Chapter 4 PAS Application Software
Configuring Communication Protocols
Series PM172 Powermeters
95
Parameter Options Default
Description
Analog Input
Change Event
Object
32-bit -Time
32-bit +Time
16-bit -Time
16-bit +Time
16-bit +Time The default AI change event object
variation for requests with qualifier code
06 when no specific variation is
requested
Binary Counters (BC)
Number of BC
to Generate
events
0-64
3
0
The total number of BC change event
points for monitoring
Binary Counter
Object
32-bit +Flag
32-bit –Flag
16-bit +Flag
16-bit –Flag
32-bit -Flag
The default BC object variation for
requests with qualifier code 06 when no
specific variation is requested
Binary Counter
Change Event
Object
32-bit -Time
32-bit +Time
16-bit -Time
16-bit +Time
32-bit +Time The default BC change event object
variation for requests with qualifier code
06 when no specific variation is
requested
Frozen Binary
Counter Object
32-bit +Flag
32-bit –Flag
32-bit +Time
16-bit +Flag
16-bit –Flag
16-bit +Time
32-bit -Flag
The default frozen BC object variation
for requests with qualifier code 06 when
no specific variation is requested
DNP General Options
16-bit AI
Scaling
Disabled
Enabled
Enabled Allows
scaling 16-bit analog input
objects (see description below)
16-bit BC
Scaling
x1, x10, x100,
x1000
x1
Allows scaling 16-bit binary counter
objects (see description below)
Re-mapping
Event Points
Disabled
Enabled
Disabled
Allows re-mapping event points starting
with point 0.
SBO Timeout
1
2-30 sec
10
Defines the Select Before Operate
(SBO) timeout when using the Control-
Relay-Output-Block object
Time Sync
Period
2
0-86400 sec
86400
Defines the time interval between
periodic time synchronization requests
Multi Fragment
Interval
5-500 ms
50
Defines the time interval between
segments of the response message
when it is fragmented
1
The Select Before Operate command causes the device to start a timer. The following
Operate command must be sent before the specified timeout value expires.
2
The device requests time synchronization by bit 4 in the first octet of the internal
indication word being set to 1 when the time interval specified by the Time Sync
Period elapses. The master should synchronize the time in the device by sending the
Time and Date object to clear this bit. The device does not send time synchronization
requests if the Time Sync Period is set to 0.
3
The total number of AI, BI and BC change event points may not exceed 64. When
you change the number of the change event points in the device, all event
setpoints are set to defaults (see Configuring DNP Event Classes below).
Scaling 16-bit AI objects
Scaling 16-bit AI objects allows accommodating native 32-bit analog input
readings to 16-bit object format; otherwise it may cause an over-range error
if the full-range value exceeds a 16-bit point limit.
Scaling is enabled by default. It is not applied to points that are read using
32-bit AI objects.
Refer to the PM172 DNP3 Reference Guide for information on the data point
scales and on a reverse conversion that should be applied to the received
scaled values.
Scaling 16-bit Binary Counters
Scaling 16-bit Binary Counters allows changing a counter unit in powers of
10 to accommodate a 32-bit counter value to 16-bit BC object format.