installer manual). The sticker with 7-digit serial number which shall be entered when
registering the detector in the system can be found on the electronics board.
3. Close the detector enclosure.
4. Fasten the detector temporarily at the place of its future installation.
5. Check the level of signal received from the detector by the ACU-100 / ACU-250 /
ACU-120 / ACU-270 controller or the INTEGRA 128-WRL control panel. If the signal level
is lower than 40%, select another place for installation. Sometimes, it is sufficient to shift
the device ten or twenty centimeters to obtain a considerable improvement in the signal
quality.
6. Open the detector enclosure (Fig. 2).
7. Pull the flood sensor wires through the hole in the enclosure and screw
them to the terminals on the electronics board.
8. Use screws to fix the enclosure base to the mounting surface (Fig. 4).
9. Close the detector enclosure.
10. Configure the detector according to your requirements. For information
about the configuration, see the ABAX wireless system controller
manual.
11. Launch remotely the test mode and carry out functional test of the
detector by submerging the flood sensor in water.
12. Quit the test mode.
13. Secure the flood sensor wires and the flood sensor itself (Fig. 5). The
detector is now ready for work.