Chapter 3 Operating the ETC ONE PLUS
ETC I Communication Setup
ETC ONE PLUS Network Communicator
17
2.
Define the TCP service port number for your application protocol.
Display Label
Parameter
Default
IP Address
Device IP Address
192.168.0.203
Subnet Mask
Network Subnet Mask
255.255.255.0
Def. Gateway
Network Default Gateway
192.168.0.1
TCP Service Port
502 = Modbus/TCP
502
NOTE:
If your ETC ONE PLUS has both the Ethernet and modem network interfaces,
the eXpertPower client uses one of these for connections to the
eXpertPower
TM
server. The default Ethernet network gateway address
defines which one of the networks is used. If the default gateway address is
not defined (i.e., it is set to 0.0.0.0), the ETC ONE PLUS uses the dial-out
modem connection via your local Internet provider. If you defined the default
network gateway address, any call to the IP address, which is not included in
the address space of the both networks, is redirected to the default Ethernet
gateway.