background image

11/99

7 - 10

DS 3.401

COMMISSIONING

WARNING -
WHEN ACTUATOR IS OPERATING BEWARE OF TRAPPING
FINGERS ETC.

BEFORE SWITCHING ON POWER SUPPLY:

ALM and ALX Actuators

1.

Check that all control equipment is correctly located and fitted.

2.

Check ambient temperature conditions.

3.

Check that actuator has been correctly assembled to valve, up to
the stage when electrical power is called for.

4.

Remove terminal cover and check that all control circuit wiring is
correct and in accordance with the overall control system wiring
diagram. Check that the electrical supply voltage is correct.

5.

Note: Wiring errors not only cause malfunctions; they may also
damage controllers and/or actuators.

6.

Replace terminal cover. Set manual override push button to 'Auto'
position.

7.

Now switch on power supply.

8.

Check that the actuator functions correctly by operating the
controlling switch or adjusting the controller set value above and
below the temperature (or humidity) currently existing at the sensor
(or simulated). This must be within the scale limits.

If the actuator forms part of a multi-stage system in which several
actuators operate in sequence, wait until the appropriate stage is
reached.

9.

Whilst checking actuator travel over full stroke of valve, run
actuator to fully retracted position. Select self-adhesive indication
scale to match valve stroke, from set of four scales provided. Fix
scale along outside edge of actuator mounting bracket, in position
where it will be most clearly visible, lining up top edge of anti-
rotation plate on actuator spindle with position '0' on scale (Fig.7).

10. If auxiliary switches are fitted, remove terminal cover to check for

correct operation and switching functions. Replace terminal cover.

ALM, ALX WIRING PRECAUTIONS

WARNING -
ALM ACTUATORS AND AUXILIARY SWITCHES (WHERE FITTED)
ARE AT MAINS POTENTIAL. OBSERVE LOCAL WIRING
REGULATIONS, EARTHING REQUIREMENTS AND ALL USUAL
SAFETY PRECAUTIONS.

* When wiring to BAS outstations refer to the appropriate outstation
data sheet for the wiring precautions.

For longer lengths, increase cable size and observe max. resistance.
Screen feedback wiring, or use MICC or run in a separate conduit,
when applicable.

Caution
Do not connect ALM or ALX actuators in parallel.

ALE Actuators

BEFORE SWITCHING ON POWER SUPPLY:

Check that all control equipment is correctly located and fitted.

Check ambient temperature conditions.

Check that actuator has been correctly assembled to valve, up to the
stage when electrical power is called for.

Remove terminal cover and check that all control circuit wiring is
correct and in accordance with the overall control system wiring
diagram. Check that the electrical supply voltage is correct.

Note: Wiring errors not only cause malfunctions; they may also
damage controllers and/or actuators.

Setting the Actuator

The following instructions MUST be followed to initially set the actuator
stroke and each time the actuator is transferred to a different valve.

Set all adjustments as follows (see Fig.8):

1.

Set manual override push button to 'auto' position.

2.

Remove wire from terminal 9, ensuring a 0Vdc supply.

3.

Switch on 24V supply. The actuator drive screw will run until it is
fully retracted (position 0) operating its limit switch.

4.

Wait until the drive screw has stopped moving before continuing.

5.

Loosen the pot fixing screw 'H'. By sliding the pot assembly
towards you, disengage gear 'E' from the main drive shaft. Turn the
pot gear 'E' by hand in the anti-clockwise direction (when viewed
from above) until the end stop is reached. Gently slide the pot
assembly back into position so that the pot gear 'E' engages with
the main drive shaft. Do not apply too much force in meshing the
gears as over pressure will result in reduced life. Re-tighten the
location fixing screw 'H'.

6.

Check that the voltage between terminal 7 and 11 is 0.1V ±100mV.

7.

Reconnect wire to terminal 9.

8.

Adjust controller set value to give 10Vdc output.

9.

Check that the Voltage between terminals 7 and 9 is approximately
10Vdc.

10. Change the 'START' setting from '10' to '0'. The actuator drive

screw will now run until it is fully extended (position 10).

11. Wait until the drive screw has stopped moving before continuing.

12. Adjust the 'STROKE' setting in an anti clockwise direction until

Voltage measured between terminals 7 and 11 is 9.9V ±100mV.

13. Select and fix the appropriate self-adhesive stroke indication label

to the actuator bracket. The relevant stroke length can be found on
the appropriate Satchwell data sheet for the valve being used.

14. Re-set 'START', 'SPAN' and 'DA/RA' adjustments as required, to

suit control system. DO NOT alter 'STROKE' setting. Re-check
operation by adjusting controller set value so that actuator runs to
position '0'. If limit switch does not operate, adjust 'START' setting
very slightly anti-clockwise for 'DA' switch mode (clockwise for 'RA'
switch mode) until limit switch does operate. Now adjust controller
set value so that actuator runs to position '10'. If limit switch does
not operate, adjust 'STROKE' setting very slightly clockwise for DA
and anti-clockwise for RA until limit switch does operate. Re-adjust
controller set value as required, to suit control system.

Wiring from actuator
to controller*:

Max. length of 1.5mm²

cable unscreened

Max. resistance

per conductor

24V/240V~ Supply

100m

5

Fig.7

Adjustment

Setting

START 'C'

10

SPAN 'D'

10

STROKE 'A'

max. (fully clockwise)

DA/RA SWITCH 'B'

+ (DA)

HYSTERESIS JUMPER 'G' A-B or B-C

Fig.8

Содержание ALE 1302

Страница 1: ...operate a low hysteresis when used for tight control applications on microprocessor based controllers such as the KMC and MMC FEATURES Direct coupling to Satchwell seat valves without extra mounting brackets or linkage kits saving site time Direct coupling to other makes of seat valves where stroke thrust and mounting are compatible Universal for valve strokes up to 38mm 1 Actuator stroke is self ...

Страница 2: ...31 1 211 INPUT CONTROL SIGNAL for modulation Pulsed Mains 220 to 240Vac Voltage Pulsed 24V 0 10Vdc APPLICATION Two position control from thermostat time switch or other switching device having 220 240Vac mains rated changeover contacts Modulating control from any controller having a 3 wire mains output 220 to 240Vac Modulating control from any controller having a pulsed 24V output Modulating contr...

Страница 3: ...to 10 representing 0 to 100 stroke Fix scale to suit valve stroke see Commissioning Limit Transfer Switches ALM ALX Load dependent switches self adjusting to match valve stroke Control signal transfers from terminal 1 to 1T and 2 to 2T at respective limits of valve stroke not electrically separate ALE Limit switches operate as for other actuators but are internally connected between electronics ca...

Страница 4: ...ller having a 0 10Vdc output Using the START and SPAN adjustments the actuator can be set to make a complete stroke over any span from 4 to 10 volts starting at any point within the signal range providing the sum of START Volts plus SPAN Volts does not exceed 10 The load dependent limit switches operate basically as described for the ALM and ALX but are internally connected between the electronics...

Страница 5: ...upling E to suit valves with diameter spindle only Adaptor A is not applicable 2 Remove lug nut C from valve bonnet locate actuator mounting bracket over valve bonnet replace lug nut and tighten with actuator correctly positioned to give clear access for conduit entry and wiring 3 For size 125 and 150mm valves remove and discard lug nut and fix actuator mounting bracket to valve bonnet using the f...

Страница 6: ...ocating holes provided and tighten fixing screws 5 Note that micro switches are adjustable one S1 S2 S3 between actuator positions 0 and 5 the other S4 S5 S6 between positions 5 and 10 6 To adjust the switches energise actuator if commissioning in progress at correct voltage and run to position at which one switch is required to operate Alternatively use manual operator facility 7 Loosen micro swi...

Страница 7: ...ntrol system wiring diagram Check that the electrical supply voltage is correct Note Wiring errors not only cause malfunctions they may also damage controllers and or actuators Setting the Actuator The following instructions MUST be followed to initially set the actuator stroke and each time the actuator is transferred to a different valve Set all adjustments as follows see Fig 8 1 Set manual over...

Страница 8: ...G REQUIREMENTS AND ALL USUAL SAFETY PRECAUTIONS When wiring to BAS outstations refer to the appropriate outstation data sheet for the wiring precautions For longer lengths of 24 Volt supply wiring increase cable size and observe maximum resistance also run separate return from terminal 7 as Fig 12 Terminals 7 and 10 are both at ground potential provided for convenience of wiring Where screening is...

Страница 9: ...Y A TRANSFORMER CONFORMING TO EN 60742 Fig 10 Fig 11 Controller Auxiliary Switch ALE 1352 only S4 makes to S6 at position 0 Non adjustable WARNINGS AUXILIARY SWITCHES MAY BE AT MAINS POTENTIAL MAINS VOLTAGE ISOLATORS MUST CONFORM TO EN 60335 1 24VAC DEVICES MUST BE SUPPLIED BY A TRANSFORMER CONFORMING TO EN 60742 Fig 12 WARNINGS AUXILIARY SWITCHES MAY BE AT MAINS POTENTIAL MAINS VOLTAGE ISOLATORS ...

Страница 10: ...erve installation instructions on page 5 Observe wiring precautions on page 7 Do not apply power unless the actuator is fitted to a valve Do not switch on power supply until commissioning checks have been completed see page 7 Ensure wires are not inadvertently crossed over Wiring errors not only cause malfunctions they may also damage controllers and or actuators Steam Applications Following a shu...

Отзывы: