DS 3.401

11/99

ALM, ALX, ALE

An Invensys company

LINEAR ACTUATORS

Specification no. 477-X-XXX

Satchwell Linear Actuators type 'AL' are reversing actuators having a
linear output, for direct coupling to Satchwell lift and lay seat-type
control valves or other seat valves requiring a linear driver over stroke
lengths of up to 38mm (1½"), within the limits of output thrust stated
overleaf and with compatible mounting arrangements.

These actuators are suitable for either two-position or modulating
control, dependent on the controller or other switching device providing
the input signal. The ALM is suitable for a mains power supply, the ALX
is 24V, and the ALE is 24V, but accepts a 0-10Vdc input signal.

The ALE actuator can be set to operate a low hysteresis when used for
tight control applications on microprocessor based controllers such as
the KMC and MMC.

FEATURES

Direct coupling to Satchwell seat valves without extra
mounting brackets or linkage kits, saving site time

Direct coupling to other makes of seat valves, where stroke,
thrust and mounting are compatible

Universal for valve strokes, up to 38mm (1½"). Actuator stroke
is self-setting to suit valve stroke, including ALE by simple
adjustment

Alternative stroke times, to suit application

Manual operation or override facility built-in

Standard or low hysterisis selection on ALE to cater for
different application types

Case sealed to IP 54 as standard

Auxiliary switch kit available, see 'Accessories'

† For the full specification number replace the 4Xs with the

appropriate figures from the 'TYPE' column in the table
on page 2.

MLI 3.401 - Mounting Instructions
Valves
DS 4.410 - VZ, VSF, VZF
DS 4.610 - MZ, MJF, MZF

Содержание ALE 1302

Страница 1: ...operate a low hysteresis when used for tight control applications on microprocessor based controllers such as the KMC and MMC FEATURES Direct coupling to Satchwell seat valves without extra mounting brackets or linkage kits saving site time Direct coupling to other makes of seat valves where stroke thrust and mounting are compatible Universal for valve strokes up to 38mm 1 Actuator stroke is self ...

Страница 2: ...31 1 211 INPUT CONTROL SIGNAL for modulation Pulsed Mains 220 to 240Vac Voltage Pulsed 24V 0 10Vdc APPLICATION Two position control from thermostat time switch or other switching device having 220 240Vac mains rated changeover contacts Modulating control from any controller having a 3 wire mains output 220 to 240Vac Modulating control from any controller having a pulsed 24V output Modulating contr...

Страница 3: ...to 10 representing 0 to 100 stroke Fix scale to suit valve stroke see Commissioning Limit Transfer Switches ALM ALX Load dependent switches self adjusting to match valve stroke Control signal transfers from terminal 1 to 1T and 2 to 2T at respective limits of valve stroke not electrically separate ALE Limit switches operate as for other actuators but are internally connected between electronics ca...

Страница 4: ...ller having a 0 10Vdc output Using the START and SPAN adjustments the actuator can be set to make a complete stroke over any span from 4 to 10 volts starting at any point within the signal range providing the sum of START Volts plus SPAN Volts does not exceed 10 The load dependent limit switches operate basically as described for the ALM and ALX but are internally connected between the electronics...

Страница 5: ...upling E to suit valves with diameter spindle only Adaptor A is not applicable 2 Remove lug nut C from valve bonnet locate actuator mounting bracket over valve bonnet replace lug nut and tighten with actuator correctly positioned to give clear access for conduit entry and wiring 3 For size 125 and 150mm valves remove and discard lug nut and fix actuator mounting bracket to valve bonnet using the f...

Страница 6: ...ocating holes provided and tighten fixing screws 5 Note that micro switches are adjustable one S1 S2 S3 between actuator positions 0 and 5 the other S4 S5 S6 between positions 5 and 10 6 To adjust the switches energise actuator if commissioning in progress at correct voltage and run to position at which one switch is required to operate Alternatively use manual operator facility 7 Loosen micro swi...

Страница 7: ...ntrol system wiring diagram Check that the electrical supply voltage is correct Note Wiring errors not only cause malfunctions they may also damage controllers and or actuators Setting the Actuator The following instructions MUST be followed to initially set the actuator stroke and each time the actuator is transferred to a different valve Set all adjustments as follows see Fig 8 1 Set manual over...

Страница 8: ...G REQUIREMENTS AND ALL USUAL SAFETY PRECAUTIONS When wiring to BAS outstations refer to the appropriate outstation data sheet for the wiring precautions For longer lengths of 24 Volt supply wiring increase cable size and observe maximum resistance also run separate return from terminal 7 as Fig 12 Terminals 7 and 10 are both at ground potential provided for convenience of wiring Where screening is...

Страница 9: ...Y A TRANSFORMER CONFORMING TO EN 60742 Fig 10 Fig 11 Controller Auxiliary Switch ALE 1352 only S4 makes to S6 at position 0 Non adjustable WARNINGS AUXILIARY SWITCHES MAY BE AT MAINS POTENTIAL MAINS VOLTAGE ISOLATORS MUST CONFORM TO EN 60335 1 24VAC DEVICES MUST BE SUPPLIED BY A TRANSFORMER CONFORMING TO EN 60742 Fig 12 WARNINGS AUXILIARY SWITCHES MAY BE AT MAINS POTENTIAL MAINS VOLTAGE ISOLATORS ...

Страница 10: ...erve installation instructions on page 5 Observe wiring precautions on page 7 Do not apply power unless the actuator is fitted to a valve Do not switch on power supply until commissioning checks have been completed see page 7 Ensure wires are not inadvertently crossed over Wiring errors not only cause malfunctions they may also damage controllers and or actuators Steam Applications Following a shu...

Отзывы: