INSTALLATION

Observe the following IMPORTANT points:

WARNINGS -
WHEN OPERATING A VALVE HANDLING FLUID ABOVE 100°C, DO
NOT MOUNT ACTUATOR ABOVE VALVE, BUT TO ONE SIDE.

WHEN ACTUATOR IS OPERATING BEWARE OF TRAPPING
FINGERS ETC.

Do not switch on power supply until commissioning checks have
been completed - see page 7.

Steam Applications: Following a shutdown of the steam system
it is important that the control valve is fully open before
introducing steam into the pipeline (purging) or damage may
occur to the actuator spindle or valve plug.

Do not apply power unless the actuator is fitted to a valve.

Ambient temperature must be within limits -20 to 50°C.

Do not install valve with actuator directly underneath it.

Allow sufficient clearance for fitting and wiring, also minimum of
110mm between manual operator knob and nearest obstruction.

Complete mechanical fitting of actuator to valve BEFORE
connecting electrical wiring. This avoids damage which may occur,
due to load-dependent limit switches not being operated.

Ensure location is reasonably clean and dry.

Note: The following diagrams are typical internal views (ALX 1251
and ALE 1352 are not shown).

ACTUATOR FITTING INSTRUCTIONS

1.

a.

Actuators ALM 1601, ALX 1201 and ALE 1302, 1327, 1376 are supplied
with adaptor 'A' fitted, for direct coupling to valves with ¼" diameter spindle.
When coupling any of these actuators to valves with

3

/

8

" diameter spindle,

first loosen locknut 'F' then remove and discard adaptor 'A'.

b.

Actuators ALX 1251 and ALE 1352 have coupling 'E' to suit valves with ¼"
diameter spindle only. Adaptor 'A' is not applicable.

2.

Remove lug nut 'C' from valve bonnet, locate actuator mounting bracket over
valve bonnet, replace lug nut and tighten, with actuator correctly positioned to
give clear access for conduit entry and wiring.

3.

For size 125 and 150mm valves, remove and discard lug nut and fix actuator
mounting bracket to valve bonnet, using the four screws 'D' supplied.

4.

Lift valve spindle into actuator coupling 'E' or adaptor 'A', as applicable and
screw on fully. Do not over-tighten. Lock using nut 'B' supplied. Use manual
operator to position coupling 'E' to required extension, as necessary,
particularly when assembling to small size valves, but avoid over-extending or
retracting actuator spindle to prevent malfunction or damage.

5.

If subsequently removing the actuator to service valve gland, for example, it is
IMPORTANT to isolate power supply to controller or actuator or otherwise
select the 'Manual' position on the manual operator push button. This will avoid
malfunction or damage due to actuator spindle being accidentally driven
beyond its normal stroke limits.

WIRING

1.

Remove cover 'A' and conduit plate 'B' (see Fig.3). Fit flexible
conduit to plate, allowing sufficient length to permit removal of the
actuator.

2.

Connect cables in accordance with system wiring diagram or refer to
diagram inside cover in conjunction with controller diagram. Earth
actuator, where applicable, using the top (ALM, ALX) or bottom
(ALE) terminal screw. Observe 'Wiring precautions' (page 7). Keep
wiring clear of internal moving parts.

3.

Replace conduit plate and cover.

Caution
Do not switch on power supply until commissioning checks 1 to 6
have been completed.

Fig.2

WARNING
LABEL

Fig.3

A

Содержание ALE 1302

Страница 1: ...operate a low hysteresis when used for tight control applications on microprocessor based controllers such as the KMC and MMC FEATURES Direct coupling to Satchwell seat valves without extra mounting brackets or linkage kits saving site time Direct coupling to other makes of seat valves where stroke thrust and mounting are compatible Universal for valve strokes up to 38mm 1 Actuator stroke is self ...

Страница 2: ...31 1 211 INPUT CONTROL SIGNAL for modulation Pulsed Mains 220 to 240Vac Voltage Pulsed 24V 0 10Vdc APPLICATION Two position control from thermostat time switch or other switching device having 220 240Vac mains rated changeover contacts Modulating control from any controller having a 3 wire mains output 220 to 240Vac Modulating control from any controller having a pulsed 24V output Modulating contr...

Страница 3: ...to 10 representing 0 to 100 stroke Fix scale to suit valve stroke see Commissioning Limit Transfer Switches ALM ALX Load dependent switches self adjusting to match valve stroke Control signal transfers from terminal 1 to 1T and 2 to 2T at respective limits of valve stroke not electrically separate ALE Limit switches operate as for other actuators but are internally connected between electronics ca...

Страница 4: ...ller having a 0 10Vdc output Using the START and SPAN adjustments the actuator can be set to make a complete stroke over any span from 4 to 10 volts starting at any point within the signal range providing the sum of START Volts plus SPAN Volts does not exceed 10 The load dependent limit switches operate basically as described for the ALM and ALX but are internally connected between the electronics...

Страница 5: ...upling E to suit valves with diameter spindle only Adaptor A is not applicable 2 Remove lug nut C from valve bonnet locate actuator mounting bracket over valve bonnet replace lug nut and tighten with actuator correctly positioned to give clear access for conduit entry and wiring 3 For size 125 and 150mm valves remove and discard lug nut and fix actuator mounting bracket to valve bonnet using the f...

Страница 6: ...ocating holes provided and tighten fixing screws 5 Note that micro switches are adjustable one S1 S2 S3 between actuator positions 0 and 5 the other S4 S5 S6 between positions 5 and 10 6 To adjust the switches energise actuator if commissioning in progress at correct voltage and run to position at which one switch is required to operate Alternatively use manual operator facility 7 Loosen micro swi...

Страница 7: ...ntrol system wiring diagram Check that the electrical supply voltage is correct Note Wiring errors not only cause malfunctions they may also damage controllers and or actuators Setting the Actuator The following instructions MUST be followed to initially set the actuator stroke and each time the actuator is transferred to a different valve Set all adjustments as follows see Fig 8 1 Set manual over...

Страница 8: ...G REQUIREMENTS AND ALL USUAL SAFETY PRECAUTIONS When wiring to BAS outstations refer to the appropriate outstation data sheet for the wiring precautions For longer lengths of 24 Volt supply wiring increase cable size and observe maximum resistance also run separate return from terminal 7 as Fig 12 Terminals 7 and 10 are both at ground potential provided for convenience of wiring Where screening is...

Страница 9: ...Y A TRANSFORMER CONFORMING TO EN 60742 Fig 10 Fig 11 Controller Auxiliary Switch ALE 1352 only S4 makes to S6 at position 0 Non adjustable WARNINGS AUXILIARY SWITCHES MAY BE AT MAINS POTENTIAL MAINS VOLTAGE ISOLATORS MUST CONFORM TO EN 60335 1 24VAC DEVICES MUST BE SUPPLIED BY A TRANSFORMER CONFORMING TO EN 60742 Fig 12 WARNINGS AUXILIARY SWITCHES MAY BE AT MAINS POTENTIAL MAINS VOLTAGE ISOLATORS ...

Страница 10: ...erve installation instructions on page 5 Observe wiring precautions on page 7 Do not apply power unless the actuator is fitted to a valve Do not switch on power supply until commissioning checks have been completed see page 7 Ensure wires are not inadvertently crossed over Wiring errors not only cause malfunctions they may also damage controllers and or actuators Steam Applications Following a shu...

Отзывы: