ECO MULTI SYSTEM Unit Specifications
SM830052
I - 13
1
1-4. Other component specifications
1. Outdoor Unit
MODEL No.
Outdoor Unit
SPW – C483GYH8 / SPW – C483GY8
Power Transformer
ATR-195, CL-4
Thermostat
Available
Cooling
18 – 30
°
C
(Option)
setting temp.
Dry
18 – 30
°
C
Heating
16 – 26
°
C
Thermistor (Coil sensor)
PBC-41E-S36
Coil resistance
K
Ω
–10 ˚C : 23.7
±
5 %
,
20 ˚C : 6.5
±
5 %
–5 ˚C : 18.8
±
5 %
,
30 ˚C : 4.4
±
5 %
0 ˚C : 15.0
±
5 %
,
40 ˚C : 3.1
±
5 %
5 ˚C : 12.1
±
5 %
,
45 ˚C : 2.6
±
5 %
10 ˚C : 9.7
±
5 %
Thermistor (Discharge gas sensor
PTC-51H
or coil sensor)
Coil resistance
K
Ω
60 ˚C : 13.8
±
5 %
,
90 ˚C : 5.1
±
5 %
70 ˚C :
9.7
±
5 %
, 100 ˚C : 3.8
±
5 %
75 ˚C :
8.2
±
5 %
, 110 ˚C : 2.8
±
5 %
80 ˚C :
7.0
±
5 %
, 120 ˚C : 2.2
±
5 %
85 ˚C :
5.9
±
5 %
, 130 ˚C : 1.7
±
5 %
Relay
FMCA-1SZ607
Coil rated
V
AC 220 V - 240 V
Contact rating
V.A
AC 440 V, 13 A
Coil Resistance (at 25 ˚C)
k
Ω
—
Solenoid control valve or coil
Solenoid control valve
NEV603DXFa19 / NEV202DXFa19
Solenoid coil
NEV-MOAJ50B0
Reversing valve or coil
(only heat pump type)
Reversing valve
CHV-0401
Solenoid coil
CHV-01AJ504D1