIA 

The user can change the codes of events generated on input violation / end of violation 
and output activating / deactivating. You can also add a comment to all the generated 
events, including the system ones, which will be send with an appropriate code 
immediately on sending the main event. You can enter the new SIA code manually or you 
can make use of the code editor. To open the code editor window, click on the button 
designated with three dots. 

Содержание ETHM-2

Страница 1: ...Ethernet Module ETHM 2 Firmware version 2 00 ethm2_en 05 15 FreeRTOS is used in this product www freertos org SATEL sp z o o ul Budowlanych 66 80 298 Gdańsk POLAND tel 48 58 320 94 00 www satel pl ...

Страница 2: ... improve the quality of its products which may result in alteration of their technical specifications and firmware Current information on the introduced modifications is available on our website Please visit us at http www satel eu ...

Страница 3: ...rmat and report them to the monitoring station through Ethernet with the use of TCP IP protocols Acknowledgment of event receipt Buffer for 512 received events Coded event transmission 8 inputs 4 outputs Remote control of output status Power supply output Monitoring of the status of inputs outputs power supply communications etc by means of codes sent through Ethernet network to 2 monitoring stati...

Страница 4: ... with 16 V 10 alternating voltage 2 LED whose blinking indicates the module status lights up for a short while the device operation is normal blinking regularly at a slow rate configuration data memory error blinking regularly at a fast rate module firmware update running 3 CR2032 3 V battery for backup of the real time clock 4 RJ 45 socket for connecting the module to Ethernet network 100Base TX ...

Страница 5: ...h on 230 V AC power supply in the circuit to which the transformer is connected Measure the voltage across the battery leads the correct value should be between 13 6 and 13 8 V DC 3 Switch off 230 V AC power supply 4 Connect the battery The module will not start on connecting the battery alone 5 Switch on 230 V AC power supply The module is now ready for operation Notes A battery voltage drop belo...

Страница 6: ...on the Apply button Close and restart the program 3 The login window will be displayed Enter in the fields the user name by default service see section LOGGING DETAIL p 6 the password by default service see section LOGGING DETAIL p 6 4 Click on the Login button The data from the module will be downloaded automatically 5 Configure the module settings as required 6 Save the data to the module 4 2 VI...

Страница 7: ...ng the status of communication with the module green color the program is connected to the module gray color no connection with the module 6 field enabling selection of the computer COM port through which communication with the module will be effected 7 button enabling communication with the module to be switched on off 8 information on the progress of writing reading data 9 icon indicating troubl...

Страница 8: ...t mask mask of the subnet in which the module operates Default gateway net gateway i e IP address of the network device through which the other devices in the given local network communicate with devices in other networks Obtain DNS server address automatically select this option if the DNS server network address is to be automatically obtained from DHCP server Use the DNS server address select th...

Страница 9: ...y month when the module clock will be changed to winter time i e shifted back Time zone enter in this field the time zone i e the difference between the universal time UTC and the zone time Time synchronization if this box is selected the module will automatically synchronize its clock with the time server once a day and just after a restart In the event of failure the module will be repeating the...

Страница 10: ...am language 4 6 REPORTING TAB 4 6 1 Station 1 Station 2 Active select the box if the events are to be sent to the chosen monitoring station 4 6 1 1 Common tab Reporting format Selection of the reporting format only applies to the event codes generated by the module input monitoring troubles etc The events received through telephone line are sent to the monitoring station in the same format in whic...

Страница 11: ...enerated events will be sent inputs monitoring troubles etc SIA prefix select this box to activate the field for entering 2 characters which will precede the System identifier in case of the SIA format Thus you can obtain an identifier consisting of 6 characters 2 hexadecimal characters digits or letters from A to F should be programmed If you enter 00 no prefix will be added Using the digit 0 in ...

Страница 12: ...quires defining test transmission rules Supply output overload End of supply output overload Inputs restore Inputs 1 8 Outputs turning off Outputs 1 4 4 6 1 3 Event codes tab The tab makes it possible to define codes for the module generated events For the 4 2 format all codes can be defined For the Contact ID format and SIA the codes are factory defined Contact ID The user can change the codes of...

Страница 13: ...d to the module Entering 0 in the fields Days and Hours means that no event will be generated Note The Test transmission event is generated irrespective of whether it is to be sent to the monitoring station or not Disabling the feature of generating this type of events is only possible in the After time transmission 4 7 INPUTS OUTPUTS TAB 4 7 1 Inputs The following parameters can be defined for ea...

Страница 14: ...er the counter If the number of violations indicated in the Bypass after field occurs during that time the input will be bypassed If the indicated number of violations does not occur the counter will be reset The time can be programmed in seconds up to 255 seconds or minutes up to 255 minutes Entering 0 means that the counter of violations will not be reset Fig 8 Inputs outputs tab 4 7 2 Bypassed ...

Страница 15: ...TP server SMTP server enter in this field the SMTP server address outgoing mail server SMTP Port enter in this field the SMTP port number the outgoing mail port Server requires authorization select this box if the SMTP server requires authentication If this box is checked you can define whether the outgoing mail is to be encrypted By default the No encryption option is selected SSL TLS and STARTTL...

Страница 16: ...ule and those received through the telephone line The latter are designated by the symbol displayed in the Tel column Shown in the S1 S2 and M columns is information on the event status The symbols have the following meaning event code e mail message has been sent event code e mail message is waiting to be sent sending the event code e mail message has been cancelled ETHM 2 module user has disable...

Отзывы: